57-606 ECLIPSE Model 706 Guided Wave Radar Transmitter
1.3
QuickStart Wiring
WARNING!
Possible explosion hazard. Do not connect or discon-
nect equipment unless power has been switched off and
the area is known to be non-hazardous.
NOTE: Ensure that the electrical wiring to the ECLIPSE Model 706
transmitter is complete and in compliance with all local regula-
tions and codes.
1. Remove the cover of the upper wiring compartment of the
Model 706 transmitter.
2. Attach a conduit fitting and mount the conduit plug in the
spare opening. Pull the power supply wire through the con-
duit fitting.
3. If present, connect cable shield to an earth ground at the
power supply.
4. Connect an earth ground to the nearest green ground screw.
(Not shown in illustration.)
5. Connect the positive supply wire to the (+) terminal and the
negative supply wire to the (-) terminal. For Explosion
Proof Installations, see Wiring, Section 2.5.3.
6. Replace and tighten the cover.
1.4
QuickStart Configuration
If requested, the ECLIPSE Model 706 transmitter is
shipped fully pre-configured for the application and can be
installed immediately. Otherwise it is shipped configured
with default values from the factory and can be easily
reconfigured in the shop.
The minimum configuration instructions required for using
the QuickStart menu follow. Use the information from the
operating parameters table in Section 1.1.2 before proceeding
with the configuration.
The QuickStart menu offers a very simple two screen
overview showing the basic parameters required for typical
“Level Only” operation.
1. Apply power to the transmitter.
The graphic LCD display can be programmed to change
every 2 seconds to show pertinent Measured Values on the
Home Screen. For example: Level, %Output, and Loop
current can all be displayed on a rotating screen.
The LCD can also be programmed to always show just one
of the Measured Variables at all times. For example: Level
can be the only value displayed on the screen.
2. Remove the lower electronic compartment cover.
Level Offset
Probe Length
Probe Mount
4 mA Level
(0%-point)
Probe Model
Dielectric
of Medium
In or Cm
20 mA
(100% Point)
NOTE: A small transition zone (0–12")
(0-300 mm) may exist at the top
and bottom of certain probes.
Red (+)
Black (-)
(+)
(-)
Up
Down
Back
Enter