9
PU-2A USERS
MANUAL EM-9255-C Rev.14
A-4. INPUT/OUTPUT PROGRAMMING FLOW CHART
The JX transmitters process data using an internal digital operation circuit.
The following chart shows a typical input data programming procedure which covers Data Indication, Data Input to
Enter Data Command has been explained on the previous page.
Type in the thermocouple type, RTD type or potenti
-
ometer value.
For DC input units, first type [ITEM] 10 which speci
-
fies the type of transmitter and then type [ITEM] 11
which is used to set the coarse range.
THESE ARE FACTORY SETTING ITEMS ONLY. They
cannot be adjusted by the operator.
Zero and fullscale value adj. (fine adj.) Type in the
actual values for 0% and 100% input.
Used for the JX Linearizer units only.
[GROUP] 01 for Models xJM, 10JRE, xJPA, xJS, xJDL
and xJFX, and [GROUP] 02 & 03 for Model JFX1.
Type in a percentage value for the ZERO and SPAN
adjustments.
THESE ARE FACTORY SETTING ITEMS ONLY. They
cannot be adjusted by the operator.
ITEM 10 - 11
INPUT RANGE ADJUSTMENT
ITEM 12 - 13
INPUT ZERO/SPAN ADJUSTMENTS
ITEM 14 - 15
SCALING
ITEM 60 - 91
LINEARIZATION DATA INPUT
ITEM 19 - 20
FINE ZERO/SPAN ADJUSTMENTS
ITEM 16 - 17
OUTPUT ZERO/SPAN ADJUSTMENTS
Refer to Section A-5 for the specific DATA NO.
for each input type.
See Section A-5. GROUP 01 TABLE.
See Section A-5. LINEARIZATION DATA
TABLE.