41
BE 58-602 Pulsar
®
Model R96 Radar Transmitter
3.3.3.2 Configuration using Custom Table
If none of the nine
Vessel Types
shown can be used, a
Custom Table
can be created. A maximum of 30 points can
be used to establish the level to volume relationship. The
following table provides an explanation of each of the
System Configuration parameters for volume applications
where a Custom Table is needed.
Configuration Parameter
Explanation (Custom Volumetric Table)
Volume Units
A selection of
Gallons, Barrels, Milliliters
,
Liters
,
Cubic Feet
, or
Cubic Inches
,
is provided.
Vessel Type
Select
Custom Table
if none of the nine
Vessel Types
can be used.
Cust Table Type
The
Custom Table
points can be a
Linear
(straight line between adjacent points) or
Spline
(can be a curved line between points) relationship. See drawing below for
more information.
Cust Table Vals
A maximum of 30 points can be used in building the
Custom Table
. Each pair of
values will have a level (height) in the units chosen in the
Level Units
screen, and
the associated volume for that level point. The values must be monotonic, i.e.,
each pair of values must be greater than the previous level/volume pair. The last
pair of values should have the highest level value and volume value associated
with the level in the vessel.
LINEAR
SPLINE
P2
P1
P1 P2
P3
P4
P5
P6
P7
P8
P9
Use where walls are not perpendicular to base.
Concentrate at least two points at beginning (P1) and end (P9);
and three points at either side of transition points.
3.3.4 Reset Function
A parameter labeled “Reset Parameter” is located at the end
of the DEVICE SETUP/ADVANCED CONFIG menu.
In the event a user gets confused during configuration or
advanced troubleshooting, this parameter gives the user the
ability to reset the Model R96 transmitter configuration.
Unique to the Model R96 transmitter is the ability for
MAGNETROL to fully “pre-configure” devices to customer
requests. For that reason, the Reset function will return the
device back to the state
at which it left the factory
.
It is recommended that MAGNETROL Technical Support
be contacted as the Advanced User password will be
required for this reset.