OPERATION AND MAINTENANCE MANUAL
SINGLE PHASE MCRII SERIES BATTERY CHARGER
Rev: 1.15
24/08/2018
Doc: MAN-1P_MCRII
Page 31 of 36
Australian Technology
–
Australian Made
64 Bushland Ridge, Bibra Lake, WA 6163 P: +61 8 9434 6621 F: + 61 8 9434 6623
7.4
CHECKING BOOST VOLTAGE
With the charger set to boost, connect a precision voltmeter across output terminals
and take a reading. If adjustment is required refer to the adjustments section.
The following tests are optional and do not constitute the normal commissioning
procedure.
7.5
CHECKING BATTERY CURRENT LIMITS
This test is to be carried out on one battery at a time.
Discharge Battery 1 for a while by switching the charger off and providing some DC
load for a period of approx. 10 min. This time may vary depending on the size of the
DC load compared to the battery capacity. When the battery has discharged
sufficiently remove the load and switch charger on. The output current from the
charger will now rise to the battery current limit level; check the current limit level. If
adjustment is required refer to the Adjustments section.
Repeat for Battery 2.
Reconnect the load.
7.6
CHECKING CHARGER CURRENT LIMIT
Disconnect the batteries. Connect a load to draw more than the rated current of the
charger at the float level. Switch charger on. The output current from the rectifier will
now rise to the current limit level. Check the current limit setting on the ammeter on
the front panel.
Reconnect the battery.