22 | ACX2120H | Maintenance
en
10.3
Self leak test
t
This test is designed to check the internal ACX2120H circuit
for any leaks.
To perform Self leak test:
1.
From the
MAINTENANCE
menu, press
ª©
until
SELF LEAK
TEST
is highlighted and press
.
2.
Allow unit to perform test to completion.
Fig. 23:
Self leak test screen
t
If a test fails, check charge hoses and quick couplers for
r
repeat test.
10.4
Cylinder pressure check
1.
From the
MAINTENANCE
menu, press
ª©
until
CYLINDER
PRESSURE CHECK
is highlighted and press
.
2.
Screen will display message shown in Fig. 24.
Fig. 24:
Cylinder pressure check screen
3.
Press stop once HP (red) gauge displays pressure inside
tank.
10.5
Cylinder refrigerant view
1.
From the
MAINTENANCE
menu, press
ª©
until
CYLINDER
REFRIGERANT VIEW
is highlighted and press
.
2.
Screen will display the Total refrigerant weight and the Avail -
able refrigerant weight.
Fig. 25:
Refrigerant weight screen
t
Available refrigerant weight is 2kg less than total contents of
cylinder. 2kg is the minimum quantity that should be left in
an operating ACX2120H.
10.6
Pressure zero
t
This function allows technician to determine and store the
atmospheric pressure value.
1.
From the
MAINTENANCE
menu, press
ª©
until
PRESSURE
ZERO
is highlighted and press
.
m
This procedure should be performed every time the
ACX2120H is moved from one location to another that has a
rent altitude.
10.7
Counters
t
These screens will display the vacuum pump and compres -
sor hours of life and the remaining time before vacuum
ter dryer need replacement.
1.
From the
MAINTENANCE
menu,
press
ª©
until
COUNTERS
is highlighted and press
.
2.
Press
ª©
to display all counters.
Fig. 26:
Counters