BE 58-602 Pulsar
®
Model R96 Radar Transmitter
When the transmitter is operating normally and the high-
light cursor is positioned on Present Status, the bottom
LCD line displays “OK” because no diagnostic indicators
are active.
EVENT HISTORY
– This menu displays the parameters
related to diagnostic event logging.
ADVANCED DIAGNOSTICS
– This menu displays
parameters related to some of the advanced diagnostics
available within the Model R96.
INTERNAL VALUES
– Displays read-only internal
parameters.
ELEC TEMPERATURES
– Displays temperature
information as measured in the electronics module in
degrees F or C.
TRANSMITTER TESTS
– Allows the user to
manually set the output current to a constant value.
This is a method for the user to verify operation of the
other equipment in the loop.
ECHO CURVES
– This menu allows the user to display
the live Echo Curve on the LCD.