13.1.1 ELECTRONIC CONTROLLER LA1.1
The following steps must be carried out for electrical connection (see Figure 4):
•
Loosen the 4 lid screws and remove the lid.
•
Lead the connection cables through the respective clamp fitting.
•
The electrical connection of the sensor
LA1S
or
LA25S
is made according the colors on the
terminals 5 = brown and 6 = white.
Old sensors of type
LA1, LA25
and
LA1-H
are to be connected to terminals 5 = brown and 8 =
white. In this case, a bridge must be installed between terminals 6 and 7.
N O T E !
If the older sensor LA1, LA25 or LA1-H is connected the same way as the
new sensor LA1S, the function of the electronic is inverted: no liquid = alarm,
liquid = OK.
N O T E !
If a new sensor LA1S is connected the same way as the old sensor LA1, LA25
or LA1-H no line break control is existing.
•
The voltage supply is connected to terminals 1 = L, 2 = N and 3 = PE.
•
The alarms are connected to terminals 12, 22 = alarm.
•
The center contact is connected to terminals 11, 21.
•
The relay contact 14, 24 = OK is energized in the good state.