manualshive.com logo in svg
background image

MODEL: M2LMS

Super-mini Signal Conditioners Mini-M Series

LIMITER

Functions & Features
• Prevents DC output signals from going above or below
preset values
• High and low limits independently adjustable from -10.0 %
to +105 %
• Easy high/low limit setting with the front digital display
• CE marking
• UL approval

Typical Applications
• Protecting the receiving instrument which could
malfunction with an overscale input
• Securing the minimum fuel flow in a combustion control
loop

Model

23 (.91)

76

(2.99)

mm (inch)

124

(4.88)

MODEL: M2LMS–[1][2]–[3][4]

ORDERING INFORMATION

• Code number: M2LMS-[1][2]-[3][4]
 Specify a code from below for each [1] through [4].
 (e.g. M2LMS-6A-M2/CE/Q)
• Special input and output ranges (For codes Z & 0)
• Specify the specification for option code /Q
  (e.g. /C01/S01)

[1] INPUT

Current

A: 4 – 20 mA DC (Input resistance 250 Ω)
A1: 4 – 20 mA DC (Input resistance 50 Ω)
B: 2 – 10 mA DC (Input resistance 500 Ω)
C: 1 – 5 mA DC (Input resistance 1000 Ω)
D: 0 – 20 mA DC (Input resistance 50 Ω)
E: 0 – 16 mA DC (Input resistance 62.5 Ω)
F: 0 – 10 mA DC (Input resistance 100 Ω)
G: 0 – 1 mA DC (Input resistance 1000 Ω)
H: 10 – 50 mA DC (Input resistance 100 Ω)
J: 0 – 10 μA DC (Input resistance 1000 Ω)

K: 0 – 100 μA DC (Input resistance 1000 Ω)
GW: -1 – +1 mA DC (Input resistance 1000 Ω)
FW: -10 – +10 mA DC (Input resistance 100 Ω)
Z: Specify current (See INPUT SPECIFICATIONS)

Voltage

1: 0 – 10 mV DC (Input resistance 10 kΩ min.)
15: 0 – 50 mV DC (Input resistance 10 kΩ min.)
16: 0 – 60 mV DC (Input resistance 10 kΩ min.)
2: 0 – 100 mV DC (Input resistance 100 kΩ min.)
3: 0 – 1 V DC (Input resistance 1 MΩ min.)
4: 0 – 10 V DC (Input resistance 1 MΩ min.)
5: 0 – 5 V DC (Input resistance 1 MΩ min.)
6: 1 – 5 V DC (Input resistance 1 MΩ min.)
4W: -10 – +10 V DC (Input resistance 1 MΩ min.)
5W: -5 – +5 V DC (Input resistance 1 MΩ min.)
0: Specify voltage (See INPUT SPECIFICATIONS)

[2] OUTPUT

Current

A: 4 – 20 mA DC (Load resistance 750 Ω max.)
B: 2 – 10 mA DC (Load resistance 1500 Ω max.)
C: 1 – 5 mA DC (Load resistance 3000 Ω max.)
D: 0 – 20 mA DC (Load resistance 750 Ω max.)
E: 0 – 16 mA DC (Load resistance 900 Ω max.)
F: 0 – 10 mA DC (Load resistance 1500 Ω max.)
G: 0 – 1 mA DC (Load resistance 15 kΩ max.)
Z: Specify current (See OUTPUT SPECIFICATIONS)

Voltage

1: 0 – 10 mV DC (Load resistance 10 kΩ min.)
2: 0 – 100 mV DC (Load resistance 100 kΩ min.)
3: 0 – 1 V DC (Load resistance 1000 Ω min.)
4: 0 – 10 V DC (Load resistance 10 kΩ min.)
5: 0 – 5 V DC (Load resistance 5000 Ω min.)
6: 1 – 5 V DC (Load resistance 5000 Ω min.)
4W: -10 – +10 V DC (Load resistance 10 kΩ min.)
5W: -5 – +5 V DC (Load resistance 5000 Ω min.)
0: Specify voltage (See OUTPUT SPECIFICATIONS)

[3] POWER INPUT

AC Power

M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
(90 – 264 V for UL)

DC Power

R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
R2: 11 – 27 V DC
(Operational voltage range 11 – 27 V, ripple 10 %p-p max.)
(Select ‘/N’ for ‘Standards & Approvals’ code.)
P: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Содержание Mini-M Series

Страница 1: ...k min 16 0 60 mV DC Input resistance 10 k min 2 0 100 mV DC Input resistance 100 k min 3 0 1 V DC Input resistance 1 M min 4 0 10 V DC Input resistance 1 M min 5 0 5 V DC Input resistance 1 M min 6 1...

Страница 2: ...nput resistance value for code Z DC Voltage 30 30 V DC Minimum span 3 mV Offset Max 1 5 times span Input resistance Span 3 10 mV 10 k Span 10 100 mV 10 k Span 0 1 1 V 100 k Span 1 V 1 M OUTPUT SPECIFI...

Страница 3: ...hen the set value is in positive range green when in negative range The high limit is factory set to 100 How to Set Low Limit Turn the High Low Limit Selector C to the bottom The High Low Limit Displa...

Страница 4: ...Z 1 Low Drift Amplifier Output Driver OUTPUT 4 5 8 9 12 U V POWER 13 14 Input shunt resistor attached for current input INPUT R Digital Computation UP DOWN SW HI LO LIMIT SELECTOR Hi Lo Limit Display...

Страница 5: ...must be mounted inside a panel The equipment must be installed such that appropriate clearance and creepage distances are maintained to con form to CE UL requirements Failure to observe these re quire...

Страница 6: ...ta sheet When the output is out of tolerance recalibrate the unit according to the ADJUST MENT PROCEDURE explained earlier FRONT PANEL CONFIGURATION How to Set High Limit Turn the High Low Limit Selec...

Страница 7: ...70 5 2 78 86 7 3 41 7 3 29 15 59 6 23 59 2 32 DIN RAIL 35mm wide 4 16 8 M3 SCREW 72 2 83 23 91 2 4 2x5 17x 20 MTG HOLE 6 24 deep 116 7 4 59 When mounting no extra space is needed between units 1 4 8...

Отзывы: