MG5000 PCB Layout
Refer to
Single Zone
Inputs
on page 37
Refer to
AC Power
& Backup Battery
Connections on
page 40.
For the keypad’s zone
configurations, refer to page 42.
If EOL is enabled: see section
[706]
option
[2]
.
AUX Power
Refer to transformer requirements on page 40 for Aux.
Power Output. To connect additional wiring to auxiliary
power, use the red (+) and black (-) keypad connectors.
Auxiliary power will shut down if current exceeds 1.1A. If the
auxiliary output is overloaded and is shut down, you must
disconnect all loads from the output for at least 10 seconds
before reconnecting any load back to the auxiliary output.
MG5000 Keypads
The maximum number of keypads per installation is dependent on the auxiliary
output, which cannot exceed 700mA or 15 modules. Do not connect keypads more
than 76m (250ft) from the control panel.
To provide maximum lightning protection
we strongly recommend having separate
earth connections for the dialer and zone
ground terminals.
To metallic
enclosure
Ground
clamp
AWG#14 single
conductor solid
copper wire
Cold water
pipe
grounding
The "
BELL
" output will
shutdown if the current
exceeds 3A.
Communication Bus
Warning:
Disconnect
telephone line
before servicing.
Four pin connector
can be used for
quick installation of a
MG5000 keypad.
Warning:
Do not cut, bend or
alter the antennae
and ensure that
electrical wires do
not cross over the
antennae, as this
may affect signal
reception.
Paradox Memory
Key (PMC-3,
PMC-4)
Reset Button
Antennas
"RX" & “TX” LED:
Flashes quickly when
receiving or transmitting
RF signals from
wireless devices.
"STATUS" LED:
Flash once every second = Normal
Flashes ON 1 second and OFF 1 second =
Trouble
Always ON = Panel is using phone line
Fast flash 6 seconds after power up = Installer
lock enabled
This equipment must be installed and
maintained by qualified service personnel only.
For UL and C-UL warnings, refer to the UL and
C-UL Warnings section at the back of the
MG5000 Reference & Installation Manual.
Used for In-Field Firmware
upgrade through a 306
Direct Connect Interface
Coming soon: VDMP3
plug-in voice module
for voice reporting
Press and hold the RESET
button for five seconds. The
STATUS LED will start
flashing. Within 2 seconds
of this flashing, press the
reset switch again. The
panel will reset to default
and restart.