![M-system PU-2A Скачать руководство пользователя страница 22](http://html1.mh-extra.com/html/m-system/pu-2a/pu-2a_operation-manual_3116625022.webp)
22
PU-2A USERS
MANUAL EM-9255-C Rev.14
■
3-input MATH FUNCTION model xJFK (Group 01)
ITEM
MDFY.
DATA INPUT
DISPLAY
CONTENTS
01
S
MAINTENANCE SWITCH (lock command)
0
MTSW: MON.MODE
MONITOR mode: data monitoring only
1
MTSW: PRG.MODE
PROGRAM mode: “P” marked data modifiable
02
P
Alphabets & No.
TG: XXXXXXXXXX
Tag name entry (10 characters max.)
03
04
05
06
07
P
D
D
D
D
Number (%)
No input
No input
No input
No input
OUTPER XXX.XX
INPER1 XXX.XX X
INPER2 XXX.XX
INPER3 XXX.XX
(X0) XXX.XXXX
Output status monitor (%) & simulation output
X
1
: Input 1 status monitor (%)*
1
X
2
: Input 2 status monitor (%)*
1
X
3
: Input 3 status monitor (%)*
1
X
0
: Normalization parameter monitor (1.0000=100%)
10
P
TYPE OF EQUATION
1
X1 * SQR (X2 / X3)
Temp. & press. compensation for DP flowmeter
X
0
= K
1
X
1
K
2
X
2
+ A
2
√
K
3
X
3
+ A
3
where X
1
= flow
X
2
= pressure
X
3
= temperature
Specify ITEM 11 square root extraction for a square input X
1
.
2
X1 + X2 + X3
Addition & Subtraction
X
0
= K
0
{K
1
(X
1
+ A
1
) + K
2
(X
2
+ A
2
) + K
3
(X
3
+ A
3
)} + A
0
3
X1 * X2 * X3
Multiplication
X
0
= K
0
(K
1
X
1
+ A
1
)(K
2
X
2
+ A
2
)(K
3
X
3
+ A
3
) + A
0
4
(X1 * X2) / X3
Multiplication & Division
X
0
=
K
0
(K
1
X
1
+ A
1
)(K
2
X
2
+ A
2
)
+
A
0
K
3
X
3
+ A
3
5
X1 / (X2 * X3)
Multiplication & Division
X
0
=
K
0
(K
1
X
1
+ A
1
)
+
A
0
(K
2
X
2
+ A
2
)(K
3
X
3
+ A
3
)
6
(X1 + X2) * X3
Addition & Multiplication
X
0
= K
0
(K
1
X
1
+ K
2
X
2
+ A
1
)(K
3
X
3
+ A
3
) + A
0
7
(X1 + X2) / X3
Addition & Division
X
0
=
K
0
(K
1
X
1
+ K
2
X
2
+ A
1
)
+
A
0
(K
3
X
3
+ A
3
)
8
X1 / (X2 + X3)
Division & Addition
X
0
=
K
0
(K
1
X
1
+ A
1
)
+
A
0
(K
2
X
2
+ K
3
X
3
+ A
2
)
9
X1 + (X2 * X3)
Addition & Multiplication
X
0
= K
0
(K
1
X
1
+ A
1
) + K
0
(K
2
X
2
+ A
2
)(K
3
X
3
+ A
3
) + A
0
10
X1 + (X2 / X3)
Addition & Division
X
0
= K
0
(K
1
X
1
+ A
1
) +
K
0
(K
2
X
2
+ A
2
)
+
A
0
(K
3
X
3
+ A
3
)
11
P
SQUARE ROOT EXTRACTION FOR INPUT X
1
0
SQR NO OPTION
Without
1
SQR OPTION
With
19
P
Percentage
FINZER
Fine zero adjustment
Initial status shows actual bias (%). When data is entered, output
(%) is shown.
20
P
Percentage
FINSPN
Fine span adjustment
Initial status shows actual gain (%). When data is entered, output
(%) is shown
.