Assembly and installation
51
8.3.1 Foundation
and
empty
conduits for the barrier
Assembly site
The assembly site must meet the following requirements:
The barrier must not be put up where there is a danger of
flooding.
Keep a safety distance of at least 500 mm between the tip of
the barrier boom and other objects, such as walls, masonry or
houses.
→
See page 50, Fig. 13.
Foundation and reinforcement
The foundation must meet the following requirements:
→
See page 50, Fig. 13 and page 52, Fig. 15.
have sufficient load-carrying capacity.
(concrete foundations: C35/45 XD3 XF2)
Water cement value: 0.5
Foundation depth: at least 800 mm, frost-protected
foundation depth to be adjusted to the local situation.
Foundation section: 450 mm x 600 mm
Reinforcing grid as shown in figure Fig. 15
Empty conduits
The empty conduits must meet the following requirements:
→
See page 52, Fig. 14.
Separate empty conduits for mains cable and control line
Diameter: 29 mm each
Optional empty conduit for induction loop.
Diameter: 29 mm each
Conduits have to be planned to a sufficient length.
NOTE!
To provide a trouble-free operation use separate
conduits for control lines and mains cables.