MMAJ

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8155  Rev.2  P. 2 / 4

PERFORMANCE

MMAJ-100xxx

MMAJ-200xxx

Max. Continuous Operating Voltage (Uc)

132V AC

264V AC

Operational Voltage Range *

1

85 – 132V AC

170 – 264V AC

Discharge Voltage (Vmin)

Line to line: 190V

Line to earth: 300V

Line to line: 380V

Line to earth: 450V

Voltage Protection Level (Up)

900V

1500V

Leakage Current @ Uc

Line to line: Without Alarm 6mA, With Alarm 20mA

Line to earth: 10μA

Nominal Discharge Current (In)

MMAJ-xxL: 5kA

MMAJ-xxM: 10kA

Max. Load Current *

2

MMAJ-x10: 10A 
MMAJ-x20: 20A  
MMAJ-x30: 30A

Voltage Drop

≤ 1V

Surge Energy Attenuation Ratio @8/20 µs

(Line to earth)

MMAJ-10010: -56 dB
MMAJ-10020: -56 dB
MMAJ-10030: -40 dB

MMAJ-20010: -53 dB
MMAJ-20020: -53 dB
MMAJ-20030: -40 dB

Response Time (Line to line)

3 nsec.

Insulation Resistance

≥ 100 MΩ with 500V DC (line to alarm output to housing)

Dielectric Strength

2000V AC @1 minute (line to alarm output to housing)

*1.  MMAJ is operational as an SPD despite the voltage less than the minimum.  However, the functions of the monitor LED and the 

alarm output are not guaranteed.

*2. Refer to Derating Curve

INSTALLATION

Refer to the drawings below.  The unit weighs heavily.  Mount it on a rigid wall.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

50 (1.97)

117 (4.61)

22

(0.87)

80 (3.15)

88 (3.46)

77 (3.03)

75 (2.95)

11 (0.43)

66 (2.60)

U

V

u

v

PE

Monitor

ALM

A2
A1

C

Surge

Side

Protect

Side

4 – M4 SLOT

 

MOUNTING REQUIREMENTS  unit: mm (inch)

75 (2.95)

77 (3.03)

50 (1.97)

75 (2.95)

77 (3.03)

4 – M4 SLOT

90 (3.54) min.