B36LA & B36RA Woodburning Fireplaces
TRIM INSTALLATION
Installation of Noncombustible Facing Materials to the Front Face of the Fireplace
�����
�������������������
����
Noncombustible Facing
Material
Do Not Install Combustible
Framing or Trim Below Top
Edge of Fireplace
Figure 30
CAUTION:
Do not allow any trim materials to extend closer than 3/8 inch to the vertical edges of the
firebox opening if glass doors are to be installed.
Use Only Noncombustible Materials
Below Top of Spacers
Fireplace Face
Steel Lintel
(Optional)
CAUTION:
Do not cover or
restrict vent areas with any trim
materials.
WARNING:
The space between the face
of the fireplace and the noncombustible
facing material must be sealed. Failure to
properly seal this crack can cause a pos-
sible fire hazard and will void the MHSC
warranty.
M1002
Mantel install
8/08
Figure 31
Do Not Install Combustible
Framing or Trim Below Top
Edge of Fireplace
Combustible Mantel
Top Edge of Fireplace
18” Min. From Fireplace Opening to
Bottom of Combustible Mantel
(Manufacturer Recommendation)
Top Edge of Fireplace Opening
Top of Fireplace
Opening
* For B Models, facing
materials can be brought
to the top of the fireplace
opening
NOTE:
On B36LA or B36RA Models, noncombustible facing materials may be installed to the top of
the fireplace opening. This facing material must be secured and sealed to the face of the fireplace.
Failure to properly secure and seal noncombustible facing material to the fireplace can cause a
possible fire hazard and will void the warranty.
Mantel Installation
Do Not Install Combustible
Facing Material Below Top
Edge of Fireplace
Air Inlet Opening
M1021
CAUTION: Never block bottom air
inlet opening. Covering the bot-
tom air inlet openings of the fire-
place may cuase a fire hazard.
Hearth Exten-
sion
Safety Strip
Outside
Air Inlet
Insulate Outer and Inner
Walls of Chase Always Main-
taining Proper Clearance
1” Air Space to Rear
of Fireplace
1/2” Air space to Side
of Fireplace
M1002