Termination Location and Vent Information
A. Approved Pipe
WARNING!
Risk of Fire, Delayed Ignition or Asphyxi
-
ation.
This appliance requires a separate vent.
DO NOT
vent to a pipe serving any other appliance.
This appliance is only approved for use with the Hearth &
Home Technologies SLP venting system. Refer to Sec
-
tion 12.A for vent component information and dimensions.
Only use listed decorative termination caps/shrouds with
Hearth & Home Technologies approved venting systems.
DO NOT
mix pipe, fittings or joining methods from differ
-
ent manufacturers.
The pipe is tested to be run inside an enclosed wall.
There is no requirement for inspection openings at each
joint within the wall.
Approved Pipe - Rigid
This appliance is approved for use with Hearth & Home
Technologies SLP venting systems. Refer to Section
12.A for vent component information and dimensions.
DO NOT
mix pipe, fittings or joining methods from differ
-
ent manufacturers.
The pipe is tested to be run inside an enclosed wall.
There is no requirement for inspection openings at each
joint within the wall.
WARNING!
Risk of Fire or Asphyxiation.
This appli-
ance requires a separate vent.
DO NOT
vent to a pipe
serving a separate solid fuel burning appliance.
Approved Pipe - Flex
This appliance is approved for use with Hearth & Home
Technologies SLP-FLEX (6-5/8 inch) and SLP-FLEX7 (7
inch) venting systems.
DO NOT
mix pipe, fittings or joining methods from
different manufacturers. SLP-FLEX and SLP-FLEX7
venting cannot be interchanged.
SLP-FLEX (6-5/8 Inch):
Venting may be used in any
venting configuration shown in the venting tables pro
-
vided that the horizontal vent length is reduced by 25%.
SLP-FLEX7 (7 Inch-Canada Only):
Venting requires
adapter collars to transition from the 6-5/8 IN. appliance
starting collar and to the 6-5/8 IN. termination cap. Refer
to installation instructions included with the SLP-FLEX7
collar adapter (SLP-FLEX7-A). SLP-FLEX7 Series vent
-
ing is approved for use in Canada only.
The pipe is tested to be run inside an enclosed wall.
There is no requirement for inspection openings at each
joint within the wall.
WARNING!
Risk of Fire or Asphyxiation.
This appli-
ance requires a separate vent.
DO NOT
vent to a pipe
serving a separate solid fuel burning appliance.
B. Vent Termination Minimum Clearances
Roof Pitch
H (Min.) Ft
Flat to 6/12...........................................................1.0*
Over 6/12 to 7/12 .................................................1.25*
Over 7/12 to 8/12 .................................................1.5*
Over 8/12 to 9/12 .................................................2.0*
Over 9/12 to 10/12 ...............................................2.5*
Over 10/12 to 11/12 .............................................3.25
Over 11/12 to 12/12 .............................................4.0
Over 12/12 to 14/12 .............................................5.0
Over 14/12 to 16/12 .............................................6.0
Over 16/12 to 18/12 .............................................7.0
Over 18/12 to 20/12 .............................................7.5
Over 20/12 to 21/12 .............................................8.0
Figure 4.1 Minimum Height From Roof to Lowest Discharge
Opening
HORIZONTAL
OVERHANG
VERTICAL
WALL
GAS DIRECT VENT
TERMINATION CAP
12
X
ROOF PITCH
IS X/ 12
LOWEST
DISCHARGE
OPENING
2 FT.
MIN.
20 INCHES MIN.
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
Fire Risk.
Maintain vent clearance to combustibles as
specified.
•
DO NOT
pack air space with insulation or other
materials.
Failure to keep insulation or other materials away
from vent pipe could cause overheating and fire.
WARNING
* H minimum may vary depending on regional snowfall.
Refer to local codes.