5. Starting the Dimmer

Please check all relevant safety instructions (see also Chapter 9), the EN-standards and requirements
before starting the dimmer!
Additionally the local electric power company should be informed before starting dimmers with phase
angle control of such power.

The MA Digital Dimmer can be built in a 19" rack mount housing (case). For additional stability
horizontal bars should be used.

Phasedistribution: L1 = Channel 1 - 4, L2 = Channel 5 - 8, L3 = Channel 9 - 12.
The minimum load is 20Watt.

5.1 Mains Supply and earthing

The dimmer should be connected to the three phase mains power with neutral (3x230 Volt Y) via an 5
pin 63A- or 32A-CEE connector. Earth must be connected.
The CEE connector is not included. The 3 phase power must be equipped with a 30mA-"Fail current
protecting switch".
The dimmer can also be used in 1- and 2- phase mode at a 230 Volt mains supply. In this case the max.
Load is only 40% of the normal maximum load (cable of the neutral is too thin!).
If "Socapex" connectors or "Hot-Patch-St17" connectors are used an additional Earth must be applied
between dimmer and load cables or load distribution. Reason: The Socapex connector has no earth
contact which is conducting at first!

After connecting and switching on no ERROR messages should show in the display; the three
voltmeters should display 200-240 Volt. When one phase is lost, the green LED in the middle button
will blink.

5.2 Fan Control

Please check good air-supply for the dimmer. The fan which takes the air in and transports it to the front
where it is blown out is at the backside.
The fan is temperature-controlled. The first stage starts at 40 °C, the second at 50 °C.
At 80 °C the message "OVERTEMP" shows and the red LED´s in the buttons will blink. Please check
whether the fan is running correctly or whether the dimmer is overloaded!
When the temperature increases further, the dimmer is switched off and a beep will be started.

5.3 Overvoltage

The MA Digital Dimmer is equipped with a mains power observation.
This checks an overvoltage, which is regularly caused by exchanging phase and neutral or having lost
neutral.
In this cases the power protection reacts immediately:
- All channels are switched off,
- the red LED´s blink,
- a loud "Beep" starts.
If the phase and neutral are exchanged for a longer time (>15min.), the dimmer can be damaged.

Содержание Digital Dimmer

Страница 1: ...Digital Dimmer User s Manual Version 1 40...

Страница 2: ...rves to linear default 10 4 4 6 USER MODE cut down the operation 10 4 4 7 DELETE ALL 10 4 4 8 a 4 4 9 CURVE USER user definable control curves 11 4 4 10 PHASE CORR activate phaseangle correction 11 4...

Страница 3: ...ervoltage and overtemperature warning with switch off indication of incoming signals phase voltage memories etc by the LCD display several dimmers can be linked MIDI interface to call internal chase a...

Страница 4: ...analogue input it is not necessary to make any adjustments If the dimmer is delivered ex work and used with DMX input please press the Menu button middle under the display once Now the channel menu ap...

Страница 5: ...940 User s Manual Digital Dimmer 5 5 5 5 5 3 Overview of Functions This Menu Tree shows all possible menus Menu Menu Menu Menu Menu Memory Menu s 4 3 Setup Menu s 4 4 Curve Menu s 4 4 9 Chase Menu s 4...

Страница 6: ...itch to the 2nd menu channel menu Exception Dimmer is in locked mode Loadcheck is not activated small rectangle Message DMX signal is received Encoder selects one of 12 channels without pressing any b...

Страница 7: ...selects channel 1 12 without pressing any button Pressing the left button and simultaneously turning the Encoder selects DMX Curve Limit etc 1 100 No DMX CUR LIM PRE LC 1 1 100 2 2 100 E 3 3 100 4 4 C...

Страница 8: ...conds Fade crossfade time 0 100 Steps number of steps 0 12 e g Steps 3 means that the case consist out of the first three memories The way to control this menu is the same as in the Channel menu 2nd m...

Страница 9: ...waiting for 1 second see 4 3 M1 1s calls internal memory no 1 after waiting for 1 second M2 1s calls internal memory no 1 after waiting for 1 second M3 1s etc etc CHA 9s starts the internal chase afte...

Страница 10: ...R MODE cut down the operation of the dimmer With this function the dimmer function can be cut down in 3 steps SUPER Supervisor means that all functions can be used NORM Normal User means that in the C...

Страница 11: ...t is at 50 but in this case reacts linear Example 5 Lamp is controlled inversely If the input is 0 the Lamp is activated to 100 if input is 100 the lamp is off 0 4 4 10 PHASE CORR activate phase angle...

Страница 12: ...ot Patch St17 connectors are used an additional Earth must be applied between dimmer and load cables or load distribution Reason The Socapex connector has no earth contact which is conducting at first...

Страница 13: ...Volt The analogue control input will be automatically switched off when DMX is fed in The input impedance is 50 kOhm The pinout of the 15 pin Sub D connector is pin 1 12 channel 1 12 Ground is pin 15...

Страница 14: ...s follows A light control desk or a special controller sends out a special code on the DMX line and switches its own DMX transceiver off Then the controller switches to receive data by listening into...

Страница 15: ...eutrals are connected inside the unit Pinout for the Wieland connectors dimmer 6x5 7 kW top plug Pin 1 3 5 Phase 1 3 bottom plug Pin 1 3 5 Phase 4 6 Pin 2 4 6 Neutral 1 3 Pin 2 4 6 Neutral 4 6 all Neu...

Страница 16: ...ove the knob and the small screw M3 at the front panel 4 Turn the dimmer on its side to make work easier 5 Pull forward cover with front panel 3 cm to the front then tilt the cover to the top see draw...

Страница 17: ...s the socket should be replaced by an electrician 9 Don t put any objects on the wire and make sure nobody steps on it 10 In case you use an extension wire make sure the sum of the power consumption o...

Страница 18: ...ng product specifications Safety EN60065 resp EN 60950 EMC EN55103 1 resp EN55103 2 Additionalinformation All DMX512 and analogue inputs and outputs must be shielded and the shielding must be connecte...

Страница 19: ...37 35 9375 37 5000 000110 38 37 5000 39 0625 100110 40 39 0625 40 6250 010110 41 40 6250 42 1875 110110 43 42 1875 43 7500 001110 45 43 7500 45 3125 101110 46 45 3125 46 8750 011110 48 46 8750 48 4375...

Страница 20: ...Fan Control 12 FI Protection 12 G Go button 8 H HOLD 9 I Imput Impedance 13 Input Monitoring 6 Introduction 3 L Limit 7 Link 11 15 Loadcheck 6 Loadcheck switched off 7 Loadcheck activated 7 Locked 6 M...

Отзывы: