185
CHECK PROCEDURE
Symptom #1 Machine is off and the display indicates
“Delay xx min, HPCO Active”.
1. Leave all wiring connectors attached and perform
testing within the 60 minute time delay period
2. Check for line voltage at P9 connector on control
board (Two wire connector adjacent to 9 pin
connector).
A. Line voltage present - HPCO switch has reset
and closed.
B. No line voltage present - HPCO switch is open.
Verify pressure - Below cut-in replace HPCO -
Above cut-in find root cause problem.
3. Depending on timing either wait for the delay
period to end or start a new freeze cycle by cycling
the power button.
A. HPCO is open - Another 60 minute delay period
starts.
B. HPCO closed - A 3.5 minute harvest cycle starts
followed by an ice making cycle.
4. Run the system to see if the control trips at the rated
pressure. If HPCO opens at a pressure significantly
lower or higher than the control setting of 450 psig
replace the HPCO.
5. If the control opens at the correct pressure find the
root cause - Fan motor, dirty condenser, refrigeration
system issue, etc.The ice machine will go to an initial
start sequence if the HPCO is closed. If the HPCO is
open, another 60 minute delay period starts. When
the compressor relay closes the control board checks
the HPCO.
Содержание Indigo ID0302A
Страница 1: ...Part Number STH025 11 16 Indigo Series Air Water Remote Condenser Ice Machines Technician s Handbook ...
Страница 2: ......
Страница 20: ...20 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 36: ...36 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 162: ...162 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 212: ...212 Part Number STH025 11 16 ACCESS REMOTE RECOVERY EVACUATION CONNECTIONS ...
Страница 224: ...224 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 266: ...266 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 268: ...268 Part Number STH025 11 16 I0300 I0450 I0500 I0520 1PH AIR WATER Self Contained Air Water cooled 000007346_12 ...
Страница 269: ...Part Number STH025 11 16 269 I0320 1PH AIR WATER Self Contained Air Water cooled ...
Страница 270: ...270 Part Number STH025 11 16 I0500 1PH REMOTE Remote Air cooled 000007405_06 ...
Страница 273: ...Part Number STH025 11 16 273 I0600 I606 I0850 I0906 I1000 I1106 1PH REMOTE Remote Condenser Air cooled 000007606_09 ...
Страница 274: ...274 Part Number STH025 11 16 I0600 I606 I0850 I0906 I1000 I1106 3PH REMOTE Remote Condenser Air cooled 000007606_09 ...
Страница 275: ...Part Number STH025 11 16 275 I1400 I1406 I1800 1PH AIR WATER Self Contained Air Water cooled 000008865_02 ...
Страница 276: ...276 Part Number STH025 11 16 I1400 I1406 I1800 3PH AIR WATER Self Contained Air Water cooled 000008865_02 ...
Страница 277: ...Part Number STH025 11 16 277 I1400 II1406 1800 1PH REMOTE Remote Condenser 000008864_04 ...
Страница 278: ...278 Part Number STH025 11 16 I1400 I1406 I1800 3PH REMOTE Remote Condenser 000008864_04 ...
Страница 279: ...Part Number STH025 11 16 279 I1400 ECM FAN MOTOR 1PH AIR Self Contained Air cooled 000013616Rev03 ...
Страница 280: ...280 Part Number STH025 11 16 I1400 ECM FAN MOTOR 3PH AIR Self Contained Air cooled 000013616Rev03 ...
Страница 288: ...288 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 289: ...Part Number STH025 11 16 289 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 290: ......
Страница 291: ......
Страница 292: ......
Страница 293: ......
Страница 294: ......
Страница 295: ......