• Parameters
MODE
ITEM
SETTING PARAMETER
RANGE
UNIT
INITIAL VALUE
Ch3 Setting
01
Lockout setting
Lock / Unlock
–
Lock
202
Ch3 Enable
Disable / Enable
–
Enable
211
Ch3 Input range
0 – 20 mA
-5 – +5 V
-10 – +10 V
–
-5 – +5 V
212
Ch3 0% Input setting
0.000 – 19.000
-5.000 – 4.750
-10.000 – 9.000
mA
V
V
1.000
213
Ch3 100 % Input setting
1.000 – 20.000
-4.750 – 5.000
-9.000 – 10.000
mA
V
V
5.000
214
Ch3 0 % Input scaling
-99999 – 999999
–
0.00
215
Ch3 100 % Input scaling
-99999 – 999999
–
100.00
216
Ch3 Input decimal point
No decimal point
The number of decimal places: 1 – 5
–
2 places of decimals
217
Ch3 Unit (INP Scaling)
Choose from 68 types
–
%
261
Ch3 Output range
0 – 20 mA
-5 – +5 V
-10 – +10 V
–
0 – 20 mA
262
Ch3 0 % Output setting
0.000 – 19.000
-5.000 – 4.750
-10.000 – 9.000
mA
V
V
4.000
263
Ch3 100 % Output setting
1.000 – 20.000
-4.750 – 5.000
-9.000 – 10.000
mA
V
V
20.000
271
Ch3 Filter time constant
0 – 30
sec.
0
281
Ch3 Input zero fine adjust
-5.000 – 5.000
%
0.000
282
Ch3 Input span fine adjust
95.000 – 105.000
%
100.000
291
Ch3 Output zero fine adjust
-5.000 – 5.000
%
0.000
292
Ch3 Output span fine adjust
95.000 – 105.000
%
100.000
295
Ch3 User’s table linearization Cancel / Set
–
Cancel
298
Ch3 Loop test
-5.00 – 105.00
%
Cancel
[01] Lockout setting
Enable / disable Lockout setting.
SETTING VALUE DESCRIPTION
INITIAL VALUE
Lock
Enable Lockout setting
Lock
Unlock
Disable Lockout setting
When Lockout setting is enabled, it is possible to shift to
each setting mode and confirm the setting value of each
setting parameter item. Each parameter item display in-
dicates ‘DATA (Locked)’ when set to ‘Lock’, and indicates
‘DATA’ when set to ‘Unlock’.
[202] Ch3 Enable
Enable / disable Ch3.
No output signal or present value is displayed for the disa-
bled channel in Measuring Mode.
SETTING VALUE DESCRIPTION
INITIAL VALUE
Disable
Disable Ch3
Enable
Enable
Enable Ch3
Even when Ch3 is disabled, parameter settings for Ch3 can
be performed.
[211] Ch3 Input range
Set the input range.
SETTING VALUE DESCRIPTION
INITIAL VALUE
0 – 20 mA
Input: 0 – 20 mA DC
-5 – +5 V
-5 – +5 V
Input: -5 – +5 V DC
-10 – +10 V
Input: -10 – +10 V DC
When the input range is changed, turn the power off, and
change the connection to the input terminal of the unit ac-
cordingly. Note that input setting values are changed to the
initial values.
[212] Ch3 0 % Input setting
Set the 0 % input setting value.
Setting range differs according to input range.
INPUT RANGE
SETTING RANGE MIN. SPAN INITIAL VALUE
0 – 20 mA
0.00 – 19.00
1.00
4.00
-5 – +5 V
-5.000 – 4.750
0.250
1.000
-10 – +10 V
-10.000 – 9.000
1.000
-10.000
Set as follows.
[212] 0 % input setting < [213] 100 % input setting
[213] Ch3 100 % Input setting
Set the 100 % input setting value.
Setting range differs according to input range.
INPUT RANGE
SETTING RANGE MIN. SPAN INITIAL VALUE
0 – 20 mA
1.00 – 20.00
1.00
20.00
-5 – +5 V
-4.750 – 5.000
0.250
5.000
-10 – +10 V
-9.000 – 10.000
1.000
10.000
Set as follows.
[212] 0 % input setting < [213] 100 % input setting
[214] Ch3 0 % Input scaling
Set the display value of 0 % input setting.
SETTING RANGE
INITIAL VALUE
-99999 – 999999
0.00
[215] Ch3 100 % Input scaling
Set the display value of 100 % input setting.
SETTING RANGE
INITIAL VALUE
-99999 – 999999
100.00