Fuel placement
:
•
dry fuel must be used for proper combustion in the boiler.
•
it is forbidden to store fuel behind the boiler, store it next to the boiler at a distance of less than
400 mm.
•
the manufacturer recommends keeping the distance between the boiler and the fuel min. 1,000
mm or place the fuel in a room other than the installed boiler.
•
When connecting the boiler to the heating system, the drain valve must be located at the lowest
point and as close as possible to the boiler.
4.4 FUME OUTLET FROM THE BOILER
The flue must have an outlet to the chimney flue. If it is not possible to connect the boiler to the
chimney flue directly, the relevant flue extension must be as short as possible, not longer than 1 m,
without an additional heating surface and must rise towards the chimney. The flue should be suitably
insulated so that a sufficient flue gas temperature is reached in the chimney, so that condensation of
the chimney does not occur. The flues must be mechanically strong (we recommend installing the flue
on the boiler and screwing it tight) and tight against the penetration of flue gases and cleanable inside.
The inner cross-section of the flue must not taper towards the chimney. The use of knees is not
appropriate. The flue must be connected to the T-shaped chimney so that the condensate from the
chimney does not flow into the boiler but into the container provided.
4.5 BOILER CONNECTION TO CHIMNEY
The connection of the appliance to the chimney flue must always be made with the consent of
the relevant chimney sweep. The chimney flue must always develop sufficient draft and reliably
discharge the flue gases into the open air for all practically possible operating conditions. For the
correct function of the boiler, it is necessary that the separate chimney flue is correctly
dimensioned, because its draft depends on the combustion, output and service life of the boiler.
The draft of the chimney directly depends on its cross-section, height and roughness of the inner
wall. No other appliance may be connected to the chimney to which the boiler is connected. The
diameter of the chimney must not be smaller than the boiler outlet. The chimney draft must
reach the prescribed value. However, it must not be extremely high so as not to reduce the
efficiency of the boiler and not disturb its combustion (it does not break the flame). If the draft
is too high, install a throttle valve or chimney draft regulator in the chimney flue between the
boiler and the chimney.
Minimum height of chimney:
8m
!
For the correct function of the boiler is min. Chimney height 8m
Prescribed cross-section and chimney height values:
20 × 20 cm min. height 7 m
∅
20 cm min. height 8 m
15 × 15 cm min. height 11 m
∅
16 cm min. height 12 m