EM-8155  Rev.2  P. 3 / 4

TERMINAL CONNECTIONS

Connect the unit as in the diagram below.

 

CONNECTION DIAGRAM

MDJST

6

5

4

3

+

4 – 20mA DC

MMAJ-100

V

U

v

u

100V AC

V

U

G

G

PE

A2

A1

*

1. Sections enclosed with broken line are applicable for “alarm 

      output” option.  
      The schematic shows the relay contact status of a thermal trip 
      or power off.

*

2. Be sure to make a cross-wire.  If the protected device has no 

      earth terminal, earth only the MMAJ.

*

2

Protected Device

A MCCB
must be installed.

MCCB

*

1

C

 

EARTHING

M-RESTER

PROTECTED

DEVICE

G

PE (G)

CROSSOVER WIRE

EARTHING

(100 ohms or less)

A crossover wire between M-RESTER and earth or the 

metallic housing of device is required for protection.

DERATING CURVE

100

50

0

-5 0

20

40

60

55

20A

30A

10A

Ambient Air Temperature (°C)

Load Rate (%)

WIRING

 

LEADWIRES

Conductor cross-section area: 5.5 mm

2

 minimum for U, V 

and PE lines.  However, a local industrial standard require-
ment for wiring should take precedence.  
The wire length should ideally be less than 0.5 meters.  Ex-
tra long wires should not be bundled in coils, but be cut to 
the minimum required length.

 

SOLDERLESS TERMINAL

Applicable ring tongue terminal without insulation sleeve 
is as indicated below.  Spade tongue terminal must conform 
with the ring type size.
In order to ensure IP20 protection (IEC 60529) with a sol-
derless terminal, cover the terminal with a insulation cap  
to prevent direct touching by a hand.

F

d : M4 use
B 

 11.0 mm

F 

≥ 

5.5 mm

(

F 

≥ 

7 mm 

 for sharing terminals)
T 

≤ 

1.5 mm

• Applicable Solderless Terminal Size

diameter 

d

B

T

 

TORQUE

Tighten the screw terminals securely.  Maximum allowable 
torque is of 1.2 N·m.

ALARM OUTPUT

The power supply voltage is continuously applied to the in-
corporated discharge element (zinc oxide element).  Degrad-
ed element is automatically separated from the power lines 
for safety to prevent overheating caused by leakage current.
Optional SPDT relay output is available to alert when the 
thermal breaker has separated the discharge element from 
the power supply circuit.
If the alarm output should be transmitted remotely via 
outdoor cables, a surge protector for signal line is required. 
Choose a circuit breaker with an alarm output.  Configure a 
logical addition sequence so that the alarm trips when both 
or either of the M-RESTETR or the breaker alarm trips.

 

RELAY SPECIFICATIONS

Alarm output: The SPDT relay trips when the thermal 
breaker operates and/or power source shutdown.
Rated load: 250V AC @1A (resistive load)
     

 

  24V DC @1A (resistive load)

OUTPUT 

TERMINAL

NORMAL

THERMAL BREAKER OPERATING OR 

POWER OFF

A1 – C

Open

Close

A2 – C

Close

Open

 

CONNECTION

Terminal: Tension clamp
Applicable wire size: 0.33 to 1.5 mm

2

 ( 6 – 7 mm exposed)