[316] Ch4 Input decimal point
Set the decimal point position of [314] 0 % and [315] 100 %
input scaling.
SETTING VALUE
DESCRIPTION
INITIAL VALUE
oooooo
Decimal point: None
2 places of
decimals
ooooo.o
No. of decimal places: 1
oooo.oo
No. of decimal places: 2
ooo.ooo
No. of decimal places: 3
oo.oooo
No. of decimal places: 4
o.ooooo
No. of decimal places: 5
[317] Ch4 Unit (INP scaling)
Set the unit to display input scaling.
Available units are following 68 types.
DC, AC, mV, V, kV, μA, mA, A, kA, mW, W, kW, var, kvar,
Mvar, VA, Hz, Ω, kΩ, MΩ, cm, mm, m, m/sec, mm/min,
cm/min, m/min, m/h, m/s
2
, inch, L, L/s, L/min, L/h, m
3
,
m
3
/sec, m
3
/min, m
3
/h, Nm
3
/h, N∙m, N/m
2
, g, kg, kg/h, N, kN,
Pa, kPa, MPa, t, t/h, °C, °F, K, %RH, J, kJ, MJ, rpm, sec,
min, min
-1
, pH, %, ppm, deg, (blank), User
Selecting ‘User’ shifts to User’s unit setting display.
A unit can be created by using up to any 13 characters.*
1
Shift through characters using Up and Down buttons and
press Set button to select the character.
While setting, pressing Mode button deletes one character,
and holding down Mode button for ≥ 2 seconds discards the
set value, which returns to the value before setting change.
Hold down Set button for ≥ 2 seconds to save the setting and
return to the setting display of [317] Unit (INP Scaling).
If turning power off while setting, the display returns to the
setting display of [317] Unit (INP Scaling).
(The set value is discarded).
The unit is displayed in [Ch4 INPUT (Scaling)] in Measur-
ing mode.
Initial value: %
*1. Settable characters
0
−
9 A
−
Z a
−
z ! ” # $ % & ’ ( )
= - + * ^ | @ ` [ ] { } ; : < > ?
_ , . /
[361] Ch4 Output range
Set the range of output signal of the unit.
SETTING VALUE DESCRIPTION
INITIAL VALUE
0 – 20 mA
Output: 0 – 20 mA DC
0 – 20 mA
-5 – +5 V
Output: -5 – +5 V DC
-10 – +10 V
Output: -10 – +10 V DC
[362] Ch4 0 % Output setting
Set the 0 % output setting value.
OUTPUT RANGE SETTING RANGE MIN. SPAN INITIAL VALUE
0 – 20 mA
0.000 – 19.000
1.000
4.000
-5 – +5 V
-5.000 – 4.750
0.250
-5.000
-10 – +10 V
-10.000 – 9.000
1.000
-10.000
Set as follows.
[362] 0 % output setting < [363] 100 % output setting
[363] Ch4 100 % Output setting
Set the 100 % output setting value.
OUTPUT RANGE SETTING RANGE MIN. SPAN INITIAL VALUE
0 – 20 mA
1.000 – 20.000
1.000
20.000
-5 – +5 V
-4.750 – 5.000
0.250
5.000
-10 – +10 V
-9.000 – 10.000
1.000
10.000
Set as follows.
[362] 0 % output setting < [363] 100 % output setting
[371] Ch4 Filter time constant
Set filter time constant of the first order lowpass filter.
The first order lowpass filter is available with setting time.
When this parameter is set to ‘0’, the first order lowpass
filter is not available (Response time: ≤ 0.5 sec. (0
➝
90 %)).
The setting time constant is the time taken for output to fol-
low up to about 63 %, when input varies from 0 % to 100 %.
Settable range: 0 – 30 seconds.
Initial value: 0
[381] Ch4 Input zero fine adjust
Perform fine adjustment of input signal.
Settable range: -5.000 – +5.000 %.
Initial value: 0.000
[382] Ch4 Input span fine adjust
Perform fine adjustment of input signal.
Settable range: 95.000 – 105.000 %.
Initial value: 100.000
[391] Ch4 Output zero fine adjust
Perform fine adjustment of output signal.
Settable range: -5.000 – +5.000 %.
Initial value: 0.000
[392] Ch4 Output span fine adjust
Perform fine adjustment of output signal.
Settable range: 95.000 – 105.000 %.
Initial value: 100.000