![Magellan Power MCRII Series Скачать руководство пользователя страница 22](http://html1.mh-extra.com/html/magellan-power/mcrii-series/mcrii-series_operation-and-maintenance-manual_689698022.webp)
OPERATION AND MAINTENANCE MANUAL
SINGLE PHASE MCRII SERIES BATTERY CHARGER
Rev: 1.15
22/08/2018
Doc: MAN-1P_MCRII
Page 22 of 36
Australian Technology
–
Australian Made
64 Bushland Ridge, Bibra Lake, WA 6163 P: +61 8 9434 6621 F: + 61 8 9434 6623
Sub Menu 2
Alarm and Trip Settings
The following parameters are used for setting alarm and over/under voltage trip and
delay times.
Hi Voltage Alarm
Sets activation voltage of the DC High alarm.
Hi Voltage Alarm Delay
Sets the delay time (seconds) between alarm
detection and alarm indication.
Low Voltage Alarm
Sets activation voltage of the DC Low alarm.
Low Voltage Alarm Delay
Sets the delay time (seconds) between alarm
detection and alarm indication.
Over Voltage Trip
Sets activation voltage of the Over Voltage Trip
alarm and protection relay (optional).
Over Voltage Trip Delay
Sets the delay time (seconds) between alarm
detection and alarm indication.
Under Voltage Trip
Sets activation voltage of the Under-Voltage Trip
alarm and protection relay (optional).
Under Voltage Trip Delay
Sets the delay time (seconds) between alarm
detection and alarm indication.
Charger Fail Delay
Sets the delay time (seconds) between alarm
detection and alarm indication of the Charger Fail
Alarm.
Battery Topping Temperature
Sets the battery temperature at which point the
charging current is reduced by 50% to prevent
overheating. This should be set to 250 if not
used.
Battery Over Temperature
Sets the battery temperature at which point the
charging is terminated. This should be set to 250
if not used.
Maximum Impedance Change
Percentage Change in the battery impedance
value beyond which the battery is considered to
be faulty.