TEMPERATURE DATA (16-bit data, models: R3-RS4, TS4 and US4, etc.)

16-bit binary data.
With °C temperature unit, raw data is multiplied by 10.  For example, 25.5°C is converted into 255.
With °F temperature unit, the integer section of raw data is directly converted into the data.  For example, 135.4°F is con-
verted into 135.
Minus temperature is converted into negative values, represented in 2’s complements.

0

15

 

ANALOG DATA (16-bit data, models: R3-CT4A, CT4B, etc.)

16-bit binary data.
Integer obtained by multiplying unit value (A) by 100.
In case of CLSE-R5, integer obtained by multiplying unit value (A) by 1000.

0

15

 

ACCUMULATED COUNT DATA (32-bit data, models: R3-PA2, PA4A, WT1, WT4, etc.)

32-bit binary data is used for accumulated counts and encoder positions.
Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn.

0

15

+0

Lower 16 bits

0

15

+1

Higher 16 bits

 

BCD DATA (32-bit data, models: R3-BA32A, BC32A, etc.)

32-bit binary data is used for BCD.
Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn.

0

15

+0

Lower 16 bits

0

15

+1

Higher 16 bits

 

DISCRETE DATA (models: R3-DA16, DC16, etc.)

0

15

Input 1   (Output 1)
Input 2   (Output 2)
Input 3   (Output 3)
     :               :
Input 16 (Output 16)

0 : OFF
1 : ON 