PU-2A USERS 

MANUAL EM-9255-C Rev.14

GROUP 01 : USER FUNCTION TABLE

ITEM

MDFY. DATA INPUT

DISPLAY

CONTENTS

00

D

No input

– JPAD –

Indicating Model No.

01

S

maintenance sw

Maintenance Switch (lock command)

DATA, ENTR

Current operation mode

DATA, 0, ENTR

MON (run) mode

MONITOR mode: data monitoring only

DATA, 1, ENTR

PGM (stop) mode

PROGRAM mode: “P” marked data modifiable

WARNING!! 

 THE PROGRAM IS WRITTEN IN THE EEPROM WHEN THE TRANSMITTER IS RETURNED TO THE 

MONITOR MODE.  THE MODIFICATION WILL NOT BE TRANSFERRED IF YOU TURN POWER SUP-

PLY TO THE TRANSMITTER OFF WITHOUT DOING THAT.

02

P

user’s TAG entry

User’s Tag Name entry and monitor

DATA, ENTR

Registered Tag Name

DATA, –, ENTR
Alphabets & No.

TAG not entered!
XXXXXXXXXX

Tag Name deleted

Entering Tag Name (10 characters max.)

03

P

output monitor

Output, in % of zero/span frequency

JPAD

JPQD

JRPD

JRQD

DATA, ENTR

XXX.XX %

DATA, data, ENTR

Entering simulation output in % (-15.00 – +115.00%)
data: -15.00 – 115.00

DATA, UP

DATA, DOWN

Display data increases.
Display data decreases.

05

D

measured input %

Input frequency, in % of zero/span freq.

JPAD

JRPD

JPRD

JFRD

JPSM

(out1)

DATA, ENTR

XXX.XX %

06

D

measured freq

Input frequency, in Hz

JPAD

JRPD

JPRD

JFRD

JPSM

(out1)

DATA, ENTR

XXX.XXX Hz

07

D

input counts

Input counter value

JPQD

JRQD

JPRD

JPSM

DATA, ENTR

Current counter value

08

P

output zero freq

Lower range output frequency (= output 0%)

JARP

JAPD

JPRD

JPSM

JFRD

Enter data 0 for 
JPSM, JPRD.

DATA, ENTR

Current set value

DATA, data, ENTR XXX.X xHz

Entering frequency
data: 0 – 9999 (4 digits max.) with decimal point
xHz: Frequency unit specified in ITEM 11

09

P

output span freq

Upper range output frequency (= output 100%)

JARP

JAPD

JPRD

JPSM

JFRD

Enter numerator 
of the pulse rate 
for JPSM, JPRD.

DATA, ENTR

Current set value

DATA, data, ENTR XXX.X xHz

Entering frequency
data: 0 – 9999 (4 digits max.) with decimal point
xHz: Frequency unit specified in ITEM 11

11

P

unit frequency

Frequency unit used in programming

JPAD

JRPD

JARP

JAPD

JPRD

JPSM

JFRD

DATA, ENTR

Registered frequency unit

DATA, 0, ENTR
DATA, 1, ENTR
DATA, 2, ENTR

Hz
kHz (1000 Hz)
mHz (0.001 Hz)

Hz
kHz
mHz

DATA, UP

DATA, DOWN

Display data No. increases.
Display data No. decreases.

Содержание PU-2A

Страница 1: ...TERS Model PU 2A OPERATION MANUAL 8 S I 5 P Z F 2 M W C 7 R H 4 O Y E 1 L V B 0 K U A 9 T J 6 Q G 3 GROUP ITEM DATA CLR UP DOWN ENTER http www m system co jp 5 2 55 Minamitsumori Nishinari ku Osaka 55...

Страница 2: ...HJDL GJDL 10JDL 18 K JDL 11JDL LINEARIZER JFX 7JFX FJFX HJFX GJFX 10JFX 18JFX 11JFX WJFX VJFX 100 point LINEARIZER JFX1 2 input MATH JF 7JF FJF HJF GJF 10JF 18JF 11JF WJF VJF 3 input MATH JFK 7JFK 11...

Страница 3: ...PROPER SECTION OF THIS MANUAL BEFORE PROGRAMMING The Model PU 2A is used for those M System products other than listed on the cover page of this manual Instructions for them are issued separately for...

Страница 4: ...A STRAP HERE CONNECTION CABLE IS PROVIDED DATA TO BE ENTERED OR MESSAGE GROUP NO SHIFT KEY POSITION ITEM NO RESPONSE ERROR INDICATION D G I DISPLAY RESPONSE MESSAGE OK O K NG NO GOOD NU NOT USED ER E...

Страница 5: ...YPE 10 DC INPUT ISOLATOR model xJV 10 THERMOCOUPLE INPUT model xJT 11 3 wire RTD INPUT model xJR 12 POTENTIOMETER INPUT model xJM 12 4 wire RTD INPUT model 10JRE 12 FREQUENCY INPUT model xJPA 13 SELF...

Страница 6: ...is supplied to the transmitter 2 Connect the PU 2A to the transmitter via the front modular jack 3 Switch the transmitter into PROGRAM mode with PU 2A 4 Specify an item to be changed Press GROUP NN IT...

Страница 7: ...rther adjustments with other ITEM s EXAMPLE 50 output simulated for 1 5 V output range 1 5 V range is converted into percentage against 0 5 V range with ITEM 3 20 100 1 Be sure that the power is suppl...

Страница 8: ...change the ITEM NO press ITEM and then the number or press the UP or DOWN key one or more times Press DATA and then the number required When a wrong num ber is typed start again with the DATA key and...

Страница 9: ...SETTING ITEMS ONLY They cannot be adjusted by the operator Zero and fullscale value adj fine adj Type in the actual values for 0 and 100 input Used for the JX Linearizer units only GROUP 01 for Models...

Страница 10: ...V 3 0 5 10V P 14 mV 6 1 5V D 15 mV A 4 20mA D 16 mV H 10 50mA 11 P COARSE INPUT RANGE SELECTION mV 1 mV 2 mV 3 mV 6 A H mV V V 0 INPRNG XXXX 5 0 05 0 5 1 INPRNG XXXX 10 0 10 1 0 No 2 INPRNG XXXX 20 0...

Страница 11: ...5 Tc 5 T CC T CC 6 Tc 6 B RH B RH 7 Tc 7 R R 8 Tc 8 S S 9 Tc 9 WRe 5 26 WRe 5 26 0 Tc 0 N N 14 15 P P Actual value Actual value SCLLOW XXXXXX SCLHIG XXXXXX Input range scaling 0 value Input range scal...

Страница 12: ...TMPSCL K Program ITEM 21 first before ITEM 14 15 when F or K calibra tion is needed This procedure is necessary whenever RTD type is changed REMARK 1 Temperature is indicated in the unit selected in...

Страница 13: ...10kHz FRQRNG 100kHz 0 10 kHz 0 100 kHz 13 P Percentage DRPOUT XXX XX Low end cutout adjustment 0 00 100 00 14 15 P P Actual value Actual value SCLLOW XXXXXX SCLHIG XXXXXX Input range scaling 0 value...

Страница 14: ...tual bias When data is entered output is shown 20 P Percentage FINSPN Fine span adjustment Initial status shows actual gain When data is entered output is shown REMARK 1 See LINEARIZER model xJFX tabl...

Страница 15: ...P Alphabets No TG XXXXXXXXXX Tag name entry 10 characters max 03 05 P D Number No input OUTPER XXX XX INPPER XXX XX Output status monitor simulation output Input status monitor 10 P 41 42 Sq 1 Nodrop...

Страница 16: ...1 Pt 100 RTD Pt 100 JIS 97 IEC JIS 89 32 RB 2 JPt 100 JPt 100 JIS 89 33 RB 3 Pt 50 Pt 50 JIS 81 34 RB 4 Ni 508 4 Ni 508 4 41 Sq 1 Nodrop Square root output without low end cutout 42 Sq 2 Dropout Squar...

Страница 17: ...INPRNG XXXX 5 0 05 0 5 1 INPRNG XXXX 10 0 10 1 0 No 2 INPRNG XXXX 20 0 20 2 0 Adjustment 3 INPRNG XXXX 50 0 50 5 0 Needed 4 INPRNG XXXX 100 1 00 10 0 14 15 P P Actual value Actual value SCLLOW XXXXXX...

Страница 18: ...XXX XX Input 9 61 P Y 01 XXX XX Output 1 77 P Y 09 XXX XX Output 9 62 P X 02 XXX XX Input 2 78 P X 10 XXX XX Input 10 63 P Y 02 XXX XX Output 2 79 P Y 10 XXX XX Output 10 64 P X 03 XXX XX Input 3 80 P...

Страница 19: ...tual gain When data is entered output is shown HOW TO PROGRAM SEGMENT DATA FOR LINEARIZATION JFX1 Non linear input and their corresponding output values are entered as a percentage of the full range s...

Страница 20: ...sation for DP flowmeter X0 K1X1 K2X2 A2 X1 flow X2 press 3 03 X1 X2 Addition Subtraction X0 K0 K1 X1 A1 K2 X2 A2 A0 4 04 X1 X2 Multiplication X0 K0 K1X1 A1 K2X2 A2 A0 5 05 X1 X2 Division X0 K0 K1X1 A1...

Страница 21: ...rmeter 0 400 C Design standard of orifice 300 C K1 1 K2 400 0 0 698 300 273 14 A2 0 273 14 0 4766 47 66 300 273 14 PRESSURE COMPENSATION FOR DP FLOWMETER Atmospheric pressure 101 3 kPa abs Absolute Pr...

Страница 22: ...emperature Specify ITEM 11 square root extraction for a square input X1 2 X1 X2 X3 Addition Subtraction X0 K0 K1 X1 A1 K2 X2 A2 K3 X3 A3 A0 3 X1 X2 X3 Multiplication X0 K0 K1X1 A1 K2X2 A2 K3X3 A3 A0 4...

Страница 23: ...X A1 XXX XX A2 XXX XX A3 XXX XX Bias A0 Bias A1 Bias A2 Bias A3 29 30 31 P P P Number Number Number X1LMTL XXX XX X2LMTL XXX XX X3LMTL XXX XX Input LOW limit X1 25 00 125 00 Input LOW limit X2 25 00 1...

Страница 24: ...ormeter 0 400 C Design standard of orifice 300 C K1 1 K3 400 0 0 698 300 273 14 A3 0 273 14 0 4766 47 66 300 273 14 PRESSURE COMPENSATION FOR DP FLOWMETER Atmospheric pressure 101 3 kPa abs Absolute P...

Страница 25: ...5 1 INPRNG XXXX 10 0 10 1 0 No 2 INPRNG XXXX 20 0 20 2 0 Adjustment 3 INPRNG XXXX 50 0 50 5 0 Needed 4 INPRNG XXXX 100 1 00 10 0 14 15 P P Actual value Actual value SCLLOW XXXXXX SCLHIG XXXXXX Input r...

Страница 26: ...o 8 adjustable DEAD TIME COMPUTING model xJFT2 Group 01 ITEM MDFY DATA INPUT DISPLAY CONTENTS 23 P FUNCTION TYPE 0 0 NO FILTER Without the function 2 2 DEAD TIME With the dead time computing 24 25 26...

Страница 27: ...ion Xo s 1 Ts Xi s Xi Input Xo Output Ls Lead time constant 0 0 to 100 0 seconds adjustable RAMP BUFFER model xJFT5 Group 01 ITEM MDFY DATA INPUT DISPLAY CONTENTS 23 P FUNCTION TYPE 0 0 NO FILTER With...

Страница 28: ...les to be calculated 2 to 8 adjustable U Number of largest samples to be cut off 0 to 7 adjustable L Number of smallest samples to be cut off 0 to 7 adjustable MOVING AVERAGE OUTPUT model JFTS1 Group...

Страница 29: ...T seconds FUNCTION The JFTS2 does not respond to an input signal for a preset dead time duration In addition when a time constant T value is set it generates a first order lag output after the dead ti...

Страница 30: ...Unit sec 0 00 200 00 sec adjustable 25 P HI LO ALARM AT CASCADE CONTROL Default 0 0 0 NO ALARM Without alarm setpoint 1 1 LOW ALARM With LOW setpoint only 2 2 HIG ALARM With HIGH setpoint only 3 3 AL...

Страница 31: ...Tag name entry 10 characters max 03 P Percentage OUTPER XXX XX Output status monitor simulation output 04 D No input INPPER 1 XXX XX Input 1 status monitor 05 D No input INPPER 2 XXX XX Input 2 statu...

Страница 32: ...TABLE OF CONTENTS B 1 INTRODUCTION 33 B 2 GENERAL OPERATION DESCRIPTION 33 DESCRIPTION 33 MAINTENANCE SWITCH OPERATION MODES 33 OUTPUT SIMULATION PROGRAMMING 33 B 3 OPERATION FLOW CHART 34 B 4 DIAGNO...

Страница 33: ...entry keys 4 Specify another item if necessary Repeat 3 5 Switch the transmitter into MONITOR mode with PU 2A The changed parameters are saved in the nonvolatile memory 6 Disconnect the PU 2A MAINTEN...

Страница 34: ...transmitter INITIAL STATE WAITING ITEM INPUT ITEM INDICATION WAITING DATA INPUT DATA INDICATION MESSAGE INDICATION D G01I 0 D G01I enter i t 0 em G0 m 1 a I i 0 n 1 tenan c e 0 sw G01 M I O 0 N 1 run...

Страница 35: ...ange value zero not entered Zero parameter is undefined This message appears when you try to monitor ITEM NO which is unnecessary for the hardware If it appears even for the ITEM NO of which the param...

Страница 36: ...EM is applicable The ITEMs without these indications are applicable to all models For Model WJPAD see description on JPAD GROUP 00 SYSTEM FUNCTION TABLE ITEM MDFY DATA INPUT DISPLAY CONTENTS 00 D No i...

Страница 37: ...ncreases Display data decreases 05 D measured input Input frequency in of zero span freq JPAD JRPD JPRD JFRD JPSM out1 DATA ENTR XXX XX 06 D measured freq Input frequency in Hz JPAD JRPD JPRD JFRD JPS...

Страница 38: ...ata ENTR XXX XX Entering desired bias 15 00 85 00 115 00 of zero frequency 100 00 data 85 00 115 00 DATA UP DATA DOWN Display data increases Display data decreases 19 P gain adj VR Output fine adjustm...

Страница 39: ...span count value For returning to 0 external reset input is needed 28 P initial count sw Specifying output mode at power ON JPQD JRQD DATA ENTR Indicating current mode DATA 0 ENTR DATA 1 ENTR DATA ENT...

Страница 40: ...P output frq limit Output frequency limit JPRD JPSM DATA ENTR Current set value DATA data ENTR Entering frequency minimum 0 1 Hz 34 P prms initializer Setting all parameters to default values DATA 1 E...

Отзывы: