background image

49

Hearth & Home Technologies  •  DVLINEAR36 Installation Manual  •  2569-980 Rev. E  •  11/20

A.  Fuel Conversion

•  Make sure the appliance is compatible with available gas 

types.

•  Conversions  must  be  made  by  a  qualified  service 

technician using Hearth & Home Technologies specified 

and approved parts.

B.  Gas Pressure

•  Verify inlet pressures. Verify minimum pressures when 

other household gas appliances are operating. 

•  Install  regulator  upstream  of  valve  if  line  pressure  is 

greater than 1/2 psig.

Gas Information 

Gas Pressure

Natural Gas

Propane

Minimum inlet pressure

5.0 in. w.c.

11.0 in. w.c.

Maximum inlet pressure

10.0 in. w.c.

13.0 in. w.c.

Manifold pressure

3.5 in. w.c.

10.0 in. w.c.

Note: 

Have the gas supply line installed in accordance with 

local codes, if any. If not, follow ANSI 

Z

223.1. Installation 

should be done by a qualified installer approved and/or 

licensed as required by the locality. (In the Commonwealth 

of  Massachusetts  installation  must  be  performed  by  a 

licensed plumber or gas fitter).

Note: 

A listed (and Commonwealth of Massachusetts ap

-

proved) 1/2 in. (13 mm) T-handle manual shut-off valve 

and flexible gas connector are connected to the 1/2 in. (13 

mm) control valve inlet. 

•  If substituting for these components, please consult 

local codes for compliance.

Fire Risk.
Risk of Fire!  Risk of Explosion!
Incorrect pressure will damage valve.

• Isolate 

gas supply piping BEFORE pressure 

testing gas line at test pressures above 1/2 

psig.

•  Close the manual shutoff valve BEFORE 

pressure testing gas line at test pressures 

equal to or less than 1/2 psig.

WARNING

•  Optimum appliance performance requires proper input 

pressures.

•  Gas line sizing requirements will be determined in ANSI 

Z223.1 National Fuel Gas Code in the USA and CAN/

CGA B149 in Canada.

•  Pressure requirements when in operation are:

REMOVE 2 SCREWS

Figure 9.1   Basepan Removal

Access Through the Valve Assembly
(For Service/Conversion)

1.  Locate  and  remove  the  two  screws  that  secure  the 

basepan  to  the  appliance.  See  Figure  9.1.  Remove 

basepan. Retain screws.  

Access Through the Control Cavity
(For Service/Conversion)

The  lower  access  cover  panel  pivots  down  if  finishing 

material has not been previously installed.  See Section 

8.A for removal instructions.

Содержание DVLINEAR36

Страница 1: ...performed by a qualified installer service agency or the gas supplier WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damag...

Страница 2: ...onstructing the Appliance Chase 17 4 Termination Location and Vent Information A Approved Pipe 18 B Vent Termination Minimum Clearances 18 C Vent Terminal Clearances 20 D Use of Elbows 21 E Use of Fle...

Страница 3: ..._____________________ Gas Section 9 Pg 49 52 Proper appliance for fuel type ___________________________ Was a conversion performed ___________________________ Leak check performed and inlet pressure v...

Страница 4: ...500 feet 1370 m above sea level Please consult provincial and or local authorities having jurisdiction for installations at elevations above 4500 feet 1370 m Check with your local gas utility to deter...

Страница 5: ...plastered or unplastered shall be considered combustible materials G Electrical Codes NOTICE This appliance must be electrically wired and grounded in accordance with local codes or in the absence of...

Страница 6: ...ted gas fu eled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or lo...

Страница 7: ...lation adjustment alteration service or maintenance can cause injury or property damage For assistance or additional information consult a qualified service technician service agency or your dealer Fi...

Страница 8: ...ectric Shock DO NOT use this appliance if any part has been under water Call a qualified service technician to inspect the appliance and to replace any part of the control system and or gas control wh...

Страница 9: ...ons DVLINEAR36 Location Inches Millimeters M 16 3 4 426 N 6 5 8 168 O 32 3 8 822 P 2 3 16 56 Q 6 152 R 17 1 4 438 S 25 7 8 657 T 43 1 2 1105 U 6 1 8 156 V 7 1 2 191 W 10 3 8 264 X 7 3 4 197 Location I...

Страница 10: ...ative Barrier Front G E D H B A C F Dimensions are actual decorative barrier front dimensions Use for reference only Figure 3 2 Decorative Barrier Front Dimensions IMPORTANT This fireplace requires an...

Страница 11: ...lustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Illustrations diagrams are not drawn to scale Actual installation may vary due to individual design preference Figure 3 3 App...

Страница 12: ...h thick are designed to contact the non combustible material appliance as called out in Section 10 Finishing This appliance has been thoroughly tested to minimize drywall cracking and or the protrusio...

Страница 13: ...INSTALLED PHTRIM LINEAR NO TRIM KIT Required Height of Discharge Opening Height of Discharge Opening Clearance to Discharge Opening Width of Discharge Opening DVLINEAR36 Inches 3 1 2 2 48 36 1 2 milli...

Страница 14: ...eat Front Discharge Vent Cover Dimensions C D B A FRONT DISCHARGE FRAMING DIMENSIONS A B C D Inside Height Inside Width Outside Height Outside Width PHTRIM 36LINEAR Inches 2 9 16 36 1 2 5 5 8 38 3 8 m...

Страница 15: ...Clearance Bottom of Appliance to Ceiling Minimum Clearance to Combustible Materials DVLINEAR36 Inches 12 1 4 8 3 4 39 82 18 millimeters 311 222 991 2083 457 Framing Dimensions Passive Heat Side Disch...

Страница 16: ...ing Dimensions Passive Heat Open Top Discharge PH FRT LINEAR WARNING Risk of Fire Mesh screen required on bottom of discharge opening when discharge opening is greater than 3 inches Secure mesh to top...

Страница 17: ...d construction of the chase may vary with the type of building These instructions are not substitutes for the requirements of local building codes Therefore you MUST check local building codes to dete...

Страница 18: ...urers SLP FLEX and SLP FLEX7 venting cannot be interchanged SLP FLEX 6 5 8 Inch Venting may be used in any venting configuration shown in the venting tables pro vided that the horizontal vent length i...

Страница 19: ...consider proximity to doors traffic areas or where people may pass or gather sidewalk deck patio etc Listed cap shields available Contact your dealer Local codes or regulations may require different c...

Страница 20: ...lding or the combustion air inlet to any other appliance termination mechanical or non mechanical 9 in 229 mm 12 in 305 mm I clearance to a mechanical powered air supply inlet All mechanical air intak...

Страница 21: ...e is allowed between two 45 elbows See Figure 4 6 Figure 4 7 shows the vertical and horizontal offsets for SLP elbows Figure 4 6 HORIZONTAL VERTICAL RUN RISE E F F E C T I V E L E N G T H Y X X X Vent...

Страница 22: ...length of pipe See Section 12 A Figure 12 1 for information on effective length of pipe components Horizontal terminations are measured to the outside mounting surface flange of termination cap See F...

Страница 23: ...upport is required at each change in venting direc tion and in any location where it is necessary to maintain the necessary clearance to combustibles A simple up and out installation Figure 4 10 requi...

Страница 24: ...installed horizontally See Figure 4 15 Elbows may be placed back to back anywhere in the system Any 90 elbow may be replaced with two back to back 45 elbows When penetrating a combustible wall a wall...

Страница 25: ...8 inch vent except when using the simple up and out installation See Figure 4 10 H1 V1 V Minimum H1 Maximum 90 Elbow 1 ft 305 mm 1 ft 305 mm 2 ft 610 mm 2 ft 610 mm 3 ft 914 mm 3 ft 914 mm 5 ft 1 5 m...

Страница 26: ...1 ft 305 mm 2 ft 610 mm 2 ft 610 mm 3 ft 914 mm 4 ft 1 2 m 4 ft 1 2 m 6 ft 1 8 m 5 ft 1 5 m 15 ft 4 6 m H1 H2 MAX 15 ft 4 6 m V1 H1 H2 MAX 40 ft 12 2 m CAUTION The SLP HRC SS termination caps are not...

Страница 27: ...use tempered glass breakage Note There MUST be a 25 reduction in total H when using SLP FLEX Series 6 5 8 inch vent except when using the simple up and out installation See Figure 4 10 V1 Minimum H1 H...

Страница 28: ...of Fire This vent configuration can ONLY be used for DVLINEAR36 Natural Gas appliances WARNING CAUTION The SLP HRC SS termination caps are not approved for use with these models May lead to elevated g...

Страница 29: ...al 2569 980 Rev E 11 20 Top Vent Vertical Termination No Elbow Figure 4 16 V1 60 ft Max 18 3 m Note Use SLP Series components only Note If installing a vertical vent termination off the top of the app...

Страница 30: ...st Restrictor Installation 1 Remove inner heat shield by removing two wing nuts from top front of heat shield and two screws that se cure the heat shield to back wall of fireplace Retain heat shield a...

Страница 31: ...5 reduction in total H when using SLP FLEX Series 6 5 8 inch vent except when using the simple up and out installation See Figure 4 10 V1 Minimum H Maximum V2 V1 V2 Minimum 1 ft 305 mm 2 ft 610 mm 2 f...

Страница 32: ...T be a 25 reduction in total H when using SLP FLEX Series 6 5 8 inch vent except when using the simple up and out installation See Figure 4 10 V1 Minimum H1 H2 Maximum V2 V1 V2 Minimum 1 ft 305 mm 1 f...

Страница 33: ...3 MIN 2 1 2 ft 762 mm 4 ft 1 2 m 4 ft 1 2 m 4 ft 1 2 m 3 1 2 ft 1 0 m V1 V2 V3 H1 H2 Maximum 40 ft 12 2 m V1 H1 V2 V3 H2 Figure 4 20 Four 90 Elbows Top Vent Vertical Termination continued Note There M...

Страница 34: ...ance Have the chimney and adjacent structure inspected and cleaned by qualified professionals Hearth Home Technologies recommends that NFI or CSIA certified professionals or technicians under the dire...

Страница 35: ...nd three self tapping screws to attach one section of flexible vent pipe to the exhaust collar on top of the DV 46DVA GCL adapter To minimize cold air drafts seal around the flex vents at the damper i...

Страница 36: ...clearance 1 in 25 mm clearance bottom sides Heat Shield Wall Shield Firestop Heat Shield WALL 3 in 76 mm top clearance 1 in 25 mm clearance around vertical sections B Wall Penetration Framing Firesto...

Страница 37: ...irestop Floor Penetra tion Framing WARNING Risk of Fire DO NOT pack insu lation around the vent Maintain clearances to vent to prevent overheating A ceiling firestop MUST be used between floors and at...

Страница 38: ...with the kit for installation and operation NOTICE Additional clearances are required for heat management systems installations Provisions must be made in advance to ensure fit within the framing Det...

Страница 39: ...astener per nailing tab Optional Secure the appliance to the floor by inserting two screws through the pilot holes at the bottom of the appliance Risk of Fire Prevent contact with Sagging or loose ins...

Страница 40: ...te the manual bag assembly and remove the small package containing the 1 1 2 inch Phillips screws Note Care should be taken when installing screws into the non combustible board DO NOT overtighten scr...

Страница 41: ...low including the slip section that connects directly to the horizontal termination cap Apply a bead of silicone sealant 300 F minimum con tinuous exposure rating inside the female outer pipe joint pr...

Страница 42: ...slip section See Figure 7 4 120 Figure 7 5 Securing Vertical Pipe Sections C Secure the Vent Sections WARNING Risk of Fire Explosion or Asphyxiation Improper support could allow vent to sag and separa...

Страница 43: ...11 20 D Disassemble Vent Sections Rotate either section see Figure 7 7 so the seams on both pipe sections are aligned as shown in Figure 7 8 Pull carefully to separate the pieces of pipe Figure 7 8 Al...

Страница 44: ...lation Sheet metal edges are sharp Slide the storm collar onto the exposed pipe section and align brackets Insert a bolt provided through the brackets and install nut Do not completely tighten Slide...

Страница 45: ...ting heat shields using the screws supplied with the extended heat shield Refer to vent components diagrams in the back of this manual Rest the small leg on the extended heat shield on top of the pipe...

Страница 46: ...its to mitigate the interference potential If interference is occurring on the same circuit the use of surge protectors may help alleviate the interference 8 8 Electrical Information Valve Control Acc...

Страница 47: ...r Plate outside firebox Romex Connector NOTICE DO NOT wire 110 120 VAC to wall switch Figure 8 3 Junction Box Detail Generic Model Shown Wire the appliance junction box to 110 120 VAC for proper opera...

Страница 48: ...G IN BLACK RED BATTERY PACK ORANGE TO BROWN TO BROWN GREEN VALVE GROUND TO FIREPLACE CHASSIS WHITE ORANGE IGNITION MODULE 3 VAC INTERMITTENT PILOT IGNITOR HOT NEUTRAL I S JUNCTION BOX 110 120 VAC TRAN...

Страница 49: ...and Commonwealth of Massachusetts ap proved 1 2 in 13 mm T handle manual shut off valve and flexible gas connector are connected to the 1 2 in 13 mm control valve inlet If substituting for these comp...

Страница 50: ...components please consult local codes for compliance 2 Remove the two screws that secure the pilot shield to the burner bracket and remove the two screws that secure the pilot assembly to the burner...

Страница 51: ...onsult provincial and or local authorities having jurisdiction for installations at elevations above 4500 feet 1370 m Check with your local gas utility to determine proper orifice size Figure 9 4 Inco...

Страница 52: ...more air by opening the air shutter Air shutter settings should be adjusted by a qualified ser vice technician at the time of installation The air shut ter is set at the factory for a typical horizon...

Страница 53: ...ill allow the wallboard joints to occur on the center of the framing where the panels can be fastened properly If the framing thickness is less than 1 1 2 in nominal such as with formed steel systems...

Страница 54: ...opening Ensure that the 1 8 inch gap is maintained between the factory installed non combustible board and the surrounding drywall See Figure 10 1 Secure the drywall to the framing with screws a mini...

Страница 55: ...ee Figure 10 2 Note If the desired look is painted drywall it is recommended that no additional screws are installed into the factory provided non combustible board Only install the screws provided in...

Страница 56: ...Risk of Fire Comply with all minimum clear ances as specified Framing closer than the minimums list ed must be constructed entirely of non combustible materi als i e steel studs concrete board etc No...

Страница 57: ...NG 2 IN MIN DO NOT INSTALL FINISHING MATERIAL ON THIS SURFACE 2 IN MIN OPENING MUST NOT BE BLOCKED CEILING 12 1 4 IN 8 3 4 IN SIDE DISCHARGE DISCHARGE SLOTS ON BOTH SIDES OF APPLIANCE FRONT DISCHARGE...

Страница 58: ...or underneath in the control cavity C Install Media Decorative glass media is included with the DVLINEAR36 Placing the Media Install glass media around the burner ensuring that no media is placed on...

Страница 59: ...bottom two glass latches Use one hand to support the glass at all times 2 Fasten the two upper glass latches one at a time by pulling out and downward into position on the glass assembly Use one hand...

Страница 60: ...ective bag from decorative barrier front 3 Bend the front hanging brackets to separate from the assembly See Figure 11 3 and Figure 11 4 4 Locate the mounting tabs on the two hanging brack ets The mou...

Страница 61: ...61 Hearth Home Technologies DVLINEAR36 Installation Manual 2569 980 Rev E 11 20 Figure 11 6 Decorative Barrier Front Installed...

Страница 62: ...LP45 45 Elbow SLP90 90 Elbow Effective Height Length SLP PIPE SLP HVS Horizontal Pipe Support SLP FS Ceiling Firestop SLP WS Wall Shield Firestop 10 7 8 in 276 mm 8 7 8 in 225 mm 1 1 2 in 38 mm 8 11 1...

Страница 63: ...ting heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield Term Cap Minimum Effective Length Maximum Effective Length Trap1 3 1...

Страница 64: ...ion Kit 14 in 356 mm 14 1 16 in 357 mm 7 1 2 in 192 mm 10 3 4 in 273 mm SLP CCS BK Cathedral Ceiling Support Box Black SLP DCF BK Ceiling Firestop Black SLK SNKD Snorkel Termination Cap SLP TVHW Verti...

Страница 65: ...SLP HHW2 Horizontal High Wind Termination Cap 15 IN 381 mm 12 IN 305 mm 8 IN 203 mm Figure 12 4 SLP series Vent Components A Vent Components Diagrams continued DECORATIVE TERMINATIONS SHROUDS Only use...

Страница 66: ...pproved for use with PVI SLP B only Note Wire harnesses required to power the PVI SLP B connect to the appliance and are ordered separately from PVI SLP B Contact your dealer to order 16 IN 406 mm 15...

Страница 67: ...ely from PVLP SLP Contact your dealer to order Figure 12 7 PVLP SLP Vent Components PVLP HS Heat Shield 14 IN 356 mm 15 1 2 IN 394 mm 11 1 2 IN 292 mm 8 IN 203 mm 4 3 8 IN 112 mm 10 IN 254 mm 5 1 4 IN...

Страница 68: ...PVI WH100 Description Part Number 12 in Wire Harness Sleeve PVV SLEEVE 12 48 in Wire Harness Sleeve PVV SLEEVE 48 PVV SLP Vertical Power Vent Note A wire harness is required to power the PVV SLP and c...

Страница 69: ...hock Use ONLY Hearth Home Technologies approved optional acces sories with this appliance Using non listed accessories could result in a safety hazard and will void the warranty Install approved acces...

Отзывы: