OPERATION AND MAINTENANCE MANUAL
SINGLE PHASE MCRII SERIES BATTERY CHARGER
Rev: 1.15
22/08/2018
Doc: MAN-1P_MCRII
Page 25 of 36
Australian Technology
–
Australian Made
64 Bushland Ridge, Bibra Lake, WA 6163 P: +61 8 9434 6621 F: + 61 8 9434 6623
6.3.4
Sub Menu 7
Charger and Battery Definition Set up
Note: This menu is password protected. Adjustment should only be made in
consultation with Magellan Powertronics.
The following set points are used to set the MCRII Controller to match the charger
hardware (Charger and battery size and type).
Please refer to the RATING PLATE on the inside of the charger door for the values
specific to this charger.
Serial Number
Serial Number of the Charger
Model Voltage
Identifies the charger nominal output voltage
Model Current
Identifies the charger maximum output current
Charger ID No
Identifies the charger for serial communications
purposes when more than one charger is
connected to the remote communication facility.
Dual Battery Enabled
Dual or Single Battery operation
Battery Type
Sets the type of battery to be charged by the
charger. (Ni-Cad sealed or vented Lead Acid).
Temperature Compensation
Factor
Sets the temperature compensation in mV/
C/Cell
No of cells
Sets the number of cells to be used in the battery
bank.
Battery 1 Size
Sets the ampere hour capacity of the Battery bank
1.
Battery 2 Size
Sets the ampere hour capacity of the Battery bank
2.
New Security Code
The new value of the security code.
6.3.5
Sub Menu 8
Calibration
Note: This menu is password protected. Adjustment should only be made in
consultation with Magellan Powertronics.
The chargers are factory calibrated and the calibration should not normally be
changed. Automatic calibration is available with the Charger Monitoring Software.
The following set points are used to calibrate the LCD metering functions and the
charger voltage control output. Follow the procedure given below to calibrate the
metering using the LCD and Keypad.