Full Height Turnstile MPT-132
Configuring the pedestrian barrier
48
DIP S1.x
Function
Description
4 Security
Level
The setting defines how the lock is to respond if there are
several attempts to pass the barrier in the wrong direction.
The "Security low" setting enables a complete passage in the
locked direction in several steps. If the wrong direction is de-
tected, the center column is first blocked and then cleared
again immediately. If the center column continues to be
pushed at this moment in time, it can move forward again un-
til being blocked again for a brief moment, and so on. This
enables a pedestrian to achieve a complete passage with re-
peated pushes.
If, when the center column is cleared, the control detects that
it is no longer being pushed, the drive re-approaches its origi-
nal final position.
In the case of "High security", it is not possible to repeatedly
push the barrier in the wrong direction. After several attempts,
the center column will not be cleared until a manual RESET
has been executed.
Options
OFF: Security low
ON: Security high
5 and 6
Hold-open time
The hold-open time is the maximum time for which the pas-
sage remains clear after a clearance signal if nobody starts to
pass through. After the hold-open time has expired, the pas-
sage is blocked again.
The hold-open time has four possible settings.
DIP S1.5
DIP S1.6
Hold-open time
OFF OFF 10
s
OFF ON 20
s
ON OFF 30
s
ON ON infinite
7
Version status of the
software
If this function is activated during operation, the software ver-
sion is shown on the
7 segment display in cycles.
Options
OFF: Normal operating display
ON: Version is displayed
8 Factory
settings
This DIP switch can be used to restore the factory settings for
all parameters. This requires the controller to be switched off.
DIP switch 8 is then set to ON and the controller is reactivat-
ed. If the controller notices that the DIP switch is set to ON at
activation, all parameters will be reset to the value at delivery.
If the 7-segment display shows the normal operating state,
the DIP switch can be set back to OFF.
Options
OFF: Normal operation
ON: Reset the parameters (possible only after the control
has been switched on)