ITEM
MDFY. DATA INPUT
DISPLAY
CONTENTS
12
P
input zero freq.
Lower range input frequency (= output 0%)
JPAD
JRPD
(JARP JAPD)
JPRD
JPSM
JFRD
Enter data 0 for
JPSM, JPRD.
DATA, ENTR
Current set value
DATA, data, ENTR XXX.X xHz
Entering frequency
data: 0 – ±9999 (4 digits max.) with decimal point
xHz: Frequency unit specified in ITEM 11
13
P
input span freq.
Upper range input frequency (= output 100%)
JPAD
JRPD
(JARP JAPD)
JPRD
JPSM
JFRD
Enter denominator
of the pulse rate
for JPSM, JPRD.
DATA, ENTR
Current set value
DATA, data, ENTR XXX.X xHz
Entering frequency
data: 0 – 9999 (4 digits max.) with decimal point
xHz: Frequency unit specified in ITEM 11
14
P
zero count
Lower range count (= output 0%)
JPQD
JRQD
DATA, ENTR
Current set value
DATA, data, ENTR
xXXXXXXX counts
Entering count value
data: 0 –
±
1048575
x: Negative sign (–); positive (+) is not indicated.
15
P
span count
Upper range count (= output 100%)
JPQD
JRQD
DATA, ENTR
Current set value
DATA, data, ENTR
XXXXXXX counts
Entering count value
data : 0 – 1048575
18
P
zero bias adj VR
Output fine adjustment (zero)
JPAD
JPQD
JRPD
JRQD
DATA, ENTR
Current set value in %
DATA, data, ENTR XXX.XX %
Entering desired bias, ±15.00% (85.00 – 115.00% of zero frequency
(=100.00%)
data : 85.00 – 115.00
DATA, UP
DATA, DOWN
Display data increases.
Display data decreases.
19
P
gain adj VR
Output fine adjustment (span)
JPAD
JPQD
JRPD
JRQD
DATA, ENTR
Indicating current set value in %
DATA, data, ENTR XXX.XX %
Entering desired gain, ±15.00% (85.00 – 115.00% of span frequency
(=100.00%)
data : 85.00 – 115.00
DATA, UP
DATA, DOWN
Display data increases.
Display data decreases.
20
P
drop out timer
Specifying cutout time
JPAD
JRPD
JPRD
JPSM
JFRD
DATA, ENTR
Indicating current set value
DATA, data, ENTR
XXXXX msec.
Entering desired cutout time (100 msec. – 300 sec.)
data : 100 – 300000 (msec.), 5 msec. increments
DATA, UP
DATA, DOWN
Display data increases.
Display data decreases.
21
P
sampling timer
Specifying sampling time
JPAD
JRPD
JPRD
JPSM
JFRD
JRQD
DATA, ENTR
Indicating current set value
DATA, data, ENTR
XXXXX msec.
Entering desired sampling time (50 msec. – 100 sec.)
data : 50 – 100000 (msec.), 5 msec. increments
DATA, UP
DATA, DOWN
Display data increases.
Display data decreases.
22
P
updating timer
Specifying output update time
JPAD
JPQD
JRPD
JRQD
DATA, ENTR
Indicating current set value
DATA, data, ENTR
XXXXX msec.
Entering desired output update time (50 msec. – 100 sec.)
data : 50 – 100000 (msec.), 5 msec. increments
DATA, UP
DATA, DOWN
Display data increases.