Programmable Output Options

49 = Low battery on zone

01 to 32 = Zone number
99 = Any zone number

50 = Low battery on zone restore

01 to 32 = Zone number
99 = Any zone number

51 = Zone supervision trouble

01 to 32 = Zone number
99 = Any zone number

52 = Zone supervision restore

01 to 32 = Zone number
99 = Any zone number

53 = Wireless output supervision trouble

01 to 16 =Output number
99 = Any output number

54 = Wireless output supervision restore

01 to 16 =Output number
99 = Any output number

55 = Wireless output tamper trouble

01 to 16 =Output number
99 = Any output number

56 = Wireless output tamper trouble restore 

01 to 16 =Output number
99 = Any output number

57 = Non-medical alarm (paramedic)

01 to 32 = User number
99 = Any user number

58 = Zone forced

01 to 32 = Zone number
99 = Any zone number

59 = Zone included

01 to 32 = Zone number
99 = Any zone number

Default:

 

Bold

Section:

PGM 1

[261]

PGM 2

[262]

PGM 3

[263]

PGM 4

[264]

Option

OFF

ON

OFF

ON

  

 

OFF

ON

OFF

ON

[1]

PGM  Base Time (Off=Sec; On=Min)

‡

 

N

 

‡

 

N

 

‡

 

N

 

‡

 

N

 

[2]

PGM  State (Off=N.O., On=N.C.)

‡

 

N

 

‡

 

N

 

‡

 

N

 

‡

 

N

 

[3]

PGM Supervision

N

 

‡

 

N

 

‡

N

 

‡

N

 

‡

[4]

PGM Activation Mode (Off=Steady, On=Pulse)

‡

 

N

 

‡

 

N

 

‡

 

N

 

‡

 

N

 

[5]

PGM Pulse once every 30 seconds if armed

‡

 

N

 

‡

 

N

 

‡

 

N

 

‡

 

N

 

[6] to [8]

Future 

Use

N/A

N/A N/A 

N/A N/A 

N/A N/A 

N/A 

Default:

 

Bold

Section:

PGM 5

[265]

PGM 6

[266]

PGM 7

[267]

PGM 8

[268]

Option

OFF

ON  

          

OFF

ON

OFF

ON

OFF

ON  

         

[1]

PGM  Base Time (Off=Sec.; On=Min.)

‡

 

N

 

‡

 

N

 

‡

 

N

 

‡

 

N

 

[2]

PGM  State (Off=N.O., On= N.C.)

‡

 

N

 

‡

 

N

 

‡

 

N

 

‡

 

N

 

[3]

PGM Supervision

N

 

‡

 

N

 

‡

N

 

‡

 

N

 

‡

[4]

PGM Activation

 

Mode (Off=Steady, ON=Pulse)

‡

 

N

 

‡

 

N

 

‡

 

N

 

‡

 

N

 

[5]

PGM Pulse once every 30 seconds if armed

‡

 

N

 

‡

 

N

 

‡

 

N

 

‡

 

N

 

[6] to [8]

Future 

Use

N/A N/A 

N/A N/A 

N/A N/A 

N/A N/A 

Event Group #

Sub-group #

Содержание MG5000

Страница 1: ...32 Zone Wireless Transceiver Control Panel MG5000 V1 0 Programming Guide...

Страница 2: ......

Страница 3: ...utton Assignment 22 Remote Control RC Serial Number 23 System Programming 23 System Timers 25 Daylight Savings Programming 26 Partition Programming 26 Partition Timers 27 Communication Programming 28...

Страница 4: ...Programming TBL Delays Passwords MEM Communicator BYP PGM Step 4 Select the desired setting by pressing the corresponding key 1 to 4 5 7 8 9 Step 5 3 digits 000 to 255 HH MM Code Tel ENTER Step 6 YYY...

Страница 5: ...to select the partition from which the PGM type will occur Press ENTER Monitoring Backup Per 1 Per 2 Per 3 Per 4 Per 5 Pager Cancel Com Step 5 Step 6 Step 7 Step 8 Notes To cancel all communications i...

Страница 6: ...de default 1234 Step 3 Select a menu User TBL Delay MEM Communicator BYP System Options Step 4 Select the desired setting by pressing the corresponding key 1 to 4 5 Step 5 3 digits 000 to 255 HH MM St...

Страница 7: ...ding key Auto Arm Lost Remote s Step 5 HH MM 24Hr clock Press on all available remotes Press ENTER Step 6 1 Regular 2 Sleep 3 Stay Press and hold SLEEP to erase all lost remotes Notes To call answer W...

Страница 8: ...mode which allows you to program all the features options and commands except for the MG5000 s communication settings sections 395 397 399 815 816 817 910 and 911 as well as any user codes The Mainte...

Страница 9: ..._____ _____________ 1 2 3 4 5 6 7 8 021 Zone 21 _______________ _____ _____ _____________ 1 2 3 4 5 6 7 8 022 Zone 22 _______________ _____ _____ _____________ 1 2 3 4 5 6 7 8 023 Zone 23 ___________...

Страница 10: ...nstant Stay Not Armed Instant Instant Not Armed Sleep Delay Instant 10 Instant Stay Sleep Not Armed Not Armed Instant Not Armed Not Armed Instant 11 Instant Fire As is As is As is As is As is As is 12...

Страница 11: ...5 Zone 25 ____ ____ ____ ____ ____ ____ 070 Zone 10 ____ ____ ____ ____ ____ ____ 086 Zone 26 ____ ____ ____ ____ ____ ____ 071 Zone 11 ____ ____ ____ ____ ____ ____ 087 Zone 27 ____ ____ ____ ____ __...

Страница 12: ...__ _____ _____ _____ _____ 155 Zone 15 _____ _____ _____ _____ _____ _____ _____ _____ 156 Zone 16 _____ _____ _____ _____ _____ _____ _____ _____ 157 Zone 17 _____ _____ _____ _____ _____ _____ _____...

Страница 13: ...vent ____ ____ ____ ____ ____ ____ 00 00 00 232 PGM 7 Activation Event ____ ____ ____ ____ ____ ____ 00 00 00 233 Deactivation Event ____ ____ ____ ____ ____ ____ 00 00 00 234 PGM 8 Activation Event _...

Страница 14: ...keys 1 and 2 09 Utility Key 2 pressed keys 4 and 5 10 Utility Key 3 pressed keys 7 and 8 11 Utility Key 4 pressed keys 2 and 3 12 Utility Key 5 pressed keys 5 and 6 13 Utility Key 6 pressed keys 8 an...

Страница 15: ...27 Bus module event 00 A bus module was added 01 A bus module was removed 29 Arming with user 01 to 32 User number 99 Any user number 30 Special arming 00 Auto arming on time no movement 01 Late to c...

Страница 16: ...Fail to communicate to voice report Partition 1 only 12 RF interference Partition 1 only 99 Any new trouble event 45 Trouble restored 00 Telephone line restored Partition 1 only 01 AC failure restore...

Страница 17: ...c 01 to 32 User number 99 Any user number 58 Zone forced 01 to 32 Zone number 99 Any zone number 59 Zone included 01 to 32 Zone number 99 Any zone number Default Bold Section PGM 1 261 PGM 2 262 PGM 3...

Страница 18: ...___ ___ ___ 000 to 255 x 1 sec mins PGM 2 Delay Default 005 283 PGM 3 ___ ___ ___ 000 to 255 x 1 sec mins PGM 3 Delay Default 005 284 PGM 4 ___ ___ ___ 000 to 255 x 1 sec mins PGM 4 Delay Default 005...

Страница 19: ...307 PGM 7 ____ ____ ____ ____ ____ ____ 315 PGM 15 ____ ____ ____ ____ ____ ____ 308 PGM 8 ____ ____ ____ ____ ____ ____ 316 PGM 16 ____ ____ ____ ____ ____ ____ Section Section 321 PGM 1 Wireless PGM...

Страница 20: ...t access 395 Installer code lock 816 Monitoring station telephone number 2 397 Installer code 817 Backup Monitoring station telephone 398 Maintenance code 910 Panel ID 815 Monitoring station telephone...

Страница 21: ..._ 492 User 22 ____ ____ ____ ____ 477 User 7 ____ ____ ____ ____ 493 User 23 ____ ____ ____ ____ 478 User 8 ____ ____ ____ ____ 494 User 24 ____ ____ ____ ____ 479 User 9 ____ ____ ____ ____ 495 User...

Страница 22: ...__ ______ 619 9 ______ ______ ______ ______ 636 26 ______ ______ ______ ______ 620 10 ______ ______ ______ ______ 637 27 ______ ______ ______ ______ 621 11 ______ ______ ______ ______ 638 28 ______ __...

Страница 23: ...6 for User 26 ____ ____ ____ ____ ____ ____ 661 RC 11 for User 11 ____ ____ ____ ____ ____ ____ 677 RC 27 for User 27 ____ ____ ____ ____ ____ ____ 662 RC 12 for User 12 ____ ____ ____ ____ ____ ____...

Страница 24: ...ming on battery failure N Disabled N Enabled 6 Restrict arming on tamper failure Zone Bus Module Wireless PGM N Disabled N Enabled 7 Restrict arming on wireless supervision trouble Zone Bus Module Wir...

Страница 25: ...Recycle alarm counter default 000 716 ____ ____ ____ 000 to 255 minutes Keypad lockout delay default 000 717 ____ ____ ____ 000 to 255 attempt before locking Keypad lockout counter default 000 718 ___...

Страница 26: ...15 Palestine 16 Egypt 17 Namibia 18 New 2007 USA Canada Section 741 Partition 1 Options OFF ON 1 Auto arm on time N Disabled N Enabled 2 Auto arm on no movement N Disabled N Enabled 3 4 Auto arm armi...

Страница 27: ...artition 1 bell cut off default 004 748 ____ ____ ____ 000 to 255 minutes Partition 2 bell cut off default 004 749 ____ ____ ____ 000 to 255 x 15 minutes Partition 1 no movement default 000 750 ____ _...

Страница 28: ...all tel 1 for alarm restore reporting codes N Disabled N Enabled 6 Call tel 2 for alarm restore reporting codes N Disabled N Enabled 7 Call pager for alarm restore reporting codes N Disabled N Enabled...

Страница 29: ...Sescoa 3 Ademco Express 4 Ademco Contact ID 5 SIA 811 ____ ____ ____ ____ Partition 1 Account number 812 ____ ____ ____ ____ Partition 2 Account number 815 ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___...

Страница 30: ...lt 003 838 ____ ____ ____ 000 to 255 seconds Recent closing delay default 000 839 ____ ____ ____ 000 to 255 minutes Power failure report delay default 015 840 ____ ____ ____ 000 to 255 days Auto test...

Страница 31: ...lost ____ ____ Module tamper Section Data Description Section Data Description 870 ____ ____ TLM 873 ____ ____ Module AC fail ____ ____ AC failure ____ ____ Module low no battery ____ ____ Battery fa...

Страница 32: ...ing machine override delay default 030 910 ____ ____ ____ ____ Panel identifier 911 ____ ____ ____ ____ PC password 915 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __...

Страница 33: ...co 2 fault 5F 125 Duress Egress granted 12 System Troubles 300 and 310 353 Long range radio 60 Burglar Alarms 130 300 System trouble 39 354 Fail to communicate 61 130 Burglary 13 301 AC loss 3A 355 Lo...

Страница 34: ...e 83 521 Bell 1 disabled AA 626 Time Date inaccurate D1 412 Success download access 84 522 Bell 2 disabled AB 627 Program mode entry D2 413 Unsuccessful access 85 523 Alarm relay disabled AC 628 Progr...

Страница 35: ...ne alarm restore 3 13A Burglary alarm restore BH Burglary alarm restore Fire alarm restore 3 11A Fire alarm restore FH Fire alarm restore Panic 1 emergency 1 12A Panic alarm PA Panic alarm Panic 2 med...

Страница 36: ...ivity PGM RF supervision lost 1 381 Loss of supervision RF US Untyped Zone Supervisory PGM RF supervision restore 3 381 Loss of supervision RF restore UR Untyped Zone Restoral PGM RF tamper 1 145 Expa...

Страница 37: ...Magellan 37 Hardware Connections Advanced Technology Zone ATZ Connections N C Contacts without EOL Resistor N C Contacts without EOL Resistor with Tamper Recognition...

Страница 38: ...iring Program the PGM with the Key was pressed Activation Event so that the smoke detectors can be reset by pressing the CLEAR ENTER keys for three seconds See Event Group 6 on page 14 All 4 wire smok...

Страница 39: ...Installing the Control Panel in the Metal Box 8x10 Metal Box Installation Standard Metal Box MG5000 Compatible Metal Box PCB Position 11x11 Metal Box Installation Standard Metal Box MG5000 Compatible...

Страница 40: ...typ 600mA max 700mA UL installations typ 200mA Acceptable Battery Charge Currents section 127 option 5 350mA 350mA 700mA Partial view of MG5000 control panel UL Warning A 12Vdc 7Ah battery is required...

Страница 41: ...per wire Cold water pipe grounding The BELL output will shutdown if the current exceeds 3A Communication Bus Warning Disconnect telephone line before servicing Four pin connector can be used for quick...

Страница 42: ...ler Quick keys press ENTER INSTALLER CODE MEM Test Report Send the Test Report report code programmed in section 840 page 30 to the monitoring station ENTER INSTALLER CODE STAY Cancel Communication Ca...

Страница 43: ...rendering technical advice or services in connection with the purchase of goods hereunder SELLER STRONGLY RECOMMENDS THAT THE ENTIRE SYSTEM BE COMPLETELY TESTED MONTHLY Warning Despite frequent testin...

Страница 44: ...el 3 Auxiliary overload on control panel 3 Bell trouble 1 Bell disconnect on control panel 2 Bell overload on control panel 4 Communication trouble 1 Telephone Line Monitoring on control panel 2 Fail...

Отзывы: