PU-2A USERS
MANUAL EM-9255-C Rev.14
A-5. GROUP 01 TABLE FOR EACH INPUT TYPE
In the tables, each MDFY. (modification) mark indicates:
D:
No modification (writing) possible. Used only for monitoring (reading).
S:
Modifiable at any time.
P:
Modifiable only when the MAINTENANCE SWITCH is in the “PRG” mode.
■
DC INPUT (ISOLATOR) model xJV (Group 01)
ITEM
MDFY.
DATA INPUT
DISPLAY
CONTENTS
01
S
MAINTENANCE SWITCH (lock command)
0
MTSW: MON.MODE
MONITOR mode: data monitoring only
1
MTSW: PRG.MODE
PROGRAM mode: “P” marked data modifiable
02
P
Alphabets & No.
TG: XXXXXXXXXX
Tag name entry (10 characters max.)
03
05
06
P
D
D
Number (%)
No input
No input
OUTPER XXX.XX
INPPER XXX.XX
INPVAL XXX.XX
Output status monitor (%) & simulation output
Input status monitor (%) *
1
Input status monitor in actual value, same unit as selected in
ITEM 10.
10
TYPE OF TRANSMITTER INPUT *
2
D
11
mV-1: 5 – 100mV
D
12
mV-2: 0.05 – 1V
P
13
mV-3: 0.5 – 10V
P
14
mV-6: 1 – 5V
D
15
mV-A: 4 – 20mA
D
16
mV-H: 10 – 50mA
11
P
COARSE INPUT RANGE SELECTION
mV-1
mV-2
mV-3
mV-6/A/H
(± mV)
(± V)
(± V)
0
INPRNG: XXXX
5
0.05
0.5
1
INPRNG: XXXX
10
0.10
1.0
No
2
INPRNG: XXXX
20
0.20
2.0
Adjustment
3
INPRNG: XXXX
50
0.50
5.0
Needed
4
INPRNG: XXXX
100
1.00
10.0
14
15
P
P
Actual value
Actual value
SCLLOW XXXXXX
SCLHIG XXXXXX
Input range scaling 0% value
Input range scaling 100% value
Use the same engineering unit as the coarse range selected in
ITEM 11.
19
P
Percentage
FINZER
Fine zero adjustment
Initial status shows actual bias (%). When data is entered, output (%)
is shown.
20
P
Percentage
FINSPN
Fine span adjustment
Initial status shows actual gain (%). When data is entered, output
(%) is shown.
REMARK 1
: Percentage of the coarse input range selected in ITEM 11.
(Example)
SCALED RANGE
COARSE RANGE
INPUT
DISPLAY
1 – 5 V
0 – 5 V
1 V
20%
0 – 10 V
0 – 10 V
0 V
0%
-5 – +5 V
-5 – +5 V
0 V
0%
-5 – +5 V
-5 – +5 V
-5 V
-100%
REMARK 2
:
Data 13 and 14 are selectable without needing to make hardware change. In order to get 4 – 20 mA or 10 – 50 mA
input, attach a precision resistor to input terminals.