M1EXV-4
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6040-B Rev.2 P. 33 / 37
[295-001] Ch3 User’s table linearization
SETTING VALUE DESCRIPTION
INITIAL VALUE
Disable
Disable Linearization
Disable
Enable
Enable Linearization
When ‘Enable’ is selected, input is converted to output based on a user specified table.
[295-002] Ch3 Number of points
Set the number of points for the user’s table.
Settable range: 2 – 111 points.
Initial value: 2
[295-003 to 295-224] Ch3 Table
Conversion is performed based on the user specified table in which values of X corresponding to input (unit: %) and values of
Y corresponding to output (unit: %) are paired, respectively.
The table is searched for an X value that matches the input to be converted and a Y value paired with the X value is outputted.
X values and Y values can be set within the range of -5 to +105 (%).
X values need to be set in ascending order from X001. Otherwise conversion cannot be correctly performed.
Initial value: X001 -5.00
Y001 -5.00
X002 105.00
Y002 105.00
[E.g.]
X001
105%
105%
-5%
Y005
Input %
Output %
Y004
Y003
Y002
Y001
-5%
X003
X002
X004 X005
When the input to be converted does not match any X value in the table, two X values which are closest to the input in positive
and negative directions are selected and linearly interpolated, thereby obtaining a Y value to be outputted.
Xn
Xn+1
Yn
Yn+1
Input %
Output %