ICE THICKNESS CHECK
After a harvest cycle, inspect the ice cubes in the ice
storage bin. The ice thickness probe is factory-set to
maintain the ice bridge thickness at 3 mm (1/8").
NOTE: Make sure the water curtain is in place when
performing this check. It prevents water from splashing
out of the water trough.
1. Inspect the bridge connecting the cubes. It should
be about 3 mm (1/8") thick.
2. If adjustment is necessary, turn the ice thickness
probe adjustment screw clockwise to increase
bridge thickness, counterclockwise to decrease
bridge thickness. As a starting point place a 7 mm
(9/32") drill bit between the ice thickness probe
and the evaporator. Make final adjustments to
achieve a 3 mm (1/8") thick bridge.
NOTE: Turning the adjustment 1/3 of a turn will
change the ice thickness about 1.5 mm (1/16").
Ice Thickness Check
3. Make sure the ice thickness probe wire doesn’t
restrict movement of the probe.
3 mm (1/8")
ICE BRIDGE THICKNESS
PLACE 9/32” DRILL BIT
HERE TO SET INTIAL
GAP
Содержание I0320A
Страница 20: ...18 Part Number STH038 5 12 This Page Intentionally Left Blank ...
Страница 26: ...24 Part Number STH038 5 12 This Page Intentionally Left Blank ...
Страница 86: ...84 Part Number STH038 5 12 This Page Intentionally Left Blank ...
Страница 124: ...122 Is the evaporator dirty Dry evaporator first then check YES NO NO ...
Страница 174: ...172 Part Number STH038 5 12 This Page Intentionally Left Blank ...
Страница 176: ...174 Part Number STH038 5 12 I0320 Self Contained 1 Ph ...
Страница 177: ...Part Number STH038 5 12 175 I0500 Self Contained 1 Ph ...
Страница 180: ...178 Part Number STH038 5 12 ...
Страница 181: ......