R3-NF1

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8429  Rev.6  P. 5 / 6

 WITH STATUS DATA (SW3-3: ON)

• I/O type: Input

Status data is assigned to the last 2 words.
Data of the slots 6 and 7 is unable.

• I/O type: Input/Output Mixed

Status data is assigned to the last 2 words of the input area. 
Data on the words 3 and 4 of the slot 2 is unable.

• I/O type: Output

  Status data cannot be assigned because there is no input data.
  For output only, operate without status area.

• Module Status indicates whether individual I/O modules are mounted or not. The bit corresponding to the mounted slot
   turns to “1,” and the unmounted slot to “0.”

• Error Status indicates error status for each module as described below. The bit corresponding to such module turns to “1.”
    R3-TSx, R3-RSx, R3-US4 (T/C, RTD input): Input burnout
    R3-DA16A: Power input in error or disconnected
    R3-YSx: Output current error (e.g. load unconnected)
    Every module which input is less than -15% or more than +115%
    R3-US4 (voltage input): out of -10% to +110% input.

0

15

+0

Slot  1

+2

+4

+6

+8

+10

+12

+14

Slot  2

Input

(8 points)

Output

(8 points)

Slot  3

Slot  4

Slot  5

Slot  6

Slot  7

0

15

+0

Slot 1

+2

+4

+6

+8

+10

+12

+14

Slot 2

Slot  3

Module Status

Error Status

Slot  4

Slot  5

Begin

Address

Begin

Address

Module Status

Error Status

MODULE STATUS, ERROR STATUS

Shows each module’s availability and error status.

0

15

Module 1
Module 2
Module 3
      :
Module 16

I/O DATA DESCRIPTIONS 

The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.

 

ANALOG DATA (16-bit data, models: R3-SV4, YV4, DS4, YS4 and US4, etc.)

16-bit binary data.
Basically, 0 to 100% of the selected I/O range is converted into 0 to 10000 (binary).
-15 to 0 % is a negative range represented in 2’s complement.
In case of R3-US4, -10 to 0% is a negative range represented in 2’s complement.

0

15