3.0 Operation

3.0 Operation

Start-up

After Installing and connecting the MM Series remote control, the

remote should be tested to ensure it is functional.
1. Press the ON/OFF push-button located on the display panel.

Note: The ON/OFF control switch is a push-button switch which

functions by momentary pressing and releasing.

2. After pressing the ON/OFF switch, verify the INVERT indicator

(green LED) is on (solid or blinking) and the status indicator on the

MM Series inverter is also on.

3. Press the ON/OFF switch again to turn the inverter off and verify

the INVERT indicator on the remote and the status indicator on the

inverter both go off.

If the remote passes all the steps, the inverter is ready for use.
If the remote fails any of the steps fails, check all the connections at

both ends of the communications cable and ensure the inverter is

operational. If the FAULT indicator comes on, refer to the Trouble-

shooting section in the MM Series Inverters, Installation and Opera-

tion Guide to help clear the fault condition.

Factory Default Settings

Your MM Series inverter has many functions that have changeable

settings. These settings are preset and loaded by the inverter when

turned on. However, if the MM remote control is connected to the

inverter, the settings from the remote over-ride any default settings

in the inverter. The settings in the remote are saved in the remote’s

non-volatile memory and will be used - even if DC power to the

inverter is lost - as long as the remote is connected. See Table 1 for

the inverter’s default settings and the settings that are changed when

connected to the MM remote.

Function

Inverter Settings

Remote Settings

Search Watts

NA (MM612 / MM612G),

5W (all other MM Series)

NA (MM612 / MM612G),

5W (all other MM Series)

LowBatCutOut

10.0 VDC

10.0 VDC

400 AmpHrs

400 AmpHrs

(Absorb Time = 120 minutes)

(Absorb Time = 120 minutes)

Flooded - Liquid Lead Acid

Flooded - Liquid Lead Acid

(Bulk = 14.6 VDC,

(Bulk = 14.6 VDC,

Float = 13.4 VDC)

Float = 13.4 VDC)

Charge Rate

100%

100%

VAC dropout

80VAC

90VAC

Battery AmpHrs

Battery Type

Table 1, Inverter and Remote Settings

Note: For more information on these settings, refer to the MM

Series Inverters, Installation and Operation Guide.

Содержание MM Series

Страница 1: ...Installation and Operation Guide Remote Controls for MM Series Inverters...

Страница 2: ...2006 Magnum Energy Inc...

Страница 3: ...y Inc 1111 80th Street SW Suite 250 Everett WA 98203 phone 425 353 8833 fax 425 353 8390 web www magnumenergy com Product Safety Instructions Read and follow all instructions and safety information co...

Страница 4: ...FF Switch 7 Monitoring the LED Indicators 8 MM R and MM RC Remotes 8 MM RC Remote Only 10 4 0 Warranty and Service Information 11 List of Figures Figure 1 MM Remotes 1 Figure 2 Communications Cable Co...

Страница 5: ...with 25 cable This remote is for MM Series inverters without the battery charger feature such as the MM612 requires serial number L1 201 or higher or MM612G models MM RC Provides six LED indicators fo...

Страница 6: ...ted place Plan the cable route from the remote to the inverter to ensure there are no obstructions that can t be overcome before you do any cutting or drilling Allow ample room to access the ON OFF sw...

Страница 7: ...dimensions DO NOT cut the opening too big to ensure there are no cracks around the display and that there is enough material for the screws to secure the display Remove any wall insulation if applicab...

Страница 8: ...d cut break the appropriate tab on the mounting ring 4 Pull the cable through the mounting ring and place the ring with the removed tab over the communication cable against the wall 5 Position the mou...

Страница 9: ...2006 Magnum Energy Inc Figure 5 Remote Display Dimensions Figure 6 Mounting Ring Dimensions 2 0 Installation 5 BULK ABSORB FLOAT INVERT AC IN FAULT ON OFF Side Front Side Front...

Страница 10: ...a tion Guide to help clear the fault condition Factory Default Settings Your MM Series inverter has many functions that have changeable settings These settings are preset and loaded by the inverter wh...

Страница 11: ...battery charger feature this switch can also be used to disable the charger Charger Standby so that all the incoming power can be used exclusively for the AC loads To turn the charger off press and h...

Страница 12: ...energy from the battery to supply AC power to the loads connected to the inverter and AC IN LED indicator is On solid The inverter is in Standby The external AC power Utility or generator connected to...

Страница 13: ...s Over temperature condition The internal temperature of the inverter has risen above acceptable limits caused by loads too great for the inverter to operate continuously or by lack of ventilation to...

Страница 14: ...arger reduces the charge rate to maintain temperature or 2 The AC input voltage has fallen below 85 VAC the charger reduces the charge rate to help stabilize the incoming AC voltage Off charger is not...

Страница 15: ...ir determined by the price paid by the original purchaser Magnum Energy shall not be liable for any other losses or damages 4 Upon request from Magnum Energy the original purchaser must prove the prod...

Страница 16: ...2006 Magnum Energy Inc Magnum Energy Inc 1111 80th Street SW Suite 250 Everett WA 98203 phone 425 353 8833 fax 425 353 8390 web www magnumenergy com PN 64 00012...

Отзывы: