148
Comparing Evaporator Inlet and Outlet Temperatures
- Self-contained & Remote Condenser Single
Expansion Valve Machines
The temperatures of the suction lines entering and
leaving the evaporator alone cannot diagnose an ice
machine. However, comparing these temperatures during
the freeze cycle, along with using Manitowoc’s Freeze
Cycle Refrigeration System Operational Analysis Table,
can help diagnose an ice machine malfunction.
The actual temperatures entering and leaving the
evaporator vary by model, and change throughout
the freeze cycle. This makes documenting the “normal”
inlet and outlet temperature readings difficult. The key
to the diagnosis lies in the difference between the two
temperatures five minutes into the freeze cycle. These
temperatures should be within 7° of each other.
Use this procedure to document freeze cycle inlet and
outlet temperatures.
1. Navigate to Service / Real Time Data / Time & Temp
/ T3 & T4 Thermistors (See “Service Menu” on page
79 for details).
2. Wait five minutes into the freeze cycle.
3. Record the evaporator inlet (T3) and outlet (T4)
temperatures at 5 minutes into the freeze cycle.
Determine the difference.
4. Record the information on the table.
Содержание Indigo ID0302A
Страница 1: ...Part Number STH025 11 16 Indigo Series Air Water Remote Condenser Ice Machines Technician s Handbook ...
Страница 2: ......
Страница 20: ...20 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 36: ...36 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 162: ...162 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 212: ...212 Part Number STH025 11 16 ACCESS REMOTE RECOVERY EVACUATION CONNECTIONS ...
Страница 224: ...224 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 266: ...266 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 268: ...268 Part Number STH025 11 16 I0300 I0450 I0500 I0520 1PH AIR WATER Self Contained Air Water cooled 000007346_12 ...
Страница 269: ...Part Number STH025 11 16 269 I0320 1PH AIR WATER Self Contained Air Water cooled ...
Страница 270: ...270 Part Number STH025 11 16 I0500 1PH REMOTE Remote Air cooled 000007405_06 ...
Страница 273: ...Part Number STH025 11 16 273 I0600 I606 I0850 I0906 I1000 I1106 1PH REMOTE Remote Condenser Air cooled 000007606_09 ...
Страница 274: ...274 Part Number STH025 11 16 I0600 I606 I0850 I0906 I1000 I1106 3PH REMOTE Remote Condenser Air cooled 000007606_09 ...
Страница 275: ...Part Number STH025 11 16 275 I1400 I1406 I1800 1PH AIR WATER Self Contained Air Water cooled 000008865_02 ...
Страница 276: ...276 Part Number STH025 11 16 I1400 I1406 I1800 3PH AIR WATER Self Contained Air Water cooled 000008865_02 ...
Страница 277: ...Part Number STH025 11 16 277 I1400 II1406 1800 1PH REMOTE Remote Condenser 000008864_04 ...
Страница 278: ...278 Part Number STH025 11 16 I1400 I1406 I1800 3PH REMOTE Remote Condenser 000008864_04 ...
Страница 279: ...Part Number STH025 11 16 279 I1400 ECM FAN MOTOR 1PH AIR Self Contained Air cooled 000013616Rev03 ...
Страница 280: ...280 Part Number STH025 11 16 I1400 ECM FAN MOTOR 3PH AIR Self Contained Air cooled 000013616Rev03 ...
Страница 288: ...288 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 289: ...Part Number STH025 11 16 289 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 290: ......
Страница 291: ......
Страница 292: ......
Страница 293: ......
Страница 294: ......
Страница 295: ......