20
PU-2A USERS
MANUAL EM-9255-C Rev.14
■
2-input MATH FUNCTION model xJF(Group 01)
ITEM
MDFY.
DATA INPUT
DISPLAY
CONTENTS
01
S
MAINTENANCE SWITCH (lock command)
0
MTSW: MON.MODE
MONITOR mode: data monitoring only
1
MTSW: PRG.MODE
PROGRAM mode: “P” marked data modifiable
02
P
Alphabets & No.
TG: XXXXXXXXXX
Tag name entry (10 characters max.)
03
04
05
P
D
D
Number (%)
No input
No input
OUTPER XXX.XX
INPER1 XXX.XX
INPER2 XXX.XX
Output status monitor (%) & simulation output
X
1
: Input 1 status monitor (%)*
1
X
2
: Input 2 status monitor (%)*
1
06
07
08
D
D
D
No input
No input
No input
(X0) XXX.XXXX
(X1) X.XXXX
(X2) X.XXXX
X
0
: Normalization parameter monitor (1.0000=100%)
X
1
: Normalization parameter monitor (1.0000=100%)
X
2
: Normalization parameter monitor (1.0000=100%)
10
P
TYPE OF EQUATION
1
01: X1 / SQR (X2)
Temp. compensation for DP flowmeter
X
0
=
K
1
X
1
√
K
2
X
2
+ A
2
X
1
= flow, X
2
= temp.
2
02: X1 * SQR (X2)
Press. compensation for DP flowmeter
X
0
= K
1
X
1
√
K
2
X
2
+ A
2
X
1
= flow, X
2
= press.
3
03: X1 + X2
Addition & Subtraction
X
0
= K
0
{K
1
(X
1
+ A
1
) + K
2
(X
2
+ A
2
)} + A
0
4
04: X1 * X2
Multiplication
X
0
= K
0
(K
1
X
1
+ A
1
)(K
2
X
2
+ A
2
) + A
0
5
05: X1 / X2
Division
X
0
=
K
0
(K
1
X
1
+ A
1
)
+
A
0
K
2
X
2
+ A
2
11
P
SQUARE ROOT EXTRACTION FOR INPUT X
1
0
SQR NO OPTION
Without
1
SQR OPTION
With
19
P
Percentage
FINZER
Fine zero adjustment
Initial status shows actual bias (%). When data is entered, output
(%) is shown.
20
P
Percentage
FINSPN
Fine span adjustment
Initial status shows actual gain (%). When data is entered, output
(%) is shown.
21
22
23
P
P
P
Number
Number
Number
(K0) XX.XXX
(K1) XX.XXX
(K2) XX.XXX
Gain K
0
(1.000 = 100%)
Gain K
1
(1.000 = 100%)
Gain K
2
(1.000 = 100%)
24
25
26
P
P
P
Number (%)
Number (%)
Number (%)
(A0) XXX.XX
(A1) XXX.XX
(A2) XXX.XX
Bias A
0
(%)
Bias A
1
(%)
Bias A
2
(%)
27
28
P
P
Number (%)
Number (%)
X1LMTL XXX.XX
X2LMTL XXX.XX
Input LOW limit X
1
(-25.00 – +125.00%)
Input LOW limit X
2
(-25.00 – +125.00%)
29
30
P
P
Number (%)
Number (%)
X1LMTH XXX.XX
X2LMTH XXX.XX
Input HIGH limit X
1
(-25.00 – +125.00%)
Input HIGH limit X
2
(-25.00 – +125.00%)
REMARK 1
: Percentage of the input range without zero suppression (0 – 5 V, 0 – 20 mA).