10
LA | 1.01.01
www.mc-techgroup.com
The
LA1S
sensor with its Ø 12 mm glass body can be mounted inside a GL connection of a
F...-...-D
universal filter or in the
LS
flow chamber. The
LA25S
sensor has got a 1/4" special male connector for
mounting inside the
FSS...-D
universal filter or for mounting inside a 8 mm tube using a special union
tee connector
LS25
.
With the universal filters and the flow chamber, the gas inlet and gas outlet can be rotated 180 degrees
during installation.
The corresponding
M&C
controller electronics are available in 2 mounting variants for wall mounting
LA1.1
and rail mounting
LA1.4
.
A line break control system is integrated for safe operation. One LED each is provided for operation and
fault indication, as well as two potential-free changeover contacts in "Safety First" circuit for safe alarm
signalling. The electronic controller
LA1...
contain an alarm hold function and an alarm reset which can
be activated or deactivated on request. They are not activated on delivery.
By using one of the contacts, a pump or a solenoid valve in the gas conditioning system can be switched
directly and the second contact can be used as a status alarm.
The switching point of the electronic controller
LA1...
is adjustable via a potentiometer. A standard
adjustment to a conductivity of 100µS/cm is set at the factory.
A T T E N T I O N !
Use the special electronic controller ER142 Exi (without line break control)
(Part No. 03E2009(a)) only for the intrinsically safe supply of the sensor LA1
or LA25 of the old series located in the EX area.
When used with the new sensors LA1S and LA25S, there is no explosion
protection.
10
RECEIPT OF GOODS AND STORAGE
The liquid alarm series
LA
®
are normally delivered in 2 packing units:
1. Universal filter
F...-...-D
or flow chamber
LS
and liquid sensor
LA ...S
2. Electronic controller
LA1...
Carefully remove the components and any special accessories from the transport packaging
immediately upon arrival and check the scope of delivery according to the delivery note;
Check the goods for possible transport damage and, if necessary, inform your transport insurer
immediately of any possible damage.
N O T E !
The liquid alarm components should be stored in a protected frost-free
area
!
Содержание LA Series
Страница 26: ...26 LA 1 01 01 www mc techgroup com Figure 8 Flow diagram LA1 1 115 230 V 50 60 Hz ...
Страница 27: ...www mc techgroup com LA 1 01 01 27 Figure 9 Flow diagram LA1 1 24V AC DC ...
Страница 28: ...28 LA 1 01 01 www mc techgroup com Figure 10 Flow diagram LA1 4 115 230V 50 60Hz ...
Страница 29: ...www mc techgroup com LA 1 01 01 29 Figure 11 Flow diagram LA1 4 24V AC DC ...