86
Part Number STH038 5/12
SAFETY LIMIT #1
Freeze time exceeds 60 minutes for 6 consecutive
freeze cycles.
Possible cause list
Water System
•
Loss of water from sump area
•
Low water pressure 1.37 bar min (20 psig)
•
High water pressure 5.51 bar max (80 psig)
•
High water temperature 32°C max (90°F)
•
Clogged water distribution tube
•
Dirty/defective water fill valve
•
Dirty/defective water dump valve
•
Defective water pump
•
Dirty/defective water level probe
Electrical System
•
Low incoming voltage
•
Ice thickness probe out of adjustment
•
Harvest cycle not initiated electrically
•
Contactor not energizing
•
Compressor electrically non-operational
•
Defective fan cycling control
•
Defective fan motor
Miscellaneous
•
High inlet air temperature
•
Condenser discharge air recirculation
•
Restricted air flow/dirty condenser fins
•
Defective harvest valve
•
Non-Manitowoc components
•
Improper refrigerant charge
•
Defective compressor
•
TXV starving or flooding (check bulb mounting)
•
Non-condensable in refrigeration system
•
Plugged or restricted high side refrigerant lines or
component
Содержание I0320A
Страница 20: ...18 Part Number STH038 5 12 This Page Intentionally Left Blank ...
Страница 26: ...24 Part Number STH038 5 12 This Page Intentionally Left Blank ...
Страница 86: ...84 Part Number STH038 5 12 This Page Intentionally Left Blank ...
Страница 124: ...122 Is the evaporator dirty Dry evaporator first then check YES NO NO ...
Страница 174: ...172 Part Number STH038 5 12 This Page Intentionally Left Blank ...
Страница 176: ...174 Part Number STH038 5 12 I0320 Self Contained 1 Ph ...
Страница 177: ...Part Number STH038 5 12 175 I0500 Self Contained 1 Ph ...
Страница 180: ...178 Part Number STH038 5 12 ...
Страница 181: ......