10

MM-RC Remote Only

The MM-RC provides three additional charging LED indicators to provide

information on the operation of the battery charger. Monitor these

indicators for at least 10 seconds to determine the charger status.
BULK  (yellow)  -

• On (solid) - Bulk Charging; the charger is delivering maximum current

to the batteries. The charger will remain in Bulk charge until 14.6 VDC*

is achieved (determined by the Battery Type selection**).
• Blinks On (1 time every 4 seconds) - Charger Back-off; charger

current is reduced. This occurs if: 1. The internal temperature is very

hot (the charger reduces the charge rate to maintain temperature);

or 2. The AC input voltage has fallen below 85 VAC (the charger

reduces the charge rate to help stabilize the incoming AC voltage).

• Off - 

charger is not in Bulk charge mode.

ABSORB  (yellow)  -

• On (solid) - Absorb Charging; the charger is in constant voltage

stage and begins after the bulk voltage has been reached. The DC

charging current will start to taper down in order to maintain the Bulk

voltage setting. The Absorb Charging time is 120 minutes

(determined by the Battery AmpHrs selection**).
• Blinks On (1 time every 4 seconds) - Charger Back-off; charger

current is reduced. This occurs if: 1. The internal temperature is very

hot (the charger reduces the charge rate to maintain temperature);

or 2. The AC input voltage has fallen below 85 VAC (the charger

reduces the charge rate to help stabilize the incoming AC voltage).

• Off - charger is not in Absorption charge mode.

FLOAT  (green)  -

• On (solid) - Float Charging; at the end of the Absorb Charging time,

the charger reduces the charge voltage to maintain the batteries at

13.4* VDC (determined by the Battery Type selection**).
• Blinks On (1 time every 4 seconds) - Charger Back-off; charger

current is reduced. This occurs if: 1. The internal temperature is very

hot (the charger reduces the charge rate to maintain temperature);

or 2. The AC input voltage has fallen below 85 VAC (the charger

reduces the charge rate to help stabilize the incoming AC voltage).
• Blinks On (2 times every 4 seconds) - Full Charge; this mode

monitors the battery voltage to determine when to continue charging.

After four hours in the Float Charge mode, the charger turns off and

goes to Full Charge mode. If the battery voltage drops to 12.9 VDC,

the charger will automatically initiate another Float Charge.
• Off - charger is not in Float Charge mode.
* These voltage settings are based on the BTS being disconnected; if

connected, these voltage settings will increase or decrease depending

on temperature around the BTS - this ensures correct charging.
** These settings are preset by the inverter or the connected remote

(see Table 1, Inverter and Remote Settings), but can be changed by

the ME-RC50 remote.

3.0 Operation

Содержание MM Series

Страница 1: ...Installation and Operation Guide Remote Controls for MM Series Inverters...

Страница 2: ...2006 Magnum Energy Inc...

Страница 3: ...y Inc 1111 80th Street SW Suite 250 Everett WA 98203 phone 425 353 8833 fax 425 353 8390 web www magnumenergy com Product Safety Instructions Read and follow all instructions and safety information co...

Страница 4: ...FF Switch 7 Monitoring the LED Indicators 8 MM R and MM RC Remotes 8 MM RC Remote Only 10 4 0 Warranty and Service Information 11 List of Figures Figure 1 MM Remotes 1 Figure 2 Communications Cable Co...

Страница 5: ...with 25 cable This remote is for MM Series inverters without the battery charger feature such as the MM612 requires serial number L1 201 or higher or MM612G models MM RC Provides six LED indicators fo...

Страница 6: ...ted place Plan the cable route from the remote to the inverter to ensure there are no obstructions that can t be overcome before you do any cutting or drilling Allow ample room to access the ON OFF sw...

Страница 7: ...dimensions DO NOT cut the opening too big to ensure there are no cracks around the display and that there is enough material for the screws to secure the display Remove any wall insulation if applicab...

Страница 8: ...d cut break the appropriate tab on the mounting ring 4 Pull the cable through the mounting ring and place the ring with the removed tab over the communication cable against the wall 5 Position the mou...

Страница 9: ...2006 Magnum Energy Inc Figure 5 Remote Display Dimensions Figure 6 Mounting Ring Dimensions 2 0 Installation 5 BULK ABSORB FLOAT INVERT AC IN FAULT ON OFF Side Front Side Front...

Страница 10: ...a tion Guide to help clear the fault condition Factory Default Settings Your MM Series inverter has many functions that have changeable settings These settings are preset and loaded by the inverter wh...

Страница 11: ...battery charger feature this switch can also be used to disable the charger Charger Standby so that all the incoming power can be used exclusively for the AC loads To turn the charger off press and h...

Страница 12: ...energy from the battery to supply AC power to the loads connected to the inverter and AC IN LED indicator is On solid The inverter is in Standby The external AC power Utility or generator connected to...

Страница 13: ...s Over temperature condition The internal temperature of the inverter has risen above acceptable limits caused by loads too great for the inverter to operate continuously or by lack of ventilation to...

Страница 14: ...arger reduces the charge rate to maintain temperature or 2 The AC input voltage has fallen below 85 VAC the charger reduces the charge rate to help stabilize the incoming AC voltage Off charger is not...

Страница 15: ...ir determined by the price paid by the original purchaser Magnum Energy shall not be liable for any other losses or damages 4 Upon request from Magnum Energy the original purchaser must prove the prod...

Страница 16: ...2006 Magnum Energy Inc Magnum Energy Inc 1111 80th Street SW Suite 250 Everett WA 98203 phone 425 353 8833 fax 425 353 8390 web www magnumenergy com PN 64 00012...

Отзывы: