background image

NOTE REGARDING VENTED PRODUCTS

This product must be installed by a licensed plumber or gas fitter 

when installed within the Commonwealth of Massachusetts.
Any  residence  with  a  direct  vent  product  must  have  a  CO 

detector installed in the residence.
Installation  of  the  fireplace  or  vented  gas  log  in  the  State  of 

Massachusetts requires the damper to be permanently removed 

or welded in the fully open position.
In addition, a naturally vented gas log may not be installed in a 

bedroom or bathroom in the State of Massachusetts.
Flex line installation must not exceed 36 inches and must have 

a T shutoff valve. 

NOTE REGARDING VENT FREE PRODUCTS

This product must be installed by a licensed plumber or gas fitter 

when installed within the Commonwealth of Massachusetts.
In  addition,  vent  free  products  may  not  be  installed  in  a 

bedroom or bathroom regardless of size or type in the State of 

Massachusetts.
Flex line installation must not exceed 36 inches and must have 

a T shutoff valve.

CARBON MONOxIDE DETECTOR REqUIREMENTS

(2) Revise  10.8.3  by  adding  the  following  additional 

requirements:
(a)  

For  all  side  wall  horizontally  vented  gas  fueled 

equipment installed in every dwelling, building or structure used 

in  whole  or  in  part  for  residential  purposes,  including  those 

owned or operated by the Commonwealth and where the side 

wall exhaust vent termination is less than seven (7) feet above 

finished  grade  in  the  area  of  the  venting,  including  but  not 

limited to decks and porches, the following requirements shall 

be satisfied:

1. 

Installation  of  carbon  monoxide  detectors. 

At  the  time 

of  installation  of  the  side  wall  horizontal  vented  gas  fueled 

equipment,  the  installing  plumber  or  gas  fitter  shall  observe 

that a hard wired carbon monoxide detector with an alarm and 

battery  back-up  is  installed  on  the  floor  level  where  the  gas 

equipment is to be installed. In addition, the installing plumber 

or gas fitter shall observe that a battery operated or hard wired 

carbon  monoxide  detector  with  an  alarm  is  installed  on  each 

additional level of the dwelling, building or structure served by 

the side wall horizontal vented gas fueled equipment. It shall be 

the responsibility of the property owner to secure the services of 

qualified licensed professionals for the installation of hard wired 

carbon monoxide detectors
 

a.  In the event that the side wall horizontally vented gas 

fueled equipment is installed in a crawl space or an attic, the 

hard  wired  carbon  monoxide  detector  with  alarm  and  battery 

back-up may be installed on the next adjacent floor level.
 

b.  In the event that the requirements of this subdivision 

can  not  be  met  at  the  time  of  completion  of  installation,  the 

owner shall have a period of thirty (30) days to comply with the 

above requirements; provided, however, that during said thirty 

(30) day period, a battery operated carbon monoxide detector 

with an alarm shall be installed.

Massachusetts Residents Only — Please read and follow these special requirements

Approved  Carbon  Monoxide  Detectors.

 

Each  carbon 

monoxide detector as required in accordance with the above 

provisions shall comply with NFPA 720 and be ANSI/UL 2034 

listed and IAS certified.

3. 

Signage.

  A  metal  or  plastic  identification  plate  shall  be 

permanently  mounted  to  the  exterior  of  the  building  at  a 

minimum height of eight (8) feet above grade directly in line with 

the exhaust vent terminal for the horizontally vented gas fueled 

heating appliance or equipment. The sign shall read, in print size 

no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY 

BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”

4. 

Inspection.

 The state or local gas inspector of the side wall 

horizontally vented gas fueled equipment shall not approve the 

installation  unless,  upon  inspection,  the  inspector  observes 

carbon monoxide detectors and signage installed in accordance 

with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) 

Exemptions:

 The following equipment is exempt from 248 

CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not 

Required To Be Vented" in the most current edition of NFPA 54 

as adopted by the Board; and
2.  Product Approved  side  wall  horizontally  vented  gas  fueled 

equipment  installed  in  a  room  or  structure  separate  from  the 

dwelling,  building  or  structure  used  in  whole  or  in  part  for 

residential purposes.
(c)  

Manufacturer requirements — Gas Equipment Venting 

System  Provided.

 

When  the  manufacturer  of  Product 

Approved side wall horizontally vented gas equipment provides 

a  venting  system  design  or  venting  system  components  with 

the equipment, the instructions provided by the manufacturer 

for installation of the equipment and the venting system shall 

include:
1. Detailed instructions for the installation of the venting system 

design or the venting system components; and
2. A complete parts list for the venting system design or venting 

system.
(d) 

Manufacturer requirements — Gas Equipment Venting 

System Not Provided. 

When the manufacturer of a Product 

Approved  side  wall  horizontally  vented  gas  fueled  equipment 

does  not  provide  the  parts  for  venting  the  flue  gases,  but 

identifies “special venting systems,” the following requirements 

shall be satisfied by the manufacturer:
1.  The  referenced  "special  venting  system"  instructions  shall 

be  included  with  the  appliance  or  equipment  installation 

instructions; and
2. The “special venting systems” shall be Product Approved by 

the Board, and the instructions for that system shall include a 

parts list and detailed installation instructions.
(e)  

A  copy  of  all  installation  instructions  for  all  Product 

Approved side wall horizontally vented gas fueled equipment, 

all  venting  instructions,  all  parts  lists  for  venting  instructions, 

and/or all venting design

Содержание Designer

Страница 1: ...information consult a qualified installer service agency or the gas supplier This appliance may be installed in an aftermarket permanently located manufactured home USA only or mobile home where not...

Страница 2: ...Rear Wall Vent Installation 21 Horizontal Termination Configuration 23 Below Grade Installation 25 Vertical Through the Roof Installation 26 Installation for Vertical Termination 27 Flat Ceiling Insta...

Страница 3: ...glass door properly seated and sealed combustion leakage can occur CARBON MONOXIDE POISONING Early signs of carbon monoxide poisoning are similar to the flu with headaches dizziness and or nausea If...

Страница 4: ...ger insert or any other accessory not approved for use with this fireplace 21 Do not operate the fireplace with glass door removed cracked or broken 22 This unit is approved for bedroooms and bath roo...

Страница 5: ...A 54 in the USA CSA B149 in Canada This appliance is mobile home approved This appliance is approved for bathroom installation The appliance must be properly connected to a venting system The applianc...

Страница 6: ...ill and Bits Tee Joint Pliers Pipe Sealant Approved for use with Propane LPG Square Resistant to Sulfur Compounds Pipe Wrench The classification noncombustible material includes but is not limited to...

Страница 7: ...all of your gas fireplaces checked annually More frequent cleaning may be required due to excess lint and dust from carpeting bedding material etc 6 Control compartments burners and air passages in th...

Страница 8: ...nt and any undetected oil form the manufacturing process Please ensure that your room is well ventilated open all widows It is recommended you burn your MHSC fireplace for at least 10 10 hours the fir...

Страница 9: ...341 2 4015 16 1 2 5 8 323 4 530419 see thru dims 10 08 1 2 5 8 Gas Electric SEE THROUGH and PENINSULA MODELS 31 4 44 241 2 395 8 47 16 187 8 373 4 13 4 321 4 191 2 4015 16 373 4 530419 corner dims 10...

Страница 10: ...ft floor coverings It may however be placed on a flat wood plywood particle board or other hard surface Be sure firebox rests on a solid continuous floor or platform with appropriate framing for suppo...

Страница 11: ...framing 10 08 Gas Connection 2 x 2 Minimum Figure 6 Top View of Framing Inside Corner Right hand configuration 2 x 4 Minimum 2 x 2 Minimum FP2037 Figure 7 Framing for Corner Installation Corner Framin...

Страница 12: ...mounted flue pipe adapter Refer to Page 17 Figures 13 and 14 Reattach both assem blies C A 2 B A 1 A1 A2 C FP3028 designer see thru framing 10 08 Install 2 x 4 minimum after Fireplace is Set into Fra...

Страница 13: ...ust be secured to the floor and or to framing studs as shown in Figure 10 Use two 2 wood screws or masonry concrete screws to secure fireplace to the floor Use four 4 screws to attach fireplace to fra...

Страница 14: ...y can create a fire hazard The appliance cannot be installed on a carpet tile or other combustible material other than wood flooring If installed on carpet or vinyl flooring the appliance shall be ins...

Страница 15: ...ing Material NOTE Any wiring i e remote control wall switch and optional fan must be done prior to final finishing to avoid costly reconstruction INSTALLATION INFORMATION Only noncombustible materials...

Страница 16: ...parate solid fuel burning appliance Each gas appliance must use a separate vent system Do not use common vent systems WARNING Horizontal sections of this vent system require a minimum of 3 clearances...

Страница 17: ...and refitted as required 1 Remove the eight 8 screws securing the flue pipe adapter to the fireplace body Figure 13 2 Set the flue pipe adapter aside complete with the gasket Do not damage the gaskets...

Страница 18: ...each floor level If an offset is needed in the attic additional pipe and elbows will be required You may use a chase with a vent termination with exposed pipe on the exterior of the house See Installi...

Страница 19: ...y inlet to building or the combustion air inlet to any other appliance 12 305mm minimum K Clearance to a mechanical air supply inlet 6 1829mm minimum L Clearance above a paved sidewalk or paved drivew...

Страница 20: ...ns to determine the relationship between the vertical and horizontal dimensions of the vent system 1 Determine the height of the center of the horizontal vent pipe exiting through the outer wall Using...

Страница 21: ...to matching slots on the male end of adjacent pipes and fittings Push the pipe sections together and twist one sec tion clockwise approximately one quarter turn until the sections are fully locked Fig...

Страница 22: ...tandoff prevents excessive heat from melting the vinyl siding material Bolt the vent cap to the standoff Apply non hardening mastic around outside edge of the standoff instead of the vent cap assembly...

Страница 23: ...is best to locate the fireplace in such a way that minimizes the number of offsets and hori zontal vent length The horizontal vent run refers to the total length of vent pipe from the flue collar of...

Страница 24: ...two 2 These elbows can be installed in either the vertical or horizontal run For each 45 elbow installed in the horizontal run the length of the hori zontal run MUST be reduced by 18 45 cm This does...

Страница 25: ...proximately 16 below base of snorkel Install drain pipe Install window well not supplied Refill hole with 12 of coarse gravel leaving a clearance of approximately 4 below snorkel Figure 31 3 Install v...

Страница 26: ...45 elbows may be used within the horizontal run For each 45 elbow used on the horizontal plane the maximum horizontal length must be reduced by 18 450 mm Example Maximum horizontal length No elbows 10...

Страница 27: ...are hole in the ceiling using the locating hole as a center point The opening should be framed to 91 2 x 91 2 241 mm x 241 mm inside dimen sions as shown in Figure 37 using framing lumber the same siz...

Страница 28: ...lashing There must be a 1 clearance from the vent pipe to combustible materials 6 Continue to add pipe sections until the height of the vent cap meets the minimum building code requirements NOTE You m...

Страница 29: ...incoming gas pressure to between 11 and 13 inches of water If you do not reduce incoming gas pressure burner system regulator damage could occur Install external regulator with the vent pointing down...

Страница 30: ...nd contaminants and keeps them from going into the burner system gas controls If sediment trap drip leg is not installed or is installed wrong burner system may not run properly Natural Gas From Gas M...

Страница 31: ...gas joints from the gas meter to the fireplace for leaks Use a solution of 50 50 water and soap or a gas sniffer 4 To adjust flame height turn HI LO knob to HI to get maximum pressure to burner Turn H...

Страница 32: ...not connect wall switch to heater 110V circuit Electrical Wiring Verify proper operation after servicing This fireplace will work without any electrical supply Electricity is only needed to operate bl...

Страница 33: ...Switch Position the wall switch Do not extend beyond the 15 feet of wire Optional DC Remote Systems See section entitled Hearth Mount in the Millivolt hand held remote instructions supplied with the r...

Страница 34: ...om of fireplace Figure 43 2 Tilt glass frame out and lift glass frame up until it clears three 3 tabs on top of fire place 3 Set glass frame aside caution Each clamp has a quick spring force When rein...

Страница 35: ...supplied with the unit Failure to position the parts in accordance with diagrams below or to use only parts specifically approved for this heater may result in property damage or personal injury INSTA...

Страница 36: ...with pins on grate Figure 47 LG561 install bot ctr back log Bottom Center Back Log 3 Pin LG561 Figure 46 Install Bottom Center Log 3 Lg562 install bot front log Bottom Front Log 4 Pin Pin LG562 Figure...

Страница 37: ...gure 49 9 Break up rock wool ember material into dime sized pieces Place evenly across burner surface and mesh of grate Figure 50 Do not exceed 1 depth of coverage LG564 install top log Top Log 6 Cuto...

Страница 38: ...lass frame Refer to Glass Frame Removal Page 34 2 Using a Phillips screwdriver loosen the screw that secures the air restrictor Do not back the screw all the way out 3 Slide the baffle on top of the r...

Страница 39: ...ted repair may result in a fire or explosion D Do not use this appliance if any part of it has been under water Immediately call a qualified ser vice technician to inspect the appliance and to replace...

Страница 40: ...onic ignitor will automatically ignite the pilot Keep knob fully depressed for a few seconds Release and check that pilot continues to burn If the pilot does not stay lit repeat steps 1 and 2 Lighting...

Страница 41: ...you to turn on and to turn off the main burner without using the gas valve knob Make sure the button is in the ON position to light the main burner Figure 53 Lighting the burner Depress and turn the...

Страница 42: ...hree times a season Use a mild glass cleaner to clean the door Do not use abrasive cleaners They will damage the glass surface PILOT AND BURNER FLAMES Visually check pilot and burner flames periodical...

Страница 43: ...trol or wire B Pilot flame too small C Defective or malfunctioning thermopile D Defective valve A Check switch and wire for proper connection Place jumper wires across terminals of switch If burner co...

Страница 44: ...Check electrical connections between module and pilot operator on gas control C Check for 24VAC across PV MVPV terminals If voltage is correct replace gas control If voltage is not correct replace mod...

Страница 45: ...r air intake at the bottom back of the combustion chamber Ensure that the glass is properly secure and latched troubleshooting CAUTION Always use gloves when handling broken glass WARNING Make sure th...

Страница 46: ...Center Log 3 1 42D0403 42D0403 4 Bottom Front Log 4 1 42D0402 42D0402 5 Left Log Top 5 1 42D0404 42D0404 6 Top Log 6 1 42D0405 42D0405 1 2 3 4 5 6 530419 designer logs WARNING Failure to position the...

Страница 47: ...t Corner Right 1 42D0406K 42D0406K 4 Small Floor Firebrick 1 42D0163 42D0163 5 Large FloorFirebrick 1 42D0164 42D0164 6 Small Wall Firebrick 1 42D0165 42D0165 7 Large Wall Firebrick 1 42D0166 42D0166...

Страница 48: ...jector 1 42D0502 42D0503 7 Burner Assembly 1 42D0500 42D0501 8 Wire Assembly Female 1 44D0500 44D0500 8 Wire Assembly Male 1 44D0501 44D0501 Accessories 9 Thermostatic Remote Control 1 RCT TRC RCT TRC...

Страница 49: ...D0048 41D0048 5 Injector 1 42D0502 42D0503 6 Burner Assembly 1 42D0500 42D0501 7 Wire Assembly 1 54D2007 54D2007 8 Ignition Module 1 37D0325 37D0325 9 Transformer 1 37D0027 37D0027 WARNING Failure to...

Страница 50: ...nation cap with built in vinyl siding standoff heat deflector firestop 20 to 48 flexible pipe and adapter 2 1 Vertical Termination Cap 980 3 6 6 Pipe Length galvanized 908 3 6 9 Pipe Length galvanized...

Страница 51: ...uirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed Massachusetts Residents Only Please read and follow these...

Страница 52: ...52 53D0419 NOTES...

Страница 53: ...53D0419 53 NOTES...

Страница 54: ...54 53D0419 NOTES...

Страница 55: ...ed Lifetime Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner assem...

Страница 56: ...OCTOBER 2008 P N 63D0419 Rev 9 MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Отзывы: