background image

4

CALIBRATION - TRANSMITTER WITH LCD SCREENMENU: STEP BY STEP PROCEDURE

Units!

cm

Units

cm

Units!

cm

Ent Pass

0

New Pass

4096

New Pass

0000

Ent Pass!

1

Press  :

The last character on the first line of the display changes to "!". This sign confirms

that the values/choices of the second line can be modified via the  and  push

buttons.

Press  :

* Scroll through the choices or increase/decrease the values on the second line

of the display by  and  pushbuttons.

* Accept values/choices as selected by  pushbutton.

Press  :

Scroll through the menu.

20 mA Level

(100%-point)

min. 2 % of

probe length

cm or Inch

4 mA Level

(0%-point)

TERMINOLOGY

Units

cm or inches

Select the units of measurement in which the unit will be

calibrated and will show values.

20 mA Level = 

cm or inches

or  100  %  level  point,  is  measured  from  the  end  of  the

probe. Keep this reference point also for the introduction

of all future values.

Hi Cal

cm or inches

High Calibration point is the highest level from which the

calibration is performed. Hi Cal is measured from the end

of the probe.

Lo Cal

cm or inches

Low  Calibration  point  is  the  lowest  level  from  which  the

calibration is performed. Lo Cal is measured from the end

of the probe.

4 mA Level = 

cm or inches

or  0  %  level  point,  is  measured  from  the  bottom  of  the

probe.  The  4  mA  level  is  by  preferrence  located  on  the

probe.  The  unit  will  not  measure  below  the  end  of  the

probe.

"0" means that no password is introduced

Factory default setting

Press  and last character changes into "!"

Changing password

Enter a value between 1 up to 255

as your personal password with  and 

Display shows an encrypted value, enter your password

Data is protected by a valid

or call Magnetrol for assistance to recoop your password

Password

if necessary

Protect data by new password

Data is not protected

Hi Cal

Lo Cal

NOTE: The above example shows the end of the probe as reference point. Also the bottom or top of the tank can be used as refer-

ence point. Whichever point is used, it must always be used for all further values.

Display

Action

Comment

Display

Comment

Содержание Kotron 805 series

Страница 1: ...R F Capacitance Level Transmitter Installation and Operating Manual Kotron 805...

Страница 2: ...wire is xed to the PCB by means of a spade plug Disconnect white probe wire always at the probe never at the electronics see above For installation details see bulletin BE50 125 Bent probe Flexible pr...

Страница 3: ...d local current meter Ex Non Ex Ex Non Ex Ex Non Ex CAUTION ALWAYS check for proper grounding Improper grounding will cause malfunction of the unit CALIBRATION NOTE When connected to an approved barri...

Страница 4: ...is the highest level from which the calibration is performed Hi Cal is measured from the end of the probe Lo Cal cm or inches Low Calibration point is the lowest level from which the calibration is p...

Страница 5: ...r a single transmitter installation Fine tune the 4 mA point Attach a mA meter to the output If the output does not equal 4 0 mA adjust the value on the display to equal 4 00 mA Fine tune the 20 mA po...

Страница 6: ...Room Display Power Supply Current Meter 250 RL 450 CONNECTIONS Connection of your Hart communicator at power terminals and in wiring compartment at rst junction box between unit and control room HART...

Страница 7: ...HART software does not Contact manufacturer of your HART information e g Mfgs ID Device account for Mfgs ID s greater master software for upgrade This is a Serial etc but will not read any than 63 Mag...

Страница 8: ...Expedite Ship Plan ESP Parts covered by ESP service are conveniently grey coded in the selection tables 1 Electronic module Digit 5 Digit 6 Replacement part 0 1 031 2809 003 2 031 2809 023 3 031 2809...

Страница 9: ...Electronic Module Yes Yes Yes Yes Yes Yes Yes No No No No No No Display has Text No Reseat Boards Check Power Supply and Wiring Loop Resistance Wrong Correct Loop Resistance Start Good Display No Act...

Страница 10: ...lure to Operate with Correct Loop Inputs Display Working Yes No Retest Unit Good Display Key Board Responds Replace Electronic Module No Check Loop Current at Wiring Board Loop Current 22 4 0 mA Adjus...

Страница 11: ...heck Calibration Parameters Yes Yes Yes Corrupt Display Text Replace Electronic Module No Yes Replace Electronic Module Same Error Message Retest No Yes Active HART Analog Loop Correct Trim 4 20mA Che...

Страница 12: ...ish French or German Housing Material Aluminium A356T6 0 25 copper or 316 SST 1 4401 IP 66 Net and Gross Weight 2 70 kg net 3 20 kg gross Overall Dimensions H 214 mm 8 43 x W 111 mm 4 38 x D 188 mm 7...

Страница 13: ...ide view Optional Mounting Flange 3 4 NPT 1 NPT 1G 1 BSP Optional Mounting Flange Optional Anchor Assembly Optional Weight 13 0 50 bare probe 16 0 625 insulated probe 5 0 1875 6 0 2500 75 2 95 34 1 32...

Страница 14: ...T6 A complete measuring system consists of 1 Kotron 805 transmitter head electronics 2 KOTRON Probe a full range of rigid and exible probes for conductive and non conductive media is available see bu...

Страница 15: ...15 Notes...

Страница 16: ...tive material or workmanship If the trouble is the result of conditions beyond our control or is NOT covered by the warranty there will be charges for labour and the parts required to rebuild or repla...

Отзывы: