Model R96 Radar Transmitter
Level Units
Select the Units of measurement for the level readout:
• Inches
• Feet
• Millimeters
• Centimeters
• Meters
Tank Height
Enter tank height (in Level Units selected)
Antenna Model
Select the Antenna Model to be used with Model R96 (refer to antenna nameplate):
• RAA-x — TFE rod
• RAB-G — Polypropylene rod
• RAB-L — Polypropylene rod
• RAB-x — Polypropylene rod
• RAC-x — Halar rod
• RA3-x — 3" horn
• RA4-x — 4" horn
• RA6-x — 6" horn
Antenna Extension
0
For nozzle height
≤
25 mm (1") (for threaded process connection only)
(refer to antenna
nameplate)
:
1
For nozzle height
≤
100 mm (4")
2
For nozzle height
≤
200 mm (8")
3
For nozzle height
≤
300 mm (12")
Antenna Mount
Select the type of Antenna Mounting to the vessel (refer to antenna nameplate):
• NPT (National Pipe Thread)
• BSP (British Standard Pipe)
• Flange (ASME or EN)
Dielectric Range
Enter the Dielectric Range for the material to be measured.
Below 1.7 (Light Hydrocarbons like Propane and Butane) — (stillwell only)
1.7 to 3.0 (Most typical hydrocarbons)
3.0 to 10 (Varying dielectric, for example: mixing tanks)
Above 10 (Water-based media)
H
A
R
T
O
nl
y
4 mA Set Point
(LRV)
Enter the level value (0 %-point) for the 4 mA point. Lower Range Value (LRV).
Refer to Section 1.4.1.1.
20mA Set Point
(URV)
Enter the level value (100 %-point) for the 20 mA point. Upper Range Value (URV).
Refer to Section 1.4.1.1.
PV Alarm
Selection
Enter the desired output state when a Failure Indicator is active.
• High (22 mA)
• Low (3.6 mA)
• Hold (Hold last value is not recommended for standard configuration). Consult factory for
use.