21
Majestic • PEARL36STIN, PEARL36PRIN Installation Manual • 2478-980 Rev. C • 3/17
Figure 4.9 Adapt DVP Pipe to SLP Using DVP-SLP24 & DVP-2SL
DVP PIPE
HORIZONTAL EXAMPLE
(IDENTICAL VENT RUNS USING DVP AND SLP PIPE)
H
1
= 3 ft. (914 mm)
max.
DVP-SLP24
SLP PIPE
V
1
= 1 ft. (305 mm)
4 ft. SLP (1.2 m)
DVP-2SL
AND
OR
V
1
= 1 ft. (305 mm)
H
1
= 3 ft. (914 mm)
max.
2 ft. SLP (305 mm)
DVP-SLP24
Adapter
3 ft (914 mm) min.
60 ft (18.3 m) max.
DVP
SLP
VERTICAL EXAMPLE
(IDENTICAL VENT RUNS USING DVP AND SLP PIPE)
4 ft. SLP
DVP-2SL
AND
OR
3 ft (914 mm) min.
56 ft (17 m) max.
2 ft. SLP
(305 mm)
Note: The PEARL II series
fi
replaces can adapt to
SLP series vent pipe, if desired.
When venting off the top of the unit, use a DVP-2SL adapter
and a minimum 48 inch vertical section of SLP series vent pipe.
A DVP-SLP24 adapter may also be used with a 24 inch
vertical section of SLP series vent pipe.
After
the 48 inch vertical section, the venting table rules
must be followed. The
fi
rst 48 inch
vertical
section is NOT
counted as part of the vertical components in the table. It is
still counted as part of the overall maximum run. All venting
table rules for the vent run must still be followed.
Example:
DVP pipe 1 ft. min. vertical = 3 ft. max. horizontal
SLP pipe 5 ft. min. vertical = 3 ft. max. horizontal