201
HARVEST PRESSURE REGULATING (HPR) SYSTEM
REMOTE CONDENSER ONLY
GENERAL
The harvest pressure regulating (HPR) system includes:
• Harvest pressure regulating solenoid valve (HPR
solenoid). This is an electrically operated valve which
opens when energized, and closes when
de-energized.
• Harvest pressure regulating valve (HPR valve). This is a
pressure regulating valve which modulates open and
closed, based on the refrigerant pressure at the outlet
of the valve. The valve closes completely and stops
refrigerant flow when the pressure at the outlet rises
above the valve setting.
FREEZE CYCLE
The HPR system is not used during the freeze cycle.
The HPR solenoid is closed (de-energized), preventing
refrigerant flow into the HPR valve.
HARVEST CYCLE
During the harvest cycle, the check valve in the discharge
line prevents refrigerant in the remote condenser and
receiver from back feeding into the evaporator and
condensing to liquid.
The HPR solenoid is opened (energized) during the
harvest cycle, allowing refrigerant gas from the top of
the receiver to flow into the HPR valve. The HPR valve
modulates open and closed, raising the suction pressure
high enough to sustain heat for the harvest cycle,
without allowing refrigerant to condense to liquid in the
evaporator.
In general, harvest cycle suction pressure rises, then
stabilizes in the range of 70-100 psig (517-758 kPa).
Exact pressures vary from model to model. Refer to cycle
time/24 hour ice production and operational pressure
charts.
Содержание Indigo ID0302A
Страница 1: ...Part Number STH025 11 16 Indigo Series Air Water Remote Condenser Ice Machines Technician s Handbook ...
Страница 2: ......
Страница 20: ...20 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 36: ...36 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 162: ...162 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 212: ...212 Part Number STH025 11 16 ACCESS REMOTE RECOVERY EVACUATION CONNECTIONS ...
Страница 224: ...224 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 266: ...266 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 268: ...268 Part Number STH025 11 16 I0300 I0450 I0500 I0520 1PH AIR WATER Self Contained Air Water cooled 000007346_12 ...
Страница 269: ...Part Number STH025 11 16 269 I0320 1PH AIR WATER Self Contained Air Water cooled ...
Страница 270: ...270 Part Number STH025 11 16 I0500 1PH REMOTE Remote Air cooled 000007405_06 ...
Страница 273: ...Part Number STH025 11 16 273 I0600 I606 I0850 I0906 I1000 I1106 1PH REMOTE Remote Condenser Air cooled 000007606_09 ...
Страница 274: ...274 Part Number STH025 11 16 I0600 I606 I0850 I0906 I1000 I1106 3PH REMOTE Remote Condenser Air cooled 000007606_09 ...
Страница 275: ...Part Number STH025 11 16 275 I1400 I1406 I1800 1PH AIR WATER Self Contained Air Water cooled 000008865_02 ...
Страница 276: ...276 Part Number STH025 11 16 I1400 I1406 I1800 3PH AIR WATER Self Contained Air Water cooled 000008865_02 ...
Страница 277: ...Part Number STH025 11 16 277 I1400 II1406 1800 1PH REMOTE Remote Condenser 000008864_04 ...
Страница 278: ...278 Part Number STH025 11 16 I1400 I1406 I1800 3PH REMOTE Remote Condenser 000008864_04 ...
Страница 279: ...Part Number STH025 11 16 279 I1400 ECM FAN MOTOR 1PH AIR Self Contained Air cooled 000013616Rev03 ...
Страница 280: ...280 Part Number STH025 11 16 I1400 ECM FAN MOTOR 3PH AIR Self Contained Air cooled 000013616Rev03 ...
Страница 288: ...288 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 289: ...Part Number STH025 11 16 289 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 290: ......
Страница 291: ......
Страница 292: ......
Страница 293: ......
Страница 294: ......
Страница 295: ......