Ice Formation Pattern
Evaporator ice formation pattern analysis is helpful in ice
machine diagnostics.
Analyzing the ice formation pattern alone cannot
diagnose an ice machine malfunction. However, when
this analysis is used along with Manitowoc’s Freeze Cycle
Refrigeration System Operational Analysis Tables, it can
help diagnose an ice machine malfunction.
Any number of problems can cause improper ice
formation.
Keep the water curtain/ice dampers in place while
checking the ice formation pattern to ensure no
water is lost.
1. Normal Ice Formation
Ice forms across the entire evaporator surface.
At the beginning of the Freeze cycle, it may appear that
more ice is forming on the inlet of the evaporator than on
the outlet. At the end of the Freeze cycle, ice formation
at the outlet will be close to, or just a bit thinner than, ice
formation at the inlet. The dimples in the cubes at the
outlet of the evaporator may be more pronounced than
those on the inlet. This is normal.
It is normal for ice thickness to vary up to 1/16” across the
surface of the evaporator. The ice bridge thickness at the
ice thickness control probe should be at least 1/8”.
The ice thickness probe must be set to maintain the ice
bridge thickness at approximately 1/8 in. If ice forms
uniformly across the evaporator surface, but does not
reach 1/8 in. in the proper amount of time, this is still
considered a normal ice fill pattern.
Содержание Indigo ID0302A
Страница 1: ...Part Number STH025 11 16 Indigo Series Air Water Remote Condenser Ice Machines Technician s Handbook ...
Страница 2: ......
Страница 20: ...20 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 36: ...36 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 162: ...162 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 212: ...212 Part Number STH025 11 16 ACCESS REMOTE RECOVERY EVACUATION CONNECTIONS ...
Страница 224: ...224 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 266: ...266 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 268: ...268 Part Number STH025 11 16 I0300 I0450 I0500 I0520 1PH AIR WATER Self Contained Air Water cooled 000007346_12 ...
Страница 269: ...Part Number STH025 11 16 269 I0320 1PH AIR WATER Self Contained Air Water cooled ...
Страница 270: ...270 Part Number STH025 11 16 I0500 1PH REMOTE Remote Air cooled 000007405_06 ...
Страница 273: ...Part Number STH025 11 16 273 I0600 I606 I0850 I0906 I1000 I1106 1PH REMOTE Remote Condenser Air cooled 000007606_09 ...
Страница 274: ...274 Part Number STH025 11 16 I0600 I606 I0850 I0906 I1000 I1106 3PH REMOTE Remote Condenser Air cooled 000007606_09 ...
Страница 275: ...Part Number STH025 11 16 275 I1400 I1406 I1800 1PH AIR WATER Self Contained Air Water cooled 000008865_02 ...
Страница 276: ...276 Part Number STH025 11 16 I1400 I1406 I1800 3PH AIR WATER Self Contained Air Water cooled 000008865_02 ...
Страница 277: ...Part Number STH025 11 16 277 I1400 II1406 1800 1PH REMOTE Remote Condenser 000008864_04 ...
Страница 278: ...278 Part Number STH025 11 16 I1400 I1406 I1800 3PH REMOTE Remote Condenser 000008864_04 ...
Страница 279: ...Part Number STH025 11 16 279 I1400 ECM FAN MOTOR 1PH AIR Self Contained Air cooled 000013616Rev03 ...
Страница 280: ...280 Part Number STH025 11 16 I1400 ECM FAN MOTOR 3PH AIR Self Contained Air cooled 000013616Rev03 ...
Страница 288: ...288 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 289: ...Part Number STH025 11 16 289 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 290: ......
Страница 291: ......
Страница 292: ......
Страница 293: ......
Страница 294: ......
Страница 295: ......