APPENDIX 6 – TROUBLE SHOOTING

Before approach the unit wear the personal protective 

The responsibility for the effects on people, animals or property resulting from inspection and repair work is entirely attri

the technician who works on the equipment. The suggestions given on the following pages are only indicative and 

manufacturer declines all responsibility for them.

MALFUNCTION 

POSSIBLE CAUSE

During the recovery phase 
there is an evident refrigerant 
leak from the exhausted oil 
container. 
The leak test is negative. 

Dirt inside the Oil 
discharge solenoid valve.

During the automatic cycle it 
is not possible to recover the 
oil. 

Oil loading cell out of 
calibration or defective.

Vacuum pump emits 
disturbing vibrations 

Defective vacuum pump

After the vacuum phase the 
leak test has a negative result. 

This may occur when the 
vacuum time is too 
4-5 minutes. 
 

Hoses emptying not 
completed with system under 
pressure 
 

Gas leakage from internal 
cylinder/tank 
or compressor 
malfunction  

Hoses emptying not 
completed. 
With pressure at 0 bar (empty 
circuit) 

Pressure sensor not 
calibrated  

First filling procedure not 
correctly carried out. 

Mistake during procedure.

Alarm A 002 Pressure switch 
intervention (compressor does 
not start) 

High pressure inside the 
recovery group
Check valve before 
condenser blocked 
Manual valve before 
internal bottle closed 

 

| ACX380/480

TROUBLE SHOOTING  

Before approach the unit wear the personal protective systems 

The responsibility for the effects on people, animals or property resulting from inspection and repair work is entirely attri

the technician who works on the equipment. The suggestions given on the following pages are only indicative and 

manufacturer declines all responsibility for them. 

 

POSSIBLE CAUSE 

POSSIBLE SOLUTION 

Dirt inside the Oil 
discharge solenoid valve. 

1. Cleaning of the solenoid valve OUT – S. 
2. Check of the gasket efficiency. 
3. calibrate pressure sensor 

Oil loading cell out of 
calibration or defective. 

1. Calibration of the exhausted oil scales. 
2. Replace if needed. 

Defective vacuum pump 

Vacuum pump replacement 

This may occur when the 
vacuum time is too short, 

When a vacuum time less than 20 minutes is set, the following message 
appears: 
“Less than 20 minutes of vacuum do not guarantee the execution of a 
correct procedure. Continue?”. 
The solution is keeping to the 20 minutes vacuum time.

Gas leakage from internal 

or compressor 

check for leaks from valves R. 
or check compressor functioning  
 

Pressure sensor not 

Altitude compensation 
and/or full pressure calibration 

Mistake during procedure. 

Altitude compensation 
and/or full pressure calibration 

High pressure inside the 
recovery group 
Check valve before 

blocked  

before 

closed  

Verify if internal bottle pressure level is over 18 bar, if yes: wait for 
pressure reduction, or uncondensable gases discharge.
If not: use personal safety protections, open equipment and check:

1)

 

Internal bottle “refrigerant pressure” is >= 18 bar inside menu 
“Maintenance” and submenu “unit values view”) 
pressure reduction or uncondensable  

2)

 

Check if inlet valve (red valve knob)  

• 

Status closed - open the valve and wait 
the pressure reduction

• 

Status open – wait for pressure reduction

3)

 

If not fixed with previous actions - it is necessary to 
investigate the following items 

• 

the pressure safety switch status

• 

the check-valve (one-way valve on condenser)

4)

 

Measure the pressure between the compressor and 
condenser HP side of recovery group (use a ¼ SAE hose with 
connector to open internal valve and a pressure gage) 

5)

 

if pressure is  

• 

<18 bar the pressure switch need to be 
not activated (circuit closed) 

• 

>18 bar the pressure switch need to be 
activated (circuit open) 

i.e. if pressure is 10 bar and pressure switch is activated (circuit open) 
change it with a new original pressure switch 

ACX380/480 | 40       en

 

The responsibility for the effects on people, animals or property resulting from inspection and repair work is entirely attributable to 

the technician who works on the equipment. The suggestions given on the following pages are only indicative and the 

When a vacuum time less than 20 minutes is set, the following message 

“Less than 20 minutes of vacuum do not guarantee the execution of a 

The solution is keeping to the 20 minutes vacuum time. 

pressure level is over 18 bar, if yes: wait for 

uction, or uncondensable gases discharge. 

If not: use personal safety protections, open equipment and check: 

“refrigerant pressure” is >= 18 bar inside menu 

“Maintenance” and submenu “unit values view”) – wait for 

 

open the valve and wait 

the pressure reduction 

wait for pressure reduction 

it is necessary to 

safety switch status 

way valve on condenser) 

Measure the pressure between the compressor and 
condenser HP side of recovery group (use a ¼ SAE hose with 
connector to open internal valve and a pressure gage)  

pressure switch need to be 

not activated (circuit closed)  
>18 bar the pressure switch need to be 
activated (circuit open)  

i.e. if pressure is 10 bar and pressure switch is activated (circuit open) 

Содержание ACX380

Страница 1: ...MAHLE ACX380 480 EN Service Manual A C Service Equipment...

Страница 2: ...rigerant fluid circuit 17 11 1 Refrigerant fluid circuit 17 11 2 Operational cycles 18 11 3 Receiving tank refrigerant cylinder 18 11 4 Manifold charts 18 11 5 NITROGEN TEST and FORMING GAS LEAK TEST...

Страница 3: ...ing of the planet The release of refrigerant gas R134a into the atmosphere is forbidden by laws that were enacted within the framework of the Kyoto protocol For information only we will mention in par...

Страница 4: ...h an original spare part or equivalent by a MAHLE centre Before opening the service station extract completely the supply cable from the plug or you can get an electric shock Do not tamper with or byp...

Страница 5: ...f instructed or certified for the equipment open the equipment The equipment parts which can cause electrocution shut off power to the equipment before servicing repairing it 2 3 Safety devices The A...

Страница 6: ...by the vehicle s manufacturer Charge filling of refrigerant into the A C system in the amount specified by the manufacturer System flushing Cleaning phase for the removal of possible polluting substa...

Страница 7: ...ant recovery and recharging Vacuum generation Flushing 4 2 Scope of delivery Description Service hose high pressure Service hose low pressure Quick release coupling high pressure Quick release couplin...

Страница 8: ...are available on the display Icon Description Device connected via WiFi The residual refrigerant weight in kg and with visual bar to enable disable the bar by vertically swiping your finger from top t...

Страница 9: ...menu The Main menu of the graphical user interface allows to select the following functions Vehicle selection OneClick Cycles Additional Functions Maintenance Setup Secured Service not available for u...

Страница 10: ...014 68 EU IV Pneumatic fittings Net length of external HP and LP hoses 4 5 m HP and LP Analog 80 mm pressure gauges pulse free 1 0 class Display Touch screen 7 TFT colours Keypad Touch screen Software...

Страница 11: ...for correct handling shall be ensured as provided for by accident prevention provisions POSITIONING Place the unit in a stable place The location must be well ventilated with a good rate of change of...

Страница 12: ...coupler Tanks without plunger have only one valve so they must be turned upside down to transfer the liquid refrigerant The LP gauge indicates the pressure inside the external tank After some minutes...

Страница 13: ...side the auto vehicle A C system To fill the UV dye bottle Fig 1 Pos 9 it has to be extracted from its housing by means of the quick coupler on the top of the bottle slightly press downward the couple...

Страница 14: ...the garage data to be printed at the bottom of the cycle report LANGUAGE by selecting this entry any language present in the database may be set In case you choose a language with unintelligible char...

Страница 15: ...ot connected to the bottle station accessories kit when the next message is displayed Fig 16 LP quick coupler opening Turn the LP quick coupler clockwise to open it and press enter OK so that air gets...

Страница 16: ...pening Turn the LP quick coupler clockwise to open it and press enter OK so that air gets into the LP hose Wait for the message to connect the reference gauge contained in the service kit and by rotat...

Страница 17: ...far from the value of the certified reference weight the result is negative in this case is not possible to update calibration It is necessary to carry out the 3 points Gas weight calibration mention...

Страница 18: ...ation is not jeopardized VESSEL 20l Category III Dir 2014 68 EU Fig 20 Refrigerant internal bottle SAFETY VALVE GAS AIRTEK VS14NPT20HNBRPED4 PS 20 bar R 1 4 NPT Category IV Dir 2014 68 EU 11 4 Manifol...

Страница 19: ...n MAHLE Fig 22 Manifold circuit Fig 23 Manifold valves Fig 24 Manifold with pressure sensors installed V A I R L1 V A I L2 R T1 T1 L1 R A V PS TP PS HP PS LP One way valve L2 V A I L2 R T1 L1 R A V PS...

Страница 20: ...LD The unit has a second manifold dedicated to nitrogen test the identification letters of the sectioning valves are highlighted is reported as follows T2 nitrogen input N IN X nitrogen output N OUT X...

Страница 21: ...izes when air is absent and when in contact with metal its aim is preventing slackening caused by impacts and vibrations Yet after application and fixing onto the junction thread you must tighten and...

Страница 22: ...and scroll to MAINTENANCE and then select Fig 26 Maintenance screens Only for model ACX380 REFRIGERANT TYPE CHANGE With this function allows the service assistance technician to change the Refrigeran...

Страница 23: ...he main menu select MAINTENANCE and press PRESSURES ZERO This function allows to determine and store the at pressure value We recommend running this procedure every time the A C service station will b...

Страница 24: ...er to zero and to start the filter replacement procedure Insert the code of the new filter Now you can replace the filter Required tools 1 flat screwdriver 1 cross screwdriver 1 regular or torque Hex...

Страница 25: ...and press CALIBRATION CHECK This function allows to check the status of gas weight scale measure with a reference weight from 100 g to 10000 g maximum not included in the scope of delivery When reque...

Страница 26: ...ovide for a the bodies in charge after the results of the previous checks performed of commissioning or period requalification do not establish different The checks must be performed by the bodies in...

Страница 27: ...install the specific components for use of R1234yf He will also carry nfigurations and verifications required by the the MAINTENANCE 14 17 Replacing white sample filter Refrigerant identification unit...

Страница 28: ...ronic power board Replacement of power supply board 15 2 Extraordinary maintenance 15 2 1 Replacement of component connected to refrigerant circuit The components pressurised equipment constituting co...

Страница 29: ...tery Evident damage to board components and circuits For the replacement of the board it is recommended to position the new board alongside the one to be replaced Disconnect and reconnect the cables i...

Страница 30: ...C SERVICE STATION ACX380 480 Blue LP quick coupler and red HP quick coupler Active Oil Protection kit 2 pcs New Oil 1 UV dye rts are available through the Service Centers USING NON ORIGINAL UNAPPROVE...

Страница 31: ...en 31 ACX380 480 APPENDIX 1 REFRIGERANT FLUID CIRCUIT ACX380 480 H...

Страница 32: ...ACX380 480 32 en APPENDIX 2 REFRIGERANT FLUID CIRCUIT ACX380 480 OPERATIONAL CYCLES Uncondensable gases H...

Страница 33: ...en 33 ACX380 480 Recovery cycle H...

Страница 34: ...ACX380 480 34 en Vacuum H...

Страница 35: ...en 35 ACX380 480 Recharge H...

Страница 36: ...load cell dye 1 10 LC New Oil1 input load cell new oil 1 11 PS Tank input pressure sensor tank 12 LC Ex Oil input load cell 13 PS LP input pressure sensor LP 14 PS HP input pressure sensor HP 15 TS Ta...

Страница 37: ...7 ACX380 480 APPENDIX 4 ACX380 480 ELECTRICAL CONNECTION POWER ELECTRONIC BOARD AND POWER SUPPLY POWER ELECTRONIC BOARD POWER SUPPLY BOARD 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 24 2...

Страница 38: ...ng 9 OUT H Heat exchanger fan 10 OUT I HP LP solenoid interconnection valve 11 OUT N Solenoid valve for draining of tank s uncondensable gases 12 OUT V Vacuum pump 13 OUT V Vacuum solenoid valve coupl...

Страница 39: ...n 39 ACX380 480 APPENDIX 5 ACX380 480 ELECTRICAL CONNECTION STATUS AND WARNING INDICATOR LIGHT ELECTRONIC BOARD Item label Description Connected Unused x 1 SER I O serial I O interface to power board...

Страница 40: ...compressor check for leaks from valves R or check compressor functioning Pressure sensor not Altitude compensation and or full pressure calibration Mistake during procedure Altitude compensation and...

Страница 41: ...acuum pump oil When the filter capacity is the filter capacity is finished Change filter with new one During the setting of the inner tank charge amount Amount required greater than that available in...

Страница 42: ...d or damaged To check electrical connections or change with new spare part During vacuum bottle filling or leak test phase in vacuum The vehicle A C system is pressurized Recover the refrigerant gas f...

Страница 43: ...leak test Empty the vehicle follow the procedure guided by the displayed messages A048 HP LEAKAGE During the gas recovery and hoses emptying phase At the end of the gas charging in the E3 Connect qui...

Страница 44: ...nalisys not possible Check with virgin refrigerant bottle if the refrigerant gas identifier is working properly If yes and the refrigerant of the car is not R1234yf empty in a safety way and in compli...

Страница 45: ...MAHLE Aftermarket Italy S p A Via Quasimodo 4 a 43126 Par ma ITALY 2019 10 28...

Отзывы: