Magnetrol Kotron 805 series Скачать руководство пользователя страница 5

5

Screen

Action

Comment

Transmitter Display

Transmitter default display. Level, % Output, and Loop

values cycle every 5 seconds.

Transmitter Display

Transmitter displays Level measurement in cm or in.

Transmitter Display

Transmitter displays % Output measurement derived from the

4-20 mA span.

Transmitter Display

Transmitter displays Loop measurement (mA).

Select units for level

cm or inches.

measurement readout.

Enter level value of the low

Set level at low calibration point

calibration point

and adapt with Up and Down the displayed value

Transmitter Display

Transmitter displays capacitance at low calibration point in pF

Enter level value of the high

Set level at high calibration point

calibration point

and adapt with Up and Down the displayed value

Transmitter Display

Transmitter displays capacitance at high calibration point in pF

Enter the level value for the

4 mA level cannot be set at a lower level than the end of the probe

4 mA point.

Enter the level value for the

20 mA level cannot be set at a higher level than the top of the 

20 mA point.

probe

Enter the damping factor.

A Damping factor (1-45 seconds) may be added to smooth a 

noisy display and/or output due to turbulence.

Enter the default value.

Select 3.6 mA, 22 mA or HOLD (last value). 3.6 mA is not

valid if unit includes HART.

Enter HART ID number.

Select a HART poll address (0-15). Enter 0 for a single

transmitter installation.

Fine tune the 4 mA point.

Attach a mA meter to the output. If the output does not equal 

4.0 mA, adjust the value on the display to equal 4.00 mA.

Fine tune the 20 mA point.

Attach a mA meter to the output. If the output does not equal 

20.0 mA, adjust the value on the display to equal 20.00 mA.

Enter a mA Output value.

Set mA Output to any given value to perform loop test.

None, do not adjust.

Transmitter displays capacitance at present level

None, do not adjust.

Transmitter displays internal timing count with fixed capacitance

(factory diagnostic)

None, do not adjust.

Transmitter displays internal timing count with probe disconnected

(factory diagnostic)

None, do not adjust.

Transmitter displays internal timing count at present level

(factory diagnostic)

Reinitialize all values.

Reinitialize - choose YES to reset all configuration values

back to factory defaults.

None, do not adjust.

Transmitter displays version number of firmware

Enter new password.

Use arrows to select desired value. Values between 1 and

255

CALIBRATION - TRANSMITTER WITH LCD SCREENMENU: STEP BY STEP PROCEDURE

Ru

m

od

e

Di

ag

no

st

ic

s

Co

nfi

gu

ra

tio

n

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

22

*Level*

*%Output*

*Loop*

Level

xx.x cm

%Output

xx.x%

Loop

xx.xx mA

Units

xxx

Lo Cal

xxx.x lu

Lo Cap

Xxxx pF

Hi Cal

xxx.x lu

Hi Cap

Xxxx pF

Set 4mA

xxx.x

Set 20mA

xxx.x

Damping

xx sec

Fault

Choice

Poll Adr

xx

Trim 4

xxxx

Trim 20

xxxx

Loop Tst

xx.x mA

Prb Rdg

Xxxx pF

Osc Tst

Xxx tk

Opn Prb

xxxx tk

23

21

# Ticks

xxxx

Reint

xxx

Vern.nAa

= min. required calibration

24

New Pass

xxx

Содержание Kotron 805 series

Страница 1: ...R F Capacitance Level Transmitter Installation and Operating Manual Kotron 805...

Страница 2: ...wire is xed to the PCB by means of a spade plug Disconnect white probe wire always at the probe never at the electronics see above For installation details see bulletin BE50 125 Bent probe Flexible pr...

Страница 3: ...d local current meter Ex Non Ex Ex Non Ex Ex Non Ex CAUTION ALWAYS check for proper grounding Improper grounding will cause malfunction of the unit CALIBRATION NOTE When connected to an approved barri...

Страница 4: ...is the highest level from which the calibration is performed Hi Cal is measured from the end of the probe Lo Cal cm or inches Low Calibration point is the lowest level from which the calibration is p...

Страница 5: ...r a single transmitter installation Fine tune the 4 mA point Attach a mA meter to the output If the output does not equal 4 0 mA adjust the value on the display to equal 4 00 mA Fine tune the 20 mA po...

Страница 6: ...Room Display Power Supply Current Meter 250 RL 450 CONNECTIONS Connection of your Hart communicator at power terminals and in wiring compartment at rst junction box between unit and control room HART...

Страница 7: ...HART software does not Contact manufacturer of your HART information e g Mfgs ID Device account for Mfgs ID s greater master software for upgrade This is a Serial etc but will not read any than 63 Mag...

Страница 8: ...Expedite Ship Plan ESP Parts covered by ESP service are conveniently grey coded in the selection tables 1 Electronic module Digit 5 Digit 6 Replacement part 0 1 031 2809 003 2 031 2809 023 3 031 2809...

Страница 9: ...Electronic Module Yes Yes Yes Yes Yes Yes Yes No No No No No No Display has Text No Reseat Boards Check Power Supply and Wiring Loop Resistance Wrong Correct Loop Resistance Start Good Display No Act...

Страница 10: ...lure to Operate with Correct Loop Inputs Display Working Yes No Retest Unit Good Display Key Board Responds Replace Electronic Module No Check Loop Current at Wiring Board Loop Current 22 4 0 mA Adjus...

Страница 11: ...heck Calibration Parameters Yes Yes Yes Corrupt Display Text Replace Electronic Module No Yes Replace Electronic Module Same Error Message Retest No Yes Active HART Analog Loop Correct Trim 4 20mA Che...

Страница 12: ...ish French or German Housing Material Aluminium A356T6 0 25 copper or 316 SST 1 4401 IP 66 Net and Gross Weight 2 70 kg net 3 20 kg gross Overall Dimensions H 214 mm 8 43 x W 111 mm 4 38 x D 188 mm 7...

Страница 13: ...ide view Optional Mounting Flange 3 4 NPT 1 NPT 1G 1 BSP Optional Mounting Flange Optional Anchor Assembly Optional Weight 13 0 50 bare probe 16 0 625 insulated probe 5 0 1875 6 0 2500 75 2 95 34 1 32...

Страница 14: ...T6 A complete measuring system consists of 1 Kotron 805 transmitter head electronics 2 KOTRON Probe a full range of rigid and exible probes for conductive and non conductive media is available see bu...

Страница 15: ...15 Notes...

Страница 16: ...tive material or workmanship If the trouble is the result of conditions beyond our control or is NOT covered by the warranty there will be charges for labour and the parts required to rebuild or repla...

Отзывы: