| ACX380/4850 | 4   en

 

 

 

 

 

 
WORKPLACE:  The  station  can  work  with  both  R134a  and 
R1234yf  (the  two  refrigerants  cannot  be  stored  within  the 
station at the same time). 
Refrigerant R1234yf is defined as flammable refrigerant. 
Nonetheless,  although  refrigerant  R134a  is  not  defined  as 
flammable,  mixtures  of  air  or  oxygen  with  R134a  may 
become flammable under very particular conditions. 
The  equipment  must  be  operated  outdoor  or  in  a  well-
ventilated  location  (at  least  1  air  change  per  hour).  The 
workshop  has  to  be  equipped  with  ventilation  systems 
able  to  ensure  air  change  in  every  environment  area  or 
carry out periodical ventilation by opening the areas. 
Use  the  equipment  away  from  heat  sources  or  hot 
surfaces. The equipment must not be used in explosion risk 
environments  (potentially  explosive  atmospheres).  Before 
using it,  put  the  equipment  on  a  levelled  plane  and  secure 
position, blocking it with suitable wheel stops. 
Do not expose the tool to direct sunrays, heat sources, rain 
and  jets  of  water.  Do  not  smoke  near  the  equipment  and 
during operations (keep at a distance of at least 1 m). 
The work area must be monitored by the operator while the 
equipment is operating. 
 ATTENTION: 

R134a 

and/or 

R1234yf 

refrigerant 

fumes/gases are heavier than air and can gather on the floor 
or  inside  cavities/holes  and  cause  choke  by  reducing  the 
oxygen available for breathing. 
At high temperatures, the refrigerant breaks down releasing 
toxic  and  aggressive  substances,  harmful  for  the  operator 
and  the  environment.  Avoid  inhaling  the  system  coolants 
and oils. Exposure can irritate eyes and the respiratory tract. 
 

 

 
ELECTRICAL  CONNECTION:  Connect  the  power  cord 
solely  to  a  mains  supply  which  conforms  to  the  ratings  on 
the  machine's  nameplate  (mounted  on  its  side).  Make  sure 
the mains socket is grounded. 
Maximum impedance allowed in the point of connection to 
the  mains  shall  comply  with  standard  EN  61000-3-11. 
Starting currents can cause short voltage drops, which may 
affect  other  equipments  under  unfavourable  conditions.  If 
impedance  in  the  point  of  connection  to  the  mains  is  not 
compliant,  this  may  lead  to  interference  so  please  consult 
the electrical power network operator before connecting the 
equipment. 
Never use the service station with a defective power cord or 
a  different  one  from  that  supplied  with  the  machine.  If 
damaged,  immediately  have  it  replaced  with  an  original 
spare  part  or  equivalent  by  a  MAHLE  centre.  Before 
opening  the  service  station,  extract  completely  the  supply 
cable from the plug, or you can get an electric shock. 
Do  not  tamper  with  or  bypass  the  safety  equipment  and 
settings. 
Do not leave the machine powered up when not in use; shut 
off  the  power  supply  before  leaving  the  equipment  unused 

for  a  long  time.  Do  not  forget  that  the  tool  (pressure  tool)  must 
always be protected.  
 

 

 
REFRIGERANTS  AND  LUBRICANTS  -  PERSONAL  SAFETY 
EQUIPMENT  AND  PRECAUTIONS:  The  refrigerants  and  the 
pressure cylinders have to be handled with care, otherwise there will 
be possible health risks.  
The  operator  must  wear  safety  glasses,  gloves  and  protective 
clothing suitable to the work. Contact with the refrigerant can cause 
blindness  (eyes)  and  other  physical  damages  (freezing)  to  the 
operator.  Avoid  contact  with  the  skin;  the  refrigerant's  low  boiling 
point (approx. –26 °C for R134a and approx. -30 °C for R1234yf) can 
cause freezing burns.  
Further  information  about  safety  can  be  obtained  from  the  safety 
sheets of lubricant and refrigerant producers. 
Do  not  inhale  refrigerant  or  oil  vapour.  Keep  away  from  the  vent 
valves  and  ventilation  coupling,  especially  when  non-condensable 
gas is being vented. 
Never  direct  the  quick  couplings  (taps)  towards  your  face  or  other 
persons or animals.  
 

 

 
OTHER  PROHIBITIONS  AND  USE  LIMITATIONS:  Only  use  pure 
R134a  or  R1234yf  refrigerants,  refrain  from  using  on  vehicles 
containing  other  types  of  refrigerants  or  mixtures  of  the  two 
refrigerants  or  other  refrigerants.  Mixture  with  other  types  of 
refrigerant produces serious damage to the conditioning and cooling 
systems. Mixed refrigerants have to be disposed of according to 
the  current  regulations.  Never  use  ACX  equipment  with  systems 
containing compressed air; mixtures of R134a or R1234yf with air or 
oxygen may be potentially flammable. 
Do not modify calibration of safety devices. Do not remove seals of 
safety  valves  and  of  control  systems.  Do  not  use  external  tanks  or 
other  storage  containers  that  are  not  type-approved  or  without 
safety valves.  
Make  sure  the  equipment's  aeration  and  ventilation  ports  are  not 
obstructed or covered while the equipment is operating. 
 

 

 

HOSE CONNECTIONS: Hoses may contain pressurised refrigerant. 
Before  changing  the  service  couplers,  check  the  respective 
pressures in the hoses (pressure gauge).  
Before connection to a car A/C system, to an external tank/cylinder, 
check  that  the  quick  couplers  are  closed  (unscrewed  HP  and  LP 
valves).  
Scrupulously follow the instructions on the equipment's display. 
 
 
 
 
 

 

Содержание ACX380

Страница 1: ...MAHLE ACX380 480 EN Service Manual A C Service Equipment...

Страница 2: ...rigerant fluid circuit 17 11 1 Refrigerant fluid circuit 17 11 2 Operational cycles 18 11 3 Receiving tank refrigerant cylinder 18 11 4 Manifold charts 18 11 5 NITROGEN TEST and FORMING GAS LEAK TEST...

Страница 3: ...ing of the planet The release of refrigerant gas R134a into the atmosphere is forbidden by laws that were enacted within the framework of the Kyoto protocol For information only we will mention in par...

Страница 4: ...h an original spare part or equivalent by a MAHLE centre Before opening the service station extract completely the supply cable from the plug or you can get an electric shock Do not tamper with or byp...

Страница 5: ...f instructed or certified for the equipment open the equipment The equipment parts which can cause electrocution shut off power to the equipment before servicing repairing it 2 3 Safety devices The A...

Страница 6: ...by the vehicle s manufacturer Charge filling of refrigerant into the A C system in the amount specified by the manufacturer System flushing Cleaning phase for the removal of possible polluting substa...

Страница 7: ...ant recovery and recharging Vacuum generation Flushing 4 2 Scope of delivery Description Service hose high pressure Service hose low pressure Quick release coupling high pressure Quick release couplin...

Страница 8: ...are available on the display Icon Description Device connected via WiFi The residual refrigerant weight in kg and with visual bar to enable disable the bar by vertically swiping your finger from top t...

Страница 9: ...menu The Main menu of the graphical user interface allows to select the following functions Vehicle selection OneClick Cycles Additional Functions Maintenance Setup Secured Service not available for u...

Страница 10: ...014 68 EU IV Pneumatic fittings Net length of external HP and LP hoses 4 5 m HP and LP Analog 80 mm pressure gauges pulse free 1 0 class Display Touch screen 7 TFT colours Keypad Touch screen Software...

Страница 11: ...for correct handling shall be ensured as provided for by accident prevention provisions POSITIONING Place the unit in a stable place The location must be well ventilated with a good rate of change of...

Страница 12: ...coupler Tanks without plunger have only one valve so they must be turned upside down to transfer the liquid refrigerant The LP gauge indicates the pressure inside the external tank After some minutes...

Страница 13: ...side the auto vehicle A C system To fill the UV dye bottle Fig 1 Pos 9 it has to be extracted from its housing by means of the quick coupler on the top of the bottle slightly press downward the couple...

Страница 14: ...the garage data to be printed at the bottom of the cycle report LANGUAGE by selecting this entry any language present in the database may be set In case you choose a language with unintelligible char...

Страница 15: ...ot connected to the bottle station accessories kit when the next message is displayed Fig 16 LP quick coupler opening Turn the LP quick coupler clockwise to open it and press enter OK so that air gets...

Страница 16: ...pening Turn the LP quick coupler clockwise to open it and press enter OK so that air gets into the LP hose Wait for the message to connect the reference gauge contained in the service kit and by rotat...

Страница 17: ...far from the value of the certified reference weight the result is negative in this case is not possible to update calibration It is necessary to carry out the 3 points Gas weight calibration mention...

Страница 18: ...ation is not jeopardized VESSEL 20l Category III Dir 2014 68 EU Fig 20 Refrigerant internal bottle SAFETY VALVE GAS AIRTEK VS14NPT20HNBRPED4 PS 20 bar R 1 4 NPT Category IV Dir 2014 68 EU 11 4 Manifol...

Страница 19: ...n MAHLE Fig 22 Manifold circuit Fig 23 Manifold valves Fig 24 Manifold with pressure sensors installed V A I R L1 V A I L2 R T1 T1 L1 R A V PS TP PS HP PS LP One way valve L2 V A I L2 R T1 L1 R A V PS...

Страница 20: ...LD The unit has a second manifold dedicated to nitrogen test the identification letters of the sectioning valves are highlighted is reported as follows T2 nitrogen input N IN X nitrogen output N OUT X...

Страница 21: ...izes when air is absent and when in contact with metal its aim is preventing slackening caused by impacts and vibrations Yet after application and fixing onto the junction thread you must tighten and...

Страница 22: ...and scroll to MAINTENANCE and then select Fig 26 Maintenance screens Only for model ACX380 REFRIGERANT TYPE CHANGE With this function allows the service assistance technician to change the Refrigeran...

Страница 23: ...he main menu select MAINTENANCE and press PRESSURES ZERO This function allows to determine and store the at pressure value We recommend running this procedure every time the A C service station will b...

Страница 24: ...er to zero and to start the filter replacement procedure Insert the code of the new filter Now you can replace the filter Required tools 1 flat screwdriver 1 cross screwdriver 1 regular or torque Hex...

Страница 25: ...and press CALIBRATION CHECK This function allows to check the status of gas weight scale measure with a reference weight from 100 g to 10000 g maximum not included in the scope of delivery When reque...

Страница 26: ...ovide for a the bodies in charge after the results of the previous checks performed of commissioning or period requalification do not establish different The checks must be performed by the bodies in...

Страница 27: ...install the specific components for use of R1234yf He will also carry nfigurations and verifications required by the the MAINTENANCE 14 17 Replacing white sample filter Refrigerant identification unit...

Страница 28: ...ronic power board Replacement of power supply board 15 2 Extraordinary maintenance 15 2 1 Replacement of component connected to refrigerant circuit The components pressurised equipment constituting co...

Страница 29: ...tery Evident damage to board components and circuits For the replacement of the board it is recommended to position the new board alongside the one to be replaced Disconnect and reconnect the cables i...

Страница 30: ...C SERVICE STATION ACX380 480 Blue LP quick coupler and red HP quick coupler Active Oil Protection kit 2 pcs New Oil 1 UV dye rts are available through the Service Centers USING NON ORIGINAL UNAPPROVE...

Страница 31: ...en 31 ACX380 480 APPENDIX 1 REFRIGERANT FLUID CIRCUIT ACX380 480 H...

Страница 32: ...ACX380 480 32 en APPENDIX 2 REFRIGERANT FLUID CIRCUIT ACX380 480 OPERATIONAL CYCLES Uncondensable gases H...

Страница 33: ...en 33 ACX380 480 Recovery cycle H...

Страница 34: ...ACX380 480 34 en Vacuum H...

Страница 35: ...en 35 ACX380 480 Recharge H...

Страница 36: ...load cell dye 1 10 LC New Oil1 input load cell new oil 1 11 PS Tank input pressure sensor tank 12 LC Ex Oil input load cell 13 PS LP input pressure sensor LP 14 PS HP input pressure sensor HP 15 TS Ta...

Страница 37: ...7 ACX380 480 APPENDIX 4 ACX380 480 ELECTRICAL CONNECTION POWER ELECTRONIC BOARD AND POWER SUPPLY POWER ELECTRONIC BOARD POWER SUPPLY BOARD 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 24 2...

Страница 38: ...ng 9 OUT H Heat exchanger fan 10 OUT I HP LP solenoid interconnection valve 11 OUT N Solenoid valve for draining of tank s uncondensable gases 12 OUT V Vacuum pump 13 OUT V Vacuum solenoid valve coupl...

Страница 39: ...n 39 ACX380 480 APPENDIX 5 ACX380 480 ELECTRICAL CONNECTION STATUS AND WARNING INDICATOR LIGHT ELECTRONIC BOARD Item label Description Connected Unused x 1 SER I O serial I O interface to power board...

Страница 40: ...compressor check for leaks from valves R or check compressor functioning Pressure sensor not Altitude compensation and or full pressure calibration Mistake during procedure Altitude compensation and...

Страница 41: ...acuum pump oil When the filter capacity is the filter capacity is finished Change filter with new one During the setting of the inner tank charge amount Amount required greater than that available in...

Страница 42: ...d or damaged To check electrical connections or change with new spare part During vacuum bottle filling or leak test phase in vacuum The vehicle A C system is pressurized Recover the refrigerant gas f...

Страница 43: ...leak test Empty the vehicle follow the procedure guided by the displayed messages A048 HP LEAKAGE During the gas recovery and hoses emptying phase At the end of the gas charging in the E3 Connect qui...

Страница 44: ...nalisys not possible Check with virgin refrigerant bottle if the refrigerant gas identifier is working properly If yes and the refrigerant of the car is not R1234yf empty in a safety way and in compli...

Страница 45: ...MAHLE Aftermarket Italy S p A Via Quasimodo 4 a 43126 Par ma ITALY 2019 10 28...

Отзывы: