![Magellan Power MCRII Series Скачать руководство пользователя страница 26](http://html1.mh-extra.com/html/magellan-power/mcrii-series/mcrii-series_operation-and-maintenance-manual_689698026.webp)
OPERATION AND MAINTENANCE MANUAL
SINGLE PHASE MCRII SERIES BATTERY CHARGER
Rev: 1.15
22/08/2018
Doc: MAN-1P_MCRII
Page 26 of 36
Australian Technology
–
Australian Made
64 Bushland Ridge, Bibra Lake, WA 6163 P: +61 8 9434 6621 F: + 61 8 9434 6623
To calibrate each setting, it is necessary to connect a calibrated meter in circuit to
measure the required meter function. The set point should then be adjusted by the
front panel arrow keys, so the set point equals the external calibrated meter
measurement. All set points, with the exception of the Reference Voltage O/P
Calibration set point, can be adjusted up or down by the front panel arrow keys.
The Charger Control O/P set point (displayed on the LCD Display) will remain fixed,
and the charger output voltage is adjusted up or down to match the setpoint by the
front panel arrow keys.
Load Voltage Calibration
Calibrates the load voltage meter reading.
Battery 1 Voltage Calibration
Calibrates the Battery 1 volt meter reading.
Battery 2 Voltage Calibration
Calibrates the Battery 2 volt meter reading.
Charger Voltage Calibration
Calibrates the Charger voltage meter
reading.
Charger Current Calibration
Calibrates the charger output current meter.
Charger Current Offset Calibration
Calibrates the charger output current offset.
Battery 1 Current Offset Calibration
Sets the zero point on the Battery 1 current
meter.
Battery 2 Current Offset Calibration
Sets the zero point on the Battery 2 current
meter.
Battery 1 Current Calibration
Calibrates the Battery 1 current meter.
Battery 2 Current Calibration
Calibrates the Battery 2 current meter.
Bridge Voltage Calibration
Calibrates the SCR bridge output voltage
reading.
Charger Output Control Calibration
Calibrates the charger output control.
Temperature Offset Calibration
Calibrates the Battery temperature readings.
6.3.6
Sub Menu 9
Communications Set up
This sub menu is used to select and set the parameters for communication with the
charger.
Details are given in the MCRII Remote Communications Manual supplied with the
MCRII Remote Communications Package.