EM-8155  Rev.2  P. 4 / 4

CHECKING

 

WIRING

• Make sure that wiring is done as instructed in the con-

nection diagram.

• Make sure that the Earth terminal is connected to the 

metallic housing of protected device.

• Make sure that the Earth terminal is connected to earth.

MAINTENANCE

Even lightning in remote locations could induce surges 
without our knowledge.  Regular checking of the surge pro-
tector is important to find degradations in early stage, be-
fore and after the storm seasons, and whenever you experi-
ence a strong lightning storm.
DO NOT attempt checking or replacing the surge protector 
during a thunderstorm for safety.
Checking procedure is as explained below. 

 

MONITOR LED & ALARM

Configure the state of the monitor LED and the alarm out-
put with the power voltage supplied.  Replace in case of fail-
ure/breakdown.

MONITOR 

LED

ALARM OUTPUT

A1 – C

A2– C

Normal

ON

Open

Close

Failure/ Power OFF

OFF

Close

Open

 

SIMPLE CHECK

The alarm output or the monitor LED could be broken even 
with no indication.  The steps below explain a simple proce-
dure to check it.
1. Remove all wiring connected to the M-RESTER.
2. Confirm there is no conduction across the terminals indi-
cated below, with a 100/125 V DC insulation tester.

TERMINALS

DUE RESULT

U – PE

≥ 10MΩ

V – PE

3. Check with a 1000 V DC insulation tester across the ter-
minals indicated below and confirm it discharges.

TERMINALS

DUE RESULT

U – PE

≤ 2MΩ

V – PE

4. Turn on the power supply with no load and measure the 
current flowing into the M-RESTER.

MODEL

DUE RESULT

MMAJ-100xxY

≤ 6mA

MMAJ-200xxY
MMAJ-100xxA

≤ 20mA

MMAJ-200xxA

If any of the above tests shows negative, replace the M-
RESTER.