TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the con-
nection diagram on the side of the unit.
When an input resistor is provided with the module, attach 
it together with input wiring to the input screw terminals.

CHECKING

1)  Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2)  Power input voltage:  Check voltage across the terminal 

13 – 14 with a multimeter.

3)  Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

4)  Output:    Check  that  the  load  resistance  meets  the  de-

scribed specifications.

ADJUSTMENT PROCEDURE

This  unit  is  calibrated  at  the  factory  to  meet  the  ordered 
specifications,  therefore  you  usually  do  not  need  any  cali-
bration.
For matching the signal to a receiving instrument or in case 
of regular calibration, adjust the output as explained in the 
following.

 HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.
1)  ZERO:  Apply 0% input and adjust output to 0%.
2)  SPAN:  Apply 100% input and adjust output to 100%.
3)  Check ZERO adjustment again with 0% input.
4)  When  ZERO  value  is  changed,  repeat  the  above  proce-

dure 1) – 3).

MAINTENANCE

Regular calibration procedure is explained below:

 CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%,  75%  and  100%  input  signal.    Check  that  the  output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of 
tolerance,  recalibrate  the  unit  according  to  the “ADJUST-
MENT PROCEDURE” explained earlier.

 FRONT PANEL CONFIGURATION

• How to Set High Limit

Turn the High/Low Limit Selector (C) to the top.
The  High/Low  Limit  Display  (B)  shows  the  current  high 
limit (-10.0 – +105%).  Press UP/DOWN Control (D) until 
the display shows a desired set value.
The Polarity Indicator LED (A) is red when the set value is 
in positive range, green when in negative range.
The high limit is factory set to 100%.

• How to Set Low Limit

Turn the High/Low Limit Selector (C) to the bottom.
The High/Low Limit Display (B) shows the current low lim-
it (-10.0 – +105%).  Press UP/DOWN Control (D) until the 
display shows a desired set value.
The Polarity Indicator LED (A) is red when the set value is 
in positive range, green when in negative range.
The low limit is factory set to 0%.

INSTALLATION

Loosen the fixing screw at the front of the unit in order to 
separate the body from the base socket.

 DIN RAIL MOUNTING

Set the base socket so that 
its  DIN  rail  adaptor  is  at 
the  bottom.    Position  the 
upper hook at the rear side 
of  base  socket  on  the  DIN 
rail and push in the lower.  
When removing the socket, 
push  down  the  DIN  rail 
adaptor  utilizing  a  minus 
screwdriver and pull.

 WALL MOUNTING

Refer  to  “EXTERNAL  DI-
MENSIONS.”

(C) High/Low Limit Selector

The front cover cannot be turned open by 180 deg. 
when there is no extra space between units.

(A) Polarity Indicator LED

(B) High/Low Limit Display

(E) Zero Adj.

(F) Span Adj.

(D) UP/DOWN Control

Top: High Limit
Bottom: Low Limit

1

4

+

*

*

Input shunt resistor attached for current input.

INPUT

R

+

OUTPUT

9

12

U(+)

V(–)

POWER

13

14

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Содержание Mini-M Series

Страница 1: ...k min 16 0 60 mV DC Input resistance 10 k min 2 0 100 mV DC Input resistance 100 k min 3 0 1 V DC Input resistance 1 M min 4 0 10 V DC Input resistance 1 M min 5 0 5 V DC Input resistance 1 M min 6 1...

Страница 2: ...nput resistance value for code Z DC Voltage 30 30 V DC Minimum span 3 mV Offset Max 1 5 times span Input resistance Span 3 10 mV 10 k Span 10 100 mV 10 k Span 0 1 1 V 100 k Span 1 V 1 M OUTPUT SPECIFI...

Страница 3: ...hen the set value is in positive range green when in negative range The high limit is factory set to 100 How to Set Low Limit Turn the High Low Limit Selector C to the bottom The High Low Limit Displa...

Страница 4: ...Z 1 Low Drift Amplifier Output Driver OUTPUT 4 5 8 9 12 U V POWER 13 14 Input shunt resistor attached for current input INPUT R Digital Computation UP DOWN SW HI LO LIMIT SELECTOR Hi Lo Limit Display...

Страница 5: ...must be mounted inside a panel The equipment must be installed such that appropriate clearance and creepage distances are maintained to con form to CE UL requirements Failure to observe these re quire...

Страница 6: ...ta sheet When the output is out of tolerance recalibrate the unit according to the ADJUST MENT PROCEDURE explained earlier FRONT PANEL CONFIGURATION How to Set High Limit Turn the High Low Limit Selec...

Страница 7: ...70 5 2 78 86 7 3 41 7 3 29 15 59 6 23 59 2 32 DIN RAIL 35mm wide 4 16 8 M3 SCREW 72 2 83 23 91 2 4 2x5 17x 20 MTG HOLE 6 24 deep 116 7 4 59 When mounting no extra space is needed between units 1 4 8...

Отзывы: